Information Notice No. 84-09: Lessons Learned from NRC Inspections of Fire Protection Safe Shutdown Systems (10 CFR 50, Appendix R)

                                                           SSINS No.:  6835 
                                                           IN 84-09        

                               UNITED STATES 
                       NUCLEAR REGULATORY COMMISSION 
                    OFFICE OF INSPECTION AND ENFORCEMENT 
                           WASHINGTON, D.C. 20555 
                                     
                             February 13, 1984 

Information Notice No. 84-09:   LESSONS LEARNED FROM NRC INSPECTIONS OF 
                                   FIRE PROTECTION SAFE SHUTDOWN SYSTEMS (10
                                   CFR 50, APPENDIX R) 

Addressees: 

All nuclear power reactor facilities holding an operating license (OL) or 
construction permit (CP). 

Purpose: 

This Information Notice is provided as guidance for power reactor facilities
conducting analyses and/or making modifications to implement requirements of
10 CFR 50, Appendix R. It is expected that licensees will review this 
information for applicability to their activities. No specific action or 
response is required at this time. 

Description of Circumstances: 

A number of inspections to evaluate licensee implementation of the 
requirements of 10 CFR 50, Appendix R have been conducted at power reactor 
facilities licensed before January 1, 1979. Significant items of 
noncompliance were found at a number of facilities. As a result of these 
inspections, the NRC staff has prepared the enclosed Supplemental Guidance 
on 10 CFR 50 Appendix R Fire Protection Safe Shutdown Requirements. 

The staff intends to conduct workshops on fire protection safe shutdown 
requirements at locations near each of the NRC's five Regional offices 
during the next two months. At these workshops, an overview of inspection 
results and associated lessons learned will be presented and participants 
will be provided with the opportunity to present specific questions 
concerning Appendix R requirements. Schedules and agenda for the regional 
workshops will be forwarded to all utilities with nuclear projects in the 
near future. 





8401190041  
.

                                                        IN 84-09           
                                                        February 13, 1984  
                                                        Page 2 of 2        

If you have any questions regarding this matter, please contact the Regional
Administrator of the appropriate NRC regional office or this office. 



                                   Edward L. Jordan, Director 
                                   Division of Emergency Preparedness 
                                     and Engineering Response 
                                   Office of Inspection and Enforcement 

Technical Contacts: L. E. Whitney, IE 
                    (301) 492-9668 

                    T. Wambach, NRR 
                    (301) 492-7072 

Attachments: 
1.   Supplemental Guidance on 10 CFR 50 Appendix R Fire Protection Safe
     Shutdown Requirements 
2.   List of Recently Issued IE Information Notices 
.

                                                        Attachment 1       
                                                        IN 84-09           
                                                        February 13, 1984  
                                                        Page 1 of 9        

              SUPPLEMENTAL GUIDANCE ON 10 CFR 50 APPENDIX R 
                FIRE PROTECTION SAFE SHUTDOWN REQUIREMENTS 

I.   Fire Areas 

At one facility inspected, the licensee's fire hazards analysis had not 
established fire areas. Therefore, in the absence of alternative means for 
safe shutdown in a separate fire area or approved exemptions, the redundant 
equipment within the plant was inspected for compliance with the separation 
requirements of Appendix R, Section III.G.2.  Significant items of 
noncompliance were identified at this facility with respect to separation of
redundant trains of systems and components. 

Footnote 3 in 10 CFR 50.48 directs attention to documents which provide 
basic fire protection guidance for nuclear power plants. One of these 
documents, Branch Technical Position Auxiliary Power Conversion System 
Branch BTP APCSB 9.5-1, "Guidelines for Fire Protection for Nuclear Power 
Plants," for new plants docketed after July 1, 1976, dated May 1976, defined 
a fire area as: 

     that portion of a building or plant that is separated from other 
     areas by boundary fire barriers (walls, floors, or roofs) with any 
     openings or penetrations protected with seals or closures having 
     a fire resistance rating equal to that of the barrier. 

