Consolidation of the 1985 Sandia National Laboratories/Factory Mutual Main Control Room and Electrical Cabinet Fire Test Data (NUREG-2164, Supplement 1)

On this page:

Publication Information

Manuscript Completed: September 2014
Date Published:
May 2015

Prepared by:
F. Gonzalez, N. Melly, S. Nowlen* and J.M. Chavez*

Office of Nuclear Regulatory Research
U.S. Nuclear Regulatory Commission
Washington, DC 20555-0001

*Sandia National Laboratories
Albuquerque, NM 87185
Operated by Sandia Corporation
For the U.S. Department of Energy

F. Gonzalez, NRC Project Manager

Availability Notice

To top of page

Control Room Data Matrix/Files

This page includes links to files in non-HTML format. See Plugins, Viewers, and Other Tools for more information.

SNL/FM Test #
(select test
to open
Data Sheet)
Fuel Type Nominal Peak
Fire Intensity
Fire Location
(select location
to open room diagram)
Nominal Enclosure
Ventilation Rate
Burner Fire Mode
Test 1 Propylene Burners 516 kW Room Center (Location 1) 10 ch/hr (8000 CFM) Steady State Mode
Test 2 Propylene Burners 516 kW Room Center (Location 1) 10 ch/hr (8000 CFM) Steady State Mode
Test 3 Propylene Burners 2000 kW Room Center (Location 1) 10 ch/hr (8000 CFM) Steady State Mode
Test 4 Propylene Burners 516 kW Room Center (Location 1) 1 ch/hr (800 CFM) Growing Fire Mode
Test 5 Propylene Burners 516 kW Room Center (Location 1) 10 ch/hr (8000 CFM) Growing Fire Mode
Test 6 Heptane Pool 500 kW South Wall (Location 2) 1 ch/hr (800 CFM) Uncontrolled
Test 7 Propylene Burners 516 kW Room Center (Location 1) 1 ch/hr (800 CFM) Steady State Mode
Test 8 Propylene Burners 1000 kW Room Center (Location 1) 1 ch/hr (800 CFM) Growing Fire Mode
Test 9 Propylene Burners 1000 kW Room Center (Location 1) 8 ch/hr (6400 CFM) Growing Fire Mode
Test 10 Heptane Pool 1000 kW South Wall (Location 2) 4.4 ch/hr (3500 CFM Uncontrolled
Test 11 Methanol Pool 500 kW South Wall (Location 2) 4.4 ch/hr (3500 CFM Uncontrolled
Test 12 Heptane Pool 2000 kW South Wall (Location 2) 4.4 ch/hr (3500 CFM Uncontrolled
Test 13 Heptane Pool 2000 kW South Wall (Location 2) 8 ch/hr (6400 CFM) Uncontrolled
Test 14 Methanol Pool 500 kW South Wall (Location 2) 1 ch/hr (800 CFM) Uncontrolled
Test 15 Heptane Pool 1000 kW South Wall (Location 2) 1 ch/hr (800 CFM) Uncontrolled
Test 16 Heptane Pool 500 kW South-West Corner
(Location 3)
1 ch/hr (800 CFM) Uncontrolled
Test 17 Heptane Pool 500 kW South-West Corner
(Location 3)
10 ch/hr (8000 CFM) Uncontrolled
Test 18 PMMA Solid Slabs 1000 kW South Wall (Location 2) 1 ch/hr (800 CFM) Uncontrolled
Test 19 Heptane Pool 1000 kW Room Center (Location 1) 1 ch/hr (800 CFM) Uncontrolled
Test 20 Heptane Pool 1000 kW South-West Corner
(Location 3)
8 ch/hr (6400 CFM) Uncontrolled
Test 21 Propylene Burners 500 kW Bench-Board Cabinet A 1 ch/hr (800 CFM) Growing Fire Mode
Test 22 Propylene Burners 1000 kW Bench-Board Cabinet A 1 ch/hr (800 CFM) Growing Fire Mode
Test 23 Qualified Cable N/A Bench-Board Cabinet A 1 ch/hr (800 CFM) Uncontrolled
Test 24 Unqualified Cable N/A Bench-Board Cabinet A 1 ch/hr (800 CFM) Uncontrolled
Test 25 Unqualified Cable N/A Vertical Cabinet C 8 ch/hr (6400 CFM) Uncontrolled

To top of page

Abstract

NUREG-2164 report consolidates and refines the report's details and all the data recorded during the 1985 series of 25 main control room (MCR) fire tests performed by Sandia National Laboratories (SNL).  These tests were conducted at the Factory Mutual Research Corporation (FMRC) for the U.S. Nuclear Regulatory Commission (NRC) under direct contract to SNL.  The objective of these tests was to provide experimental data to validate computer fire models in the analysis of nuclear power plant (NPP) large enclosure fires.  While select parts of the data have previously been reported, no single consolidated report was prepared in 1985 to produce the data in a high quality, usable manner.  This report fulfills that need.

FMRC performed these fire tests in a test enclosure simulating a typical space in a NPP MCR.  The test enclosure measured 18.3 meter (m) x 12.2 m x 6.1 m [60 feet (ft) x 40 ft x 20 ft].  The original program had two phases:  (1) the development of fire in electrical cabinets and (2) the effect of those fires on a simulated MCR.  Propylene gas burner, heptane pool, methanol pool, polymethyl methacrylate (PMMA) solids, qualified cables and unqualified cables were used as fire sources.  The parameters included were fire intensity, fire location, ventilation rate, and fire burning mode.  These test recorded over 300 data channels, which included measurements such as air and surface temperature, air velocity, heat fluxes, optical smoke density, and gas concentrations.

NUREG-2164 report is an updated and expanded compilation of the test details as described in NUREG/CR-4681,"Enclosure Environment Characterization Testing for the Base Line Validation of Computer Fire Simulation Codes," NUREG/CR-4527, "An Experimental Investigation of Internally Ignited Fires in Nuclear Power Plant Control Cabinets, Volume II:  Room Effects Tests," and Steve Nowlen's "Survivor's Guide for Users of the Baseline Validation Test Data" (Nowlen, 1999).  Most of this data has never been used because of the lack of availability, lack of fire modeling research in this area, and the difficulty in accessing and extracting the original data, in part caused by these tests being ahead of their time.  The purpose of this report is to make the data gathered by FMRC in 1985 more readily available and easier to use.  The data was converted to a Microsoft Excel spreadsheet file format to facilitate its use and is contained below; this data is also available from the NRC's Fire Research Branch.  The NRC expects that these completed data sets will be used in future advancements of NUREG-1824, "Verification and Validation of Selected Fire Models for Nuclear Power Plant Applications."

To top of page

Historical Report References

  1. NUREG/CR-4527 Part 1 and 2 "An Experimental Investigation of Internally Ignited Fires in Nuclear Power Plant Control Cabinets"
    1. Volume 1 Cabinet Effects Tests and Volume 2 Control Room Effects Tests (ML060960351)
    2. Volume 2: Control Room Effects Tests (ML071690016)
  2. NUREG/CR-4681 "Enclosure Environment Characterization Testing for the Base Line Validation of Computer Fire Simulation Codes" (ML0622601630)
  3. Steve Nowlen "Survivor's Guide for the Users of the Baseline Validation Test Data" (ML15295A370)

To top of page

Page Last Reviewed/Updated Wednesday, October 26, 2016