Information Notice No. 81-05: Degraded DC System at Palisades
SSINS No.: 6835
Accession No.:
8011040271
IN 81-05
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF INSPECTION AND ENFORCEMENT
WASHINGTON, D.C. 20555
March 10, 1981
Information Notice No. 81-05: DEGRADED DC SYSTEM AT PALISADES
Purpose:
The intent of this notice is to enhance nuclear power plant safety by
improving the reliability of the direct current (dc) distribution system in
nuclear power plants. Toward this end, this information notice alerts
holders of operating licenses and construction permits of an event that
degraded the dc system at the Palisades facility and jeopardized plant
safety.
Description of Circumstances:
On January 6, 1981, while performing monthly surveillance tests on both
station batteries, maintenance personnel inadvertently opened the breakers
from both station batteries to their 125 volt dc buses and left them open
for approximately one hour. We view this personnel error as a common-mode
failure that, if left uncorrected, would lead to a complete station blackout
(i.e., total loss of both alternating current (ac) and dc power].
Since the plant was in a normal mode of operation, dc power was being
supplied by the ac system via the battery chargers; therefore, dc power was
never interrupted during this period. Nevertheless, as described later, the
safety of the plant was jeopardized. A loss of offsite power during this
period would, in the absence of manual action, result in the loss of all
control power, blocking the automatic transfer of power to the onsite diesel
generators. In many designs, such losses would also block the starting of
the diesels. In contrast, the Palisades design would not block the starting
of the diesels; however, the loss of control power would block the
connecting of the generators to their emergency buses so that a complete
station blackout would still result. In either case, the blackout would
persist until the batter breakers were manually reclosed. During this time
the ability of the plant to remove decay heat would be severely restricted.
Since the tripping of the battery breakers is not annunciated in the
Palisades control room, a subsequent loss of offsite power would lead to an
undetected common-mode failure. Such a failure would be difficult to
diagnose, thereby limiting the operator's ability to take timely corrective
action. Consequently, an inordinate amount of time could be required to
bring the plant to a normal mode of decay heat removal.
.
IN 81-05
March 10, 1981
Page 2 of 2
Plants designed to conform with Regulatory Guide 1.47, "Bypassed and
Inoperable Status Indication for Nuclear Power Plant Safety," will
automatically alert the operator whenever a battery is disconnected from its
bus, thereby precluding a Palisades type of event. As a corrective measure,
Palisades is planning to install annunciators in the control room that will
alert the operator whenever a station battery has been disconnected from its
bus.
The information herein is being provided as an early notification of a
possibly significant matter that is still under review by the NRC staff.
Recipients should review the information for possible applicability to their
facilities. If NRC evaluations so indicate, further licensee actions may be
requested.
No written response to this Information Notice is required. If you desire
additional information regarding this matter, contact the Director of the
appropriate NRC Regional Office.
Attachment:
Recently issued IE Information Notices
Page Last Reviewed/Updated Tuesday, March 09, 2021