"Supplementary Guidance on Information Needed for Fire Protection 
Evaluation," dated October 21, 1976, requested, as part of the fire hazards 
analysis, "plan and elevation views of the plant that show the plant as 
divided into distinct fire areas." Section III.G of Appendix R sets forth 
the requirements for the fire protection of safe shutdown capability on the 
basis of fire areas. 

Fire areas should be delineated in each facility's fire hazards analysis. 
NRC Generic Letter 83-33, dated October 19, 1983, restates NRC positions on 
Appendix R requirements regarding fire areas and the concept of "fire 
zones." 

II.  Fire Barrier Testing and Configuration 

At some of the facilities inspected, fire barriers (both walls and one-hour 
fire barriers) were installed without basis for their fire rating (such as 
U/L listing or testing conducted by a nationally recognized testing 
laboratory for the configuration used in the plant). Fire barriers installed
to meet the requirements of Section III.G.2 of Appendix R must have such a 
rating. Boundary fire barriers may have previous NRC acceptance documented 
in a Safety Evaluation Report. Some one-hour enclosures or wraps inspected 
have not been complete. Cable wraps which do not extend from fire barrier to
fire barrier cannot constitute a one-hour barrier. 
.

                                                          Attachment 1     
                                                          IN 84-09         
                                                          February 13, 1984 
                                                          Page 2 of 9      

III.  Protection of Equipment Necessary To Achieve Hot Shutdown 

At one facility, redundant pressurizer heater control and power cables were 
separated by a partial horizontal pyrocrete barrier suspended from the 
overhead. At the same facility, two auxiliary feedwater pumps were located 
adjacent to each other and separated by a partial steel missile shield 
coated on one side with fire-retardant material. The separation criteria of 
Appendix R, Section III.G.2, were not met in that the coated shield did not 
meet the definition of a fire barrier of BTP APCSB 9.5-1. No alternative 
means of feedwater supply was designated. 

At a second facility, redundant pressurizer heater load centers were located
within the same cabinet. At a third facility, redundant steamline isolation 
valves control cables for HPCI and RCIC pumps were located in close 
proximity without a fire rated barrier. 

Appendix R, Section III.G.1, requires that fire protection features shall be
provided for structures, systems, and components important to safe shutdown.
These features shall be capable of limiting fire damage so that one train of
systems necessary to achieve and maintain a hot shutdown condition from 
either the control room or emergency control station(s) is free of fire 
damage. 

Sections III.G.2 and III.G.3 specify four alternatives that may be 
implemented outside of primary containment to assure that one redundant 
train of equipment, cabling and associated circuits necessary to achieve and
maintain hot shutdown remains free of fire damage. The alternatives are: 

1.   Separation of redundant trains of equipment, cabling, and associated 
     circuits by a three-hour fire barrier. 

2.   Enclosure of redundant trains of equipment, cabling, and associated 
     circuits by a one-hour fire barrier with fire detection and automatic 
     fire suppression systems installed in the area. 

3.   Separation of redundant trains of equipment, cabling, and associated 
     circuits by a horizontal distance of 20 feet with no intervening 
     combustibles and with fire detection and automatic fire suppression 
     systems installed in the area. 

4.   Installation of alternative or dedicated shutdown capability 
     independent of the equipment, cabling, and associated circuits under 
     consideration, and installation of fire detection and fixed fire 
     suppression systems in the area containing this alternative or 
     dedicated shutdown capability. 

It should be noted that Sections III.G.2.d, e and f of Appendix R, provide 
additional options for the separation of redundant trains of equipment and 
cables within non-inerted containments. 
.

                                                          Attachment 1     
                                                          IN 84-09         
                                                          February 13, 1984 
                                                          Page 3 of 9      

In addition, a licensee may request and receive exemptions from the 
requirements of Appendix R, Section III.G, under the Appendix R review 
process. Such exemptions should be for configurations and/or procedures that
provide an equivalent level of safety to that provided by the four 
alternatives above. 

