Information Notice No. 82-01:Auxiliary Feedwater Pump Lockout Resulting from Westinghouse W-2 Switch Circuit Modification
SSINS: 6835
Accession No.:
8107230043
IN 82-01
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF INSPECTION AND ENFORCEMENT
WASHINGTON, D.C. 20555
January 22, 1982
Information Notice No. 82-01: AUXILIARY FEEDWATER PUMP LOCKOUT RESULTING
FROM WESTINGHOUSE W-2 SWITCH CIRCUIT
MODIFICATION
Description of Circumstances:
On September 14, 1981, Commonwealth Edison's Zion Unit 2 was conducting a
normal plant cooldown to begin a refueling outage. The reactor coolant
system was operating at 350 psig and 250oF. Both residual heat removal
(RHR) systems were operating to remove decay heat and control reactor
coolant system temperature. Steam generator water levels dropped below the
10% low level auxiliary feedwater (AFW) pump auto-start setpoint, and the
motor-driven AFW pumps activated as designed. The operator placed the
control switched in the pull-to-lock-out position to stop the AFW pumps.
Later, to control the rate of plant cooldown, the operator tried to increase
the cooldown rate by feeding water to the steam generators. The AFW pumps
would not restart on command. The power supply circuit breaker for one of
the pumps was momentarily racked out to the disconnect position and then
racked back in for service. As result of this procedure, the AFW pump
restarted. No further problems were encountered during the plant cooldown
operation.
Investigation into the problem revealed that the licensee's modification to
the Westinghouse W-2 control switch used with the AFW pumps differed from
that recommended in IE Bulletin 80-20 (IEB). IEB 80-20, entitle "Failures
of Westinghouse Type W-2 Spring Return to Neutral Control Switches,"
recommended using only the existing green status light to provide early
detection of an open circuit caused by a neutral position (auto-start)
contact failure of the control switch. However, in this application, the
licensee's modification included both the red and green status lights. This
resulted in a sneak circuit path which prevented AFW pump restart under
certain circumstances.
Following an auto-start of the AFW pump and the subsequent securing of that
pump by placing the control switch in the pull-to-lock-out position, the
licensee found that a live continuous circuit existed between the red light
and the anti-pump coil. This sneak current path prevented deenergization of
the anti-pump coil (circuit reset) that is necessary for pump restart.
The licensee reports that, following the initial circuit modification, the
sneak path was noted to cause the red indicating light to glow only dimly
when the control switch was placed in the pull-to-lock-out or trip positions
(see Figures 1 though 3 and Table 1). However, the sneak path was not fully
analyzed at that time, and no detailed function testing of the modified
.
IN 82-01
January 22, 1982
Page 2 of 2
circuit was performed. Note that when the red light is used to indicate
"pump on," as in this application, the light should not go on when the
control switch has been placed in either the pull-to-lock-out or trip
positions.
Circuit modifications may have been made at various plants in response to
information in IEB 80-20. These modifications, where different from IEB
80-20 recommendations, may have caused sneak paths with various degrees of
impact that may not have been detected by previous engineering analysis or
post-installation testing.
This information notice is provided as an early notification of a
potentially significant matter. It is expected that recipients will review
the information for applicability to their facilities. No specific action
or response is required at this time. If you have any questions regarding
this matter, please contact the Regional Administrator of the appropriate
NRC Regional Office.
Attachments:
1. Figures 1, 2 and 3
2. Recently issued IE Information Notices
Page Last Reviewed/Updated Tuesday, March 09, 2021