The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

The Programmable Logic Controller and ItsApplication in Nuclear Reactor Systems (NUREG/CR-6090, UCRL-ID-112900)

On this page:

Download complete document

Publication Information

Manuscript Completed: August 1993
Date Published:
September 1993

Prepared by:
J. Palomar, R. Wyman
Lawrence Livermore National Laboratory
P.O. Box 808
Livermore, California 94550

Prepared for:
Division of Reactor Controls and Human Factors
Office of Nuclear Reactor Regulation
U.S. Nuclear Regulatory Commission
Washington, DC 20555-0001

NRC FIN L-1867

Availability Notice

Abstract

This document provides recommendations to guide reviewers in the application of Programmable Logic Controllers (PLCs) to the control, monitoring and protection of nuclear reactors. The first topics addressed are system-level design issues, specifically including safety. The document then discusses concerns about the PLC manufacturing organization and the protection system engineering organization. Supplementing this document are two appendices. Appendix A summarizes PLC characteristics. Specifically addressed are those characteristics that make the PLC more suitable for emergency shutdown (ESD) systems than other electrical/electronic-based systems, as well as characteristics that improve reliability of a system. Also covered are PLC characteristics that may create an unsafe operating environment. Appendix B provides an overview of the use of programmable logic controllers in emergency shutdown systems. The intent is to familiarize the reader with the design, development, test, and maintenance phases of applying a PLC to an ESD system. Each phase is described in detail and information pertinent to the application of a PLC is pointed out.

Page Last Reviewed/Updated Tuesday, March 09, 2021