IE Circular No. 78-11, Recirculation M-G Set Overspeed Stops
CR78011
UNITED STATES
NUCLEAR REGULATORY COMMISSION
WASHINGTON, D. C. 20555
June 7, 1978
MEMORANDUM FOR: B. H. Grier, Director, Region I
J. P. O'Reilly, Director, Region II
J. G. Keppler, Director, Region III
K. V. Seyfrit, Director, Region IV
R. H. Engelken, Director, Region V
FROM: Norman C. Moseley, Director, Division of Reactor
Operations Inspection, Office of Inspection and
Enforcement
SUBJECT: IE CIRCULAR 78-11, RECIRCULATION M-G SET OVERSPEED
STOPS
The subject circular is transmitted for issuance no later than the
close of business on June 15, 1978. The circular should be issued to all
holders of BWR Operating Licenses or Construction Permits. Also enclosed is
a draft copy of the transmittal letter.
Norman C. Moseley, Director
Division of Reactor Operations
Inspection
Office of Inspection and Enforcement
Enclosures:
1. Draft Transmittal Letter
2. IE Circular No. 78-11
CONTACT: C. J. DeBevec, IE
49-28180
.
(Transmittal letter for IE Circular 78-11, to each holder of a BWR Operating
License or Construction Permit.)
Addressee:
The enclosed IE Circular No. 78-11, is forwarded to you for information. No
written response is required. Should you have any questions related to your
understanding of this matter, please contact this office.
Sincerely,
Signature
(Regional Director)
Enclosures:
1. IE Circular No. 78-11
2. List of IE Circulars
Issued for 1978
.
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF INSPECTION AND ENFORCEMENT
WASHINGTON, D. C. 20555
June 15, 1978
IE Circular No. 78-11
RECIRCULATION M-G SET OVERSPEED STOPS
In August 1977, personnel at the Cooper Nuclear Station reported finding the
recirculation M-G set overspeed mechanical and electrical stops at 112
percent and 120 percent of rated core flow. The licensee had believed the
set point to be 107 percent for these stops, although a search of Station
preoperational and startup test records could not establish the actual
initial set point. Subsequent to this finding, the licensee set the
mechanical stop at 102 percent of rated core flow.
The technical specifications require that the Minimum Critical Power Ratio
(MCPR) be maintained greater than 1.22 for 8 X 8 fuel. The technical
specifications further require MCPR to be above a minimum of 1.22 times Kf
whenever operating at less than rated flow. The correction factor Kf is
always greater than or equal to 1.0 and thus increases the MCPR limit when
at less than rated flow. Technically, this factor increases the required
MCPR thermal margin in the event a recirculation M-G set speed control
failure would occur and allow the recirculation pump to overspeed. The lower
the initial core flow the more severe is the flow transient, thus Kf
increases as actual core flow is decreased. The Kf factor is read from a
curve included in the technical specifications.
A family of Kf curves is given in the figure in the technical
specifications. The proper curve to use is the curve corresponding to the
set point of the manual flow control overspeed stop (the M-G set mechanical
stop). A lower set point of the overspeed stop results in a small Kf
correction factor for a given core flow, as the flow transient on an M-G set
speed control failure is less severe. Thus, it can be seen that by using a
lower curve (e.g., 107, percent curve) than that required by the actual
overspeed stop set point (believed to have been set at 112 percent), a
nonconservative Kf correction factor was being used.
The M-G set overspeed stops were set during the preoperational test program
by a General Electric Company startup engineer. The stops were checked by a
GE preoperational test procedure. This procedure did not include a
requirement to specifically record the stop setting. It
1 of 2
.
IE Circular No. 78-11 June 15, 1978
included only a requirement to verify that the stop setting had been made.
It appears likely that these same procedures, and perhaps the same engineer,
were involved in the preoperational/startup test programs at several other
sites.
All holders of operating licenses for Boiling Water Reactor plants employing
recirculation M-G sets should be aware of the potential for improperly or
undocumented settings on recirculation M-G set speed stops. It is
recommended that the following be considered in your review:
1. Facility records should be searched to determine if the actual existing
set point on the recirculation M-G set overspeed mechanical stops is
positively established.
2. If the setting of the mechanical and electrical overspeed stops is in
doubt, then steps should be initiated to determine the setting or
additional conservatism should be included in the determination of Kf.
3. The actual Kf being used for the process computer calculations in
the determination of MCPR limits should be verified to be appropriate
to (or more conservative than) the actual setting of the recirculation
M-G set mechanical overspeed steps.
This circular is also issued to holders of BWR Construction Permits for
information or use as appropriate to assure that steps are taken during the
preoperational test program to confirm that the M-G overspeed stops are set
properly and that the proper Kf will be used with the process computer.
No written response to this circular is required. If you require additional
information regarding this matter, contact the Director of the appropriate
NRC Regional Office.
2 of 2
Page Last Reviewed/Updated Tuesday, March 09, 2021