Information Notice No. 85-73: Emergency Diesel Generator Control Circuit Logic Design Error
SSINS No.: 6835
IN 85-73
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF INSPECTION AND ENFORCEMENT
WASHINGTON, D.C. 20555
August 23, 1985
Information Notice No. 85-73: EMERGENCY DIESEL GENERATOR CONTROL
CIRCUIT LOGIC DESIGN ERROR
Addressees:
All nuclear power reactor facilities holding an operating license (OL) or a
construction permit (CP).
Purpose:
This information notice is to alert recipients of a potentially significant
emergency diesel generator (EDG) control logic error that could prevent
transfer to the emergency bus while the EDG is in the "maintenance shutdown"
mode. It is expected that recipients will review the information for
applicability to their facilities and consider actions, if appropriate, to
preclude a similar problem occurring at their facilities. However,
suggestions contained in this information notice do not constitute NRC
requirements; therefore, no specific action or written response is required.
Description Of Circumstances:
According to the design, the EDGs at Rancho Seco Nuclear Power Generating
Station enter the maintenance shutdown control mode whenever they are
normally shut down from the control room or the remote EDG control panel. On
June 1, 1985, the plant was shut down for refueling, an EDG was in the
maintenance shutdown control mode after being secured from an operational
condition (idling at 600 rpm with the output breaker open), when an
emergency bus was de-energized for planned work on a parallel bus. This
created an undervoltage condition equivalent to a loss of offsite power
(LOOP) on the emergency bus. The diesel generator sped up to the design
speed but the EDG output breaker continuously cycled open and closed,
thereby rendering the EDG set inoperable. Investigation by the licensee
indicates that the cycling of the EDG output, breaker was the result of a
design error in the EDG control circuit logic. According to the licensee,
the design "deficiency affects proper response of the EDG set when it is
operating in the maintenance shutdown control mode. Normal surveillance
testing would not discover the control circuit design error because
surveillance is not done in the maintenance shutdown control mode. The June
1, 1985 event at Rancho Seco represents the first time in the life of the
plant that an undervoltage signal occurred with an EDG in the maintenance
shutdown control mode.
8508210321
.
IN 85-73
August 23, 1985
Page 2 of 2
When an EDG is secured from operation, the control circuit logic places it
in the maintenance shutdown control mode. In this mode, the control logic
opens its output breaker and reduces its speed from,900 to 600 rpm. The EDG
then idles at 600 rpm for 15 minutes before coasting down to rest.
If a LOOP should occur while an EDG is in the maintenance shutdown control
mode, the undervoltage signal causes it to speed back up to 900 rpm and to
close its output breaker. This would cause the undervoltage signal to drop
out.
However, the maintenance shutdown control mode does not drop out for 30
seconds after the receipt of the undervoltage signal because of the control
circuit design error. Thus, the maintenance shutdown control logic senses
that the EDG output breaker is closed, opens the breaker, and resets the
15-minute timer for the maintenance shutdown control mode. As soon as the
EDG output breaker opens, the undervoltage signal recurs and the EDG output
breaker closes in response to the LOOP. The EDG output breaker continues to
cycle open and closed as this process repeats itself. At Rancho Seco, this
control circuit logic design error has been corrected by installing a relay
to de-energize the maintenance shutdown control logic immediately upon
receipt of an undervoltage signal. The Rancho Seco plant utilizes General
Motors (GM) Model 20-465-E4 diesel generators with a 2750 kw nameplate
rating. According to the licensee, the design error was in the interface
provided by the Architect-Engineer (Bechtel) to the shutdown control logic
provided by GM. Bechtel has advised the NRC that the Rancho Seco diesel
generator control logic is unique and other plants designed by them are not
affected.
No specific action or written response is required by this information.
notice. If you have any questions about this matter, please contact the
Regional Administrator of the appropriate regional office or this office.
Edward L. Jordan Director
Division of Emergency Preparedness
and Engineering Response
Office of Inspection and Enforcement
Technical Contact: W. Swenson, NRR
(301) 492-7876
R. Singh, IE
(301) 492-8985
Attachment: List of Recently Issued Information Notices
Page Last Reviewed/Updated Tuesday, March 09, 2021