IV.  Licensee's Reassessment for Conformance with Appendix R 

Problems found during the inspections with respect to providing redundant 
hot shutdown capability appear to be indicative of inadequate reassessment 
of plant configuration by the licensees. Also, at each facility inspected, 
documentation was lacking to provide assurance that a comprehensive 
associated circuits analysis had been conducted for all fire areas. 

At one facility visited in FY 1983, the inspectors could find no evidence 
(direct or indirect) that a thorough engineering review had been conducted 
against the requirements of Appendix R. At most facilities visited, the 
analyses provided for inspector review were developed prior to the issuance 
of Appendix R. 

Two letters were sent by NRR to the licensees of plants licensed prior to 
January 1, 1979. These letters clearly stated the requirement for licensee 
reassessment to ensure compliance of Appendix R, Sections III.G, III.J, and 
III.O, regardless of previous reviews and approvals by the NRC (e.g., SERs 
issued during the BTP APCSB 9.5-1 review process). 

A November 24, 1980 letter from the Director, Division of Licensing, Office 
of Nuclear Reactor Regulation, to the above licensees states, in part: 

     The provisions of Appendix R that are applicable to the fire 
     protection features of your facility can be divided into two 
     categories. The first category consists of those provisions of the 
     Appendix that are required to be backfit in their entirety by the 
     new rule, regardless of whether or not alternatives to the specific 
     requirements of these Sections have been previously approved by the 
     NRC staff. These requirements are set forth in Sections III.G, Fire 
     Protection of Safe Shutdown Capability; III.J, Emergency Lighting; 
     and III.O, Oil Collection Systems for Reactor Coolant Pump. The 
     fire protection features of your facility must satisfy the specific 
     requirements of these three Sections by the dates established by 
     Paragraph 50.48(c), unless an exemption from the Appendix R 
     requirements is approved by the Commission. 

A February 20, 1981 letter from the Director, Division of Licensing, Office 
of Nuclear Reactor Regulation, to the above licensees states, in part: 

     Paragraph 50.48(b) of 10 CFR Part 50, which became effective on 
     February 17, 1981, requires all nuclear plants licensed to operate 
     prior to January 1, 1979 to meet the requirements of 
.

                                                        Attachment 1       
                                                        IN 84-09           
                                                        February 13, 1984  
                                                        Page 4 of 9        

     Sections III.G, III.J, and III.O of Appendix R to 10 CFR Part 50 
     regardless of any previous approvals by the Nuclear Regulatory 
     Commission (NRC) for alternative design features for those items. 
     This would require each licensee to reassess areas of the plant 
     where redundant trains of systems necessary to achieve and maintain 
     hot shutdown conditions are located within the same fire area to 
     determine whether the requirements of Section III.G.2 of Appendix 
     R are satisfied. If not the licensee must provide alternative 
     shutdown capability in conformance with Section III.G.3 or request 
     an exemption if there is some justifiable basis. 

The NRC expects that, when a reassessment has been performed at a facility, 
a documented record of this engineering activity would be available within 
the utility. The availability of documentation of (and personnel familiar 
with) a licensee's reassessment activities helps to confirm the licensee's 
methodology and subsequent implementation of reassessment results. 
Therefore, this documentation helps to confirm adequate licensee control of 
Appendix R reassessment activity. 

V.   Identification of Safe Shutdown Systems and Components 

At two facilities inspected, redundant systems and components necessary for 
safe shutdown (within the same fire area) were not listed or otherwise 
identified in the licensees' fire hazards analysis or associated 
documentation. 

