Information Notice No. 85-90: Use of Sealing Compounds in an Operating System
SSINS No.: 6835 IN 85-90 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C., 20555 November 19, 1985 Information Notice No. 85-90: USE OF SEALING COMPOUNDS IN AN OPERATING SYSTEM Addressees: All nuclear power reactor facilities holding an operating license (OL) or a construction permit (CP). Purpose: This information notice is provided to alert recipients of a potentially significant problem pertaining to the injection of a sealing compound into an operating system. It is expected that recipients will review the information for applicability to their facilities and consider actions, if appropriate, to preclude a similar problem occurring at their facilities. However, suggestions contained in this information notice do not constitute NRC requirements; therefore, no specific action or written response is required. Description of Circumstances: Catawba Nuclear Station Unit 1 has a closed-loop component cooling water system (CCWS) with equipment receiving cooling flow arranged in two parallel circuits (trains). Each train provides cooling water to one train of redundant engineered safety equipment (essential header). In addition, cooling water for the nonessential header can be provided by branches from either train of the CCWS. The nonessential header is isolated from both essential headers by a 20-inch, butterfly-type, motor-operated valve in the branch for each train (See Figure 1). In May 1985, operations personnel identified that there was excessive leakage past the seats of both of the 20-inch butterfly valves. An attempt was made to shut down train B and the nonessential header to allow for work on the butterfly valve in train B. However, because of the excessive valve seat leakage from train A, train B could not be depressurized. A decision was made to inject a sealing compound into the branch piping of the operating train (train A) immediately upstream of the butterfly valve. Because the valve was located in a section of branch piping just downstream from a dead leg (approximately a 5-foot drop in piping), the conjecture was that the sealing compound would migrate to the leaking valve seat area, thus stopping the leak without being carried to any component being cooled by the main run of train A. 8511150120 . IN 85-90 November 19, 1985 Page 2 of 3 To inject the sealing compound, holes were drilled in the valve body at an angle so that the injection would be on the upstream side of the valve and below the dead leg. Sealing compound of various consistencies was then injected into this area. A total of 146 boxes (2 pounds per box) was injected into this area without stopping the leakage. Following this unsuccessful effort, a mechanical plugging technique was used to successfully plug the A train branch line downstream of the valve. The leaking butterfly valves were then removed and replaced sequentially. Also replaced during this time was a 1-inch drain line and valve located between the two 20-inch butterfly valves. The 1-inch line and valve had become plugged with sealing compound that had passed the seat of the butterfly valve. In the course of replacing the valves, it was found that most of the sealing compound settled as a large plug just upstream of the 20-inch A train valve, but this plug had not sealed the leak in the valve. Subsequent to replacement of the two 20-inch butterfly valves and the smaller piping, the CCWS was returned to service. With the system operating, higher than normal differential pressures were identified on some train A components. Further, the required cooling water flow could not be achieved. As a result of these findings, various heat exchangers were inspected and cleaned. It was found that a small amount of sealing compound had gone back up the dead leg of the branch and into the main run piping. Sealing compound was found in varying amounts in these heat exchangers. The train A coolant charging pump motor cooler had approximately 2 pounds of sealing compound (maximum amount identified) and some coolers had none. Other problems associated with the use of sealing compounds have occurred in the past. Information Notice No. 82-06, "Failure of Steam Generator Primary Side Manway Closure Studs," was issued March 12, 1982 and addressed another situation where the use of sealants to stop a leak may have contributed to other unforeseen problems. In that situation, the sealing compound was injected using a procedure which essentially created an enclosure around the bolt circle between the flanges. This resulted in an autoclave type of atmosphere where corrodents from the coolant could concentrate and contribute to degradation of the flange bolting. The results of tests sponsored by the Electric Power Research Institute (EPRI) on sealants and on line sealing procedures also show additional problems that may develop with the use of sealants. These results are published in EPRI NP-3111, "Testing and Evaluation of On-Line Leak Sealing Methods." Licensees are reminded that ANSI/ANS-3.2-1982, "Administrative Controls and Quality Assurance for the Operational Phase of Nuclear Power Plants," part 5.2.71, Maintenance Programs, requires that "planning for maintenance shall include evaluation of the use of special processes, equipment and materials in performance of the task, including assessment of potential hazards to personnel and equipment." . IN 85-90 November 19, 1985 Page 3 of 3 No specific action or written response is required by this information notice. If you have any questions about this matter, please contact the Regional Administrator of the appropriate regional office or this office. Edward L. Jordan Director Division of Emergency Preparedness and Engineering Response Office of Inspection and Enforcement Technical Contact: William F. Anderson, IE (301) 492-4819 Attachments: 1. Figure 1, "Component Cooling Water Header Interconnection" 2. List of Recently Issued IE Information Notices
Page Last Reviewed/Updated Tuesday, March 09, 2021
Page Last Reviewed/Updated Tuesday, March 09, 2021