Information Notice No. 83-04: Failure of ELMA Power Supply Units 1
SSINS No.: 6835 IN 83-04 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C. 20555 February 18, 1983 Information Notice No. 83-04: FAILURE OF ELMA POWER SUPPLY UNITS 1 Addressees: All holders of a nuclear power reactor operating license (OL) or construction permit (CP). Purpose: This information notice is provided as an early notification of potentially significant problems pertaining to 24-V DC power supply units manufactured by ELMA Engineering of Palo Alto, California. Because of the potential safety significance and related generic implications of this problem, addressees are expected to review the information for applicability to their facilities. No specific action or response is required at this time. NOTE: All power supply units, mentioned, discussed, and referred to hereafter are power supply units manufactured by ELMA Engineering. Description of Circumstances: On June 19, 1982 a loss-of-24-V DC-power test performed at Peach Bottom Unit 2 Nuclear Plant resulted in startup of high-pressure coolant injection (HPCI), reactor core isolation cooling (RCIC), and residual heat removal (RHR) systems on the Unit 3 plant while it was operating at 100% power. The initiation of the emergency core cooling system (ECCS) equipment caused a reactor power increase to 113% of normal full power and a reactor water level increase of seven inches before the feedwater flow was automatically reduced and the operator tripped the ECCS system. The initiation of the Unit 3 ECCS system was caused by the degraded operation of one power supply unit when the backup power supply was lost during the loss-of-power testing. Each ECCS logic train of Peach Bottom Units 2 and 3 has two power supply units in parallel. One of Unit 3 power supply units is powered from the 4-kV emergency bus of Unit 2. This power supply was de-energized as part of the loss-of-power test. The parallel (battery powered) power supply unit had an undetected degradation which caused the voltage to drop and cause false "double low" and "triple low" reactor water level signals which subsequently initiated the ECCS. This was the third failure of a power supply unit within a year. Subsequent testing of all remaining power supply units at Peach Bottom identified one more degraded power supply unit. In each case, the power supply degradation 8212060363 . IN 83-04 February 18, 1983 Page 2 of 2 was attributed to a faulty capacitor. Degraded operation of these power supply units is characterized by a high ripple voltage. As a result of this problem Peach Bottom decided to test the power supply units monthly, rather than semiannually as before. On May 13, 1982 the auxiliary operator at Vermont Yankee noted anomalous low water level readings from the reactor vessel sensors. The instruments were declared inoperable and a channel trip (half scram) was instituted. Subsequent investigation revealed that a degraded power supply unit was the cause of anomalous readings. The power supply unit was replaced. Preventive maintenance checks of other power supply units at Vermont Yankee revealed that one more power supply unit was close to failure, evidenced by a decreased output. This power supply unit was also replaced. In both units the problem appears to have resulted from a faulty capacitor. Previous problem history with 10-ampere output power supply units caused Vermont Yankee to switch to 6-ampere output units at the vendor's recommendation. This apparently decreased the heating problem that is discussed in the following paragraph. Licensees should note that ELMA Engineering reported recently to the NRC that extensive testing at the factory indicates that improper, vertical mounting of power supply units can result in overheating of the capacitor adjacent to the ferro-resonant transformer and could cause capacitor failures. Further, ELMA Engineering pointed out that the ferro-resonant transformers are substantially less efficient when operating at partial rather than at full power. Therefore, if two power supply units in parallel share the load, their heat output into their enclosure(s) will be greater than the heat loss output of a single unit supplying the entire load. Power supply units which are not perfectly matched will result in unequal load sharing and further increased heat output. Therefore, ELMA Engineering indicates that if two or more power supply units are used in parallel, the system must be analyzed for load sharing, efficiency at low load, and proper cooling. If you have any questions regarding this matter please contact the administrator of the appropriate NRC Regional Office, or this office. Edward L. Jordan Director Division of Emergency Preparedness and Engineering Response Office of Inspection and Enforcement Technical Contact: W. Laudan 301-492-9759 Attachments: List of Recently Issued IE Information Notices
Page Last Reviewed/Updated Tuesday, March 09, 2021
Page Last Reviewed/Updated Tuesday, March 09, 2021