At these facilities, the inspectors used the lists of required safe shutdown
systems provided in connection with the alternative shutdown analyses 
provided by the licensees in their original fire hazards analyses. At one of
these facilities, the licensee felt the list used was too restrictive (in 
that it did not include existing potentially redundant systems). At another 
facility, the licensee felt that the list used was too broad (in that the 
list contained systems that the licensee subsequently realized were not 
actually necessary for safe shutdown). This situation should not have 
occurred since identification of required safe shutdown systems for each 
area of the plant is a logical starting point for reassessment of areas 
where redundant trains are located. 

The systems and equipment needed for post-fire safe shutdown are those 
systems necessary to perform the shutdown function defined in Section III. L 
of Appendix R. These functions are reactivity control, reactor coolant 
makeup, reactor heat removal, process monitoring, and associated support 
functions. The acceptance criterion for systems performing these functions 
is also defined in Section III. L: 

     During the post-fire shutdown, the reactor coolant system process 
     variables shall be maintained within those predicted for a loss of 
     normal a.c. power, and the fission product boundary integrity shall 
     not be affected; i.e., there shall be no fuel clad damage, rupture 
     of any primary coolant boundary, or rupture of the containment 
     boundary. 
.

                                                          Attachment 1     
                                                          IN 84-09         
                                                          February 13, 1984 
                                                          Page 5 of 9      

These guidelines apply to the systems needed to satisfy both Section III.G 
and III.L of Appendix R. 

VI.  Combustibility of Electrical Cable Insulation 

At a number of facilities, findings of noncompliance were made because of 
the presence of insulated electrical cable between redundant trains of 
equipment necessary for safe shutdown. At one facility, the space between 
redundant electrical cabling at the internal and external containment 
electrical penetration areas was nearly filled with a high density of 
insulated electrical cabling. At another facility, four redundant trains of 
pressurizer heater control and/or power cables were routed in trays in the 
overhead of one room with numerous other cables and cable trays. 

Several comprehensive flammability tests conducted by the Electric Power 
Research Institute (EPRI NP-1200, EPRI EL-1263), Factory Mutual (Contract 
RP-1165-1), and Sandia National Laboratories (NUREG/CR-2431, among others) 
have shown that burning cable insulation represents a significant fire 
hazard. These tests were conducted on both IEEE-383 qualified and 
unqualified cable. While the qualified cable exhibited a tendency to ignite 
and propagate flame less rapidly, combustion of grouped cables continued at 
significant levels. In particular, grouped vertical cables which are not 
protected by a fire propagation retardant, such as metal tray covers or fire 
retardant coatings, can result in rapidly developing fires with high heat 
release rates. 

Section III.G.2.b of Appendix R requires redundant train "separation.. with 
no intervening combustibles...." The NRC staff position is that insulation 
of electrical cables, including those which are coated, should be considered
as intervening combustibles. 

VII. Detection and Automatic Suppression 

At one facility, redundant trains of safe shutdown equipment located within 
the same fire area were found to be separated by at least 20 feet of 
horizontal empty space (no intervening combustibles). Yet, because no 
general area automatic fire suppression system was installed, the area was 
found not to meet the separation requirements of Appendix R, Section III.G. 

NRC Generic Letter 83-33, dated October 19, 1983, restates detailed NRC 
positions on Appendix R requirements regarding detection and automatic 
suppression. 

At another facility, some automatic sprinkler systems were not installed in 
ceiling spaces occupied by obstructions such as ventilation equipment, cable
trays/conduit, etc. The effectiveness of these automatic sprinkler systems 
in extinguishing or suppressing fires in the overhead was therefore 
compromised. NFPA 13 should be referred to when determining sprinkler 
arrangement. 
.

