Part 21 Report - 1997-310
ACCESSION #: 9704010062
ABB
Document Control Desk Page 1
U.S. Nuclear Regulatory Commission
Washington, DC 20555
March 26, 1997
Subject: Notification of Potential Defect per 10CFR Part 21
K-Line Low Voltage AC Circuit Breakers
Notification By: ABB Power T&D Co., Inc.
Distribution Systems Division
201 Hickman Dr.
Sanford, FL 32771
On September 16, 1996, Perry Nuclear Power Plant (Perry, OH), experienced
a false trip of a K600S K-Line Low Voltage Circuit Breaker (Serial Number
934277-031295), with an SS-5 solid state trip device. At the time of the
trip, the breaker's trip setting was set at 660 amps and the breaker was
reported to be under approximately 50% load conditions. The breaker was
removed from service and returned to ABB for analysis.
On October 8, 1996, the breaker was inspected at the ABB circuit breaker
manufacturing facility in Florence, SC. The circuit wiring was checked
per the appropriate wiring diagram. The phase C current transformer
sensor wires were found to be crossed (i.e. the blue wire of terminal #2
was fastened to terminal #1 and the yellow wire of terminal #1 was
fastened to terminal #2). The result was that the polarity of the sensor
was reversed. Three phase testing at our facility's power laboratory
showed that, with the leads reversed, the breaker consistently tripped
between 350 and 360 amps, well below the 660 amp trip setting of the
breaker's trip unit. After placing the leads in their correct position,
subsequent testing showed no other false trips.
The cause of this condition was human error in the wiring of this low
voltage circuit breaker during the manufacture of this product in our
Florence, SC facility, in March of 1995. The inadvertent reversal of
these leads caused an errant, phase-shifted signal to be sent from the
phase C current transformer to the breaker's solid state trip unit. This
errant signal caused the trip unit to sense an abnormally high current
reading, tripping the breaker. This problem is only apparent when three
phase current is applied to the circuit breaker. Production testing,
conducted in accordance with ANSI C37.50-1989, uses three separate single
phase tests to check the trip point of the trip unit.
The following processes to prevent this type of error were in place at
the time of the error. The wiring diagram, the controlling document for
this process, was correct and available to the assembler. The
individuals performing this function were trained
ABB Power T&D Company Inc.
Distribution Systems Division Telephone: Telefax:
201 Hickman Drive 407 323-8220 407 322-8934
Sanford, FL 32771-8201 (Marketing/Engineering)
407 322-8938
(Operations)
407 328-9264
(Human Resources)
ABB Page 2
regularly on how to properly wire these devices. The individual leads
were color coded to aid in proper placement.
This is the first and only report of this condition received by us in
over 7,500 commercial grade and safety related breakers produced since
1990. For this reason ABB has been handling this issue as an isolated
incident related to a personnel error. Since the first report of this
occurrence, ABB has conducted an industry search to see if this condition
existed elsewhere in the commercial or nuclear industry. The search,
completed on March 15, 1997, revealed that there are no other known
reports of false trips on new K-Line circuit breakers. However, through
this search, ABB has found that many K-Line breakers are now being re-
furbished in the nuclear industry. These refurbishments are being done
by various end users and companies, many of which are not affiliated with
ABB. If there is human error in the refurbishment process, this
condition could exist on these circuit breakers also.
The following corrective actions has been taken since the time of the
reported error. The entire Low Voltage Team in Florence, SC was trained
on this incident, wiring procedures, and attention to detail in the
wiring of these current sensors. This specific condition was added to
the Low Voltage Checklist for final quality inspection to verify prior to
shipment. Maintenance and Surveillance Bulletin MS 3.1.1.9-2, Low
Voltage Switchgear Equipment, was revised to recommend that the trip unit
be tested and the wiring verified by the end user upon installation of
this equipment.
Although this faulted condition would already be apparent on any breaker
that is loaded greater than 50% of its trip value, ABB is recommending
that all ABB K-Line Low Voltage Circuit Breakers, both new and
refurbished, with solid state trip units, be inspected to verify the
proper wiring of these current transformer sensors.
ABB will notify all customers who purchased this product.
Any questions concerning this notification should be directed to Jon
Rennie 407-323-8220 or Shannon Soupiset 803-665-4144.
Prepared By Reviewed By
Jon S. Rennie Norbert Hagenhoff
Total Quality Manager Vice President/General Manager
Distribution Systems Division Distribution Systems Division
*** END OF DOCUMENT ***
Page Last Reviewed/Updated Wednesday, March 24, 2021