Information Notice No. 83-44: Potential Damage to Redundant Safety Equipment as a Result of Backflow Through the Equipment and Floor Drain System
SSINS No.: 6835
IN 83-44
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF INSPECTION AND ENFORCEMENT
WASHINGTON, D.C. 20555
July 1, 1983
Information Notice No. 83-44: POTENTIAL DAMAGE TO REDUNDANT SAFETY
EQUIPMENT AS A RESULT OF BACKFLOW THROUGH
THE EQUIPMENT AND FLOOR DRAIN SYSTEM
Addressees:
All nuclear power reactor facilities holding an operating licensee (OL) or
construction permit (CP).
Purpose:
This information notice is provided to amplify the information in IE
Circular 78-06 (Potential Common Mode Flooding of ECCS Equipment Rooms of
BWR Facilities) in response to a potentially related event at a PWR
facility. IE Circular 78-06 applied specifically to ECCS equipment rooms and
flooding of areas at lower elevations. This notice expands the concern to
other safety-related compartments and damage as a result of backflow through
equipment and floor drainage systems. It is expected that recipients will
review this information notice for applicability to their facilities.
Description of Circumstances:
Baltimore Gas & Electric Co., the licensee for the Calvert Cliffs plant,
received notification from Bechtel Corporation, the architect-engineer, that
the watertight integrity of the service water pump rooms at both units could
be impaired because check valves had not been installed in the floor drain
system which drains by gravity to the turbine condenser pit in the turbine
building. The service water system at Calvert Cliffs serves both safety (the
containment cooling units and the emergency diesel generator heat
exchangers) and nonsafety equipment. Each unit has a room in the auxiliary
building where its three service water pumps are located. The systems can be
cross connected, by spool pieces, to allow one unit's system to back up the
other unit. However, both units share a common turbine building so that both
of the service water pump rooms would be simultaneously affected by flooding
of the turbine building if backflow protection was not provided. The
licensee has sealed some of the room drains and modified the remaining drain
lines by installing check valves to prevent potential backflow into the
safety-related rooms.
8305110502
.
IN 83-44
July 1, 1983
Page 2 of 2
Discussion:
At the Calvert Cliffs plant, the relative elevations of the turbine building
and the service water pump room are such that, without backflow protection
in the floor drains of the service water pump room, a circulating water
conduit break in the turbine building or a design-basis flood could flood
the turbine condenser pit and result in 15 feet of water in both service
water pump rooms (see Figure 1). Although instrumentation would detect and
annunciate an increase in water level in the turbine pit and the service
water pump rooms, there would be no way to stop the flow of water in the
event of a design-basis flood. A loss of service water flow would affect the
four containment air coolers for each unit and all three emergency diesel
generators at the site.
If containment cooling via the air coolers is lost, containment heat removal
and pressure control following a LOCA, can be accomplished with the
containment spray system. The containment spray is pumped through the
shutdown cooling heat exchanger and transfers heat to the component cooling
water system. The latter system is not affected by the postulated flooding.
However, if the service water pump rooms flooded at the same time as there
was a loss of offsite power, both units would experience a total loss of AC
power, since cooling for all the emergency diesels at the site would also be
lost.
A recently completed engineering evaluation by the NRC Office for Analysis
and Evaluation of Operational Data concluded that the subject of potential
damage to redundant safety equipment as a result of backflow through the
equipment and floor drain system has not been addressed for some older
plants [i.e. plants not fully reviewed in accordance with the Standard
Review Plan (SRP) and thus not necessarily designed to the standards of SRP
section 9.3.3 that provides guidance for equipment and floor drainage
systems]. Therefore, these plants may be susceptible to the same or
equivalent potential problem identified at the Calvert Cliffs plant. Because
of differing designs these plants could have equivalent problems, but
involving different components or systems of components.
No written response to this information notice is required. If you have any
questions about this matter, please contact the Regional Administrator of
the appropriate NRC Regional Office, or this office.
Edward L. Jordan Director
Division of Emergency Preparedness
and Engineering Response
Office of Inspection and Enforcement
Technical Contact: C. Campbell, IE
301-492-9762
Attachments:
1. Figure 1
2. List of Recently Issued IE Information Notices
.
Page Last Reviewed/Updated Tuesday, March 09, 2021