                                                          Attachment 1     
                                                          IN 84-09         
                                                          February 13, 1984 
                                                          Page 6 of 9      

VIII.  Applicability of 10 CFR 50, Appendix R, Section III.L 

Some of the inspected licensees had not considered Section III.L of Appendix
R when attempting to meet Section III.G. The acceptance criteria for Section
III.G.3. are listed in Section III.L. Although 10 CFR 50.48(b) does not 
specifically include Section III.L with Sections III.G., J, and O of 
Appendix R as a requirement applicable to all power reactors licensed prior 
to January 1, 1979, the Appendix, read as a whole, and the Court of Appeals 
decision on the Appendix, Connecticut Light and Power, et al. v. NRC, 673 
F2d. 525 (D. C. Cir.), cert. denied (1982), does mean that Section III.L 
applies to the alternative safe shutdown option under Section III.G. 

IX.  Instrumentation Necessary for Alternative Shutdown 

At one facility inspected, hot shutdown source range neutron flux monitoring
capability could not be provided until approximately 12 hours subsequent to 
a postulated fire in the control room. At another facility inspected, no 
alternative hot shutdown source range neutron flux monitoring capability, 
cold leg temperature indication, or wide-range hot leg temperature 
indication was provided. 

Section III.L.1 of Appendix R requires that alternative shutdown capability 
achieve and maintain subcritical reactivity conditions in the reactor. 
Section III.L.2 requires provision for direct readings of the process 
variables necessary to perform and control the reactor shutdown function. 

The following lists provide the minimum monitoring capability the NRC staff 
considers necessary to achieve safe shutdown: 

                     Instrumentation Needed for PWRs 

a.   Pressurizer pressure and level.
b.   Reactor coolant hot leg temperature or exit core thermocouples, and 
     cold leg temperature.
c.   Steam generator pressure and level (wide range). 
d.   Source range flux monitor. 
e.   Diagnostic instrumentation for shutdown systems. 
f.   Level indication for all tanks used (e.g., CST). 

                     Instrumentation Needed for BWRs 

a.   Reactor water level and pressure.
b.   Suppression pool level and temperature.
c.   Emergency or isolation condenser level.
d.   Diagnostic instrumentation for shutdown systems.
e.   Level indication for all tanks used.
.

                                                        Attachment 1       
                                                        IN 84-09           
                                                        February 13, 1984  
                                                        Page 7 of 9        

X.  Procedures for Alternative Shutdown Capability 

At some facilities inspected, the alternative shutdown procedures have been 
deficient. Typical deficiencies identified have been: (1) inaccurately 
identified components, circuit breakers, wires, or terminals; (2) failure to
address the effects on alternative shutdown capability of circuitry damage 
in the fire area; and (3) failure to identify the specific equipment and 
actions required to achieve cold shutdown. 

Section III.L.3 of Appendix R requires that alternative shutdown procedures 
be in effect which accommodate post-fire conditions, where offsite power is 
available and where offsite power is not available for 72 hours. 

XI.  Fire Protection Features for Cold Shutdown Systems 

During inspection of one facility, the inspectors noted that the two 
residual heat removal (RHR) pumps were located in separate rooms in the 
Auxiliary Building. The wall separating the pumps (and other enclosing 
walls) had open penetrations. Also, the access doors to the rooms were 
constructed with non-closing ventilation louvers. Transient combustibles 
consisting of anti-C clothing, paper tape, etc., were stored on open shelves 
in the access area outside the RHR rooms. Also, the RHR pump power cables 
were not protected to preclude the loss of both trains of equipment from a 
fire in either of the pump rooms or the adjacent access area. Therefore, 
reasonable assurance was not provided that a single fire would not damage 
redundant RHR components or cables. 

The licensee had not performed an analysis to determine the limits of RHR 
system fire damage, the associated onsite repair material storage 
requirements, or the time required to complete necessary repairs. 

Section III.G.1.b requires that fire protection features for cold shutdown 
systems be capable of limiting fire damage so that systems necessary to 
achieve and maintain cold shutdown from either the control room or emergency
control station(s) can be repaired in 72 hours. To satisfy this requirement,
the licensee should have an analysis which supports conclusions that the 
design features provided will limit the fire damage. The requirements for 
such repairs specified in Section III.L.5 should also be met: 

     Materials for such repairs shall be readily available on site and 
     procedures shall be in effect to implement such repairs. 

Repairs for cold shutdown systems are allowed by Section III.L.5 of Appendix
R. For cold shutdown capability repairs, the removal of fuses for isolation 
and the replacement of cabling is permitted. Also, selected equipment 
replacement (e.g., such as replacing a valve, pump or control room controls 
and instruments) should be reviewed on a case-by-case basis to verify its 
practicality. Procedures for repairing damaged equipment should be prepared 
in advance with replacement equipment (i.e., cables made up with terminal 
lugs attached) stored on site in a controlled manner. All repairs should be 
of sufficient quality to assure  
.

                                                          Attachment 1     
                                                          IN 84-09         
                                                          February 13, 1984 
                                                          Page 8 of 9      

safe operation until the plant is restored to an operating condition. 
Repairs not permitted include the use of clip leads in control panels (which 
means that hard-wired terminal lugs must be used), and the use of jumper 
cables other than those fastened with terminal lugs. 

When repairs are necessary in the fire area, the licensee should demonstrate
that sufficient time is available to allow the area to be re-entered, that 
expected fire and fire suppressant damage will not prevent the repair from 
taking place, and that the repair procedure will not endanger operating 
systems. The licensee may, at his option, modify the plant so that cold 
shutdown can be achieved without reliance on repairs. 

XII.  RCP Oil Collection Systems 

At some facilities, the lube oil collection systems for the reactor coolant 
pumps were not sized to accept the entire lube oil inventory from all 
reactor coolant pumps without overflow. This does not protect against the 
consequences of simultaneous failure of more than one lube oil system during
a seismic event. 

Section III.O, Oil Collection Systems for Reactor Coolant Pump, is written 
for a single pump. The collection container is required to hold the entire 
inventory of the oil system of the pump. It follows that if additional pumps
are present they would each be provided full collection capacity. There are 
usually from 2 to 4 reactor coolant pumps in a plant. The oil inventory of 
one large pump is approximately 275 gallons. Some licensees have provided 
several containers connected in parallel for each pump. 

The NRC staff position on the capacity of a reactor coolant pump oil 
collection system which meets Section III.O of Appendix R to 10 CFR 50 is: 

     One or more tanks need to be provided with sufficient capacity to 
     collect the total lube oil inventory from all reactor coolant pumps 
     draining to the container. 

Alternatives which have been found acceptable under the exemption process 
are: 

1.   One or more tanks need to be provided with sufficient capacity to hold 
     the total lube oil inventory of one reactor coolant pump with mar in if
     the tank(s) is/are located such that any overflow from the tank(s) will
     be drained to a safe location where the lube oil will not present an 
     exposure fire hazard to or otherwise endanger safety-related equipment;
     or 

2.   Where the RCP lube oil system is shown, by analysis, to be capable of 
     withstanding the safe shutdown earthquake (SSE) (eliminating the 
     consideration of simultaneous lube oil system ruptures from a seismic 
     event), protection is required for random leaks at mechanical joints in
     the lube oil system (e,g, flanges, RTD connections, sightglasses). 
     Alternative methods of protection may be deemed acceptable for such 
     designs. In RCP lube oil collection systems of such designs, one or 
     more tanks need to be 
.

                                                        Attachment 1       
                                                        IN 84-09           
                                                        February 13, 1984  
                                                        Page 9 of 9        

     provided with sufficient capacity to hold the total lube oil inventory 
     of one reactor coolant pump with margin. Because protection is required
     only against possible leakage resulting from random leaks from the one 
     pump at a time, any overflow from the tanks need not be considered; or 

3.   For those pumps where the lube oil is contained entirely within the 
     pump casing, an oil collection system may not be required, provided it 
     can be shown that there are no potentially significant leakage points. 
 

Page Last Reviewed/Updated Tuesday, March 09, 2021