Part 21 Report - 1995-104
ACCESSION #: 9504050223 Commonwealth Edison 1400 Opus Place Downers Grove, Illinois 60515 March 31, 1995 U.S. Nuclear Regulatory Commission Attn.: Document Control Desk Washington, D. C. 20555 Subject: ComEd 10 CFR Part 21 Interim Report (File 94-12) Limitorque Actuator Potential Motor Pinion Key Failure Reference: I. Johnson (ComEd) letter to U.S. NRC (Document Control Desk), dated November 11, 1994. The purpose of this letter is to update the NRC staff regarding the information contained in the referenced 10 CFR Part 21 interim report. The interim report notified the NRC Staff of concerns by ComEd toward the Limitorque motor operator valve actuator AISI type 1018 motor pinion keys. The action plan listed in the referenced letter contained the following steps: 1) Complete additional review of the KALSI testing to identify the failure mechanism and applicability to installed actuators by the end of the fourth quarter, 1994. 2) Establish a model via bench testing to validate this failure mechanism and identify susceptible actuators during the first quarter, 1995. ComEd's review of the KALSI SMB-0 key failures identified impact loads as the probable failure mechanism. Inspection of the KALSI motor shaft and pinion gear found the keyway to be enlarged, allowing significant side- to-side movement of the key. KALSI had not spot drilled the shaft for proper seating of the set screw per Limitorque recommendations. Motor pinion key movement will increase impact loads. ComEd has completed two bench tests of a SMB-0 Limitorque actuator. Each test utilized a 40 ft-lb motor, but with a different overall actuator ratio (OAR). A 39:1 OAR (worst case) was used in the first test, and a 61:7 OAR (KALSI configuration) was used in the second test. No visible signs of key deformation were found after either test was completed. (illegible print) U. S. NRC - 2 - March 31, 1995 The test results are summarized below. Maximum Actuator Motor OAR Torque Cycles Results 3_/ 40 ft-lb 1_/ 39:1 500 ft-lb (100% of the 2300 Visible motor actuator torque inspection rating, MATR) found no signs of deformation. 40 ft-lb 61:7 600 ft-lb (120% of MATR 2600 Visible (KALSI inspection configuration)2_/ found no signs of deformation. ____________ 1_/ ComEd used the 40 ft-lb motor from the KALSI test. 2_/ KALSI experienced three consecutive motor pinion key failures at approximately 200 cycles at and actuator output torque of 525 ft-lb. 3_/ ComEd drilled the motor shaft per Limitorque guidance from Limitorque Maintenance Update 89-1 to ensure proper seating of the set screw. ComEd is conducting additional testing of the KALSI configuration with the set screw removed to determine the criticality of this step in the motor pinion key installation process. This configuration is expected to duplicate the KALSI results. If key failure occurs, additional testing as well as review of the KALSI testing will be conducted to determine the impacted actuator configurations. If key failure does not occur, KALSI Engineering will be contacted and an appropriate test plan will be developed to resolve the apparent discrepancy in test results between KALSI and ComEd. ComEd will update this 10 CFR Part 21 interim report no later than July 31, 1995 (illegible print) U.S. NRC - 3 - March 31, 1995 If there are any questions regarding this notification, please direct them to Eric Steckhan at (708) 663-7437. Respectively, Irene M. Johnson Licensing Operations Director Attachment: Test Methods and Results cc: J. B. Martin, Regional Administrator - RIII R. Capra, Directorate III-2 Director - NRR R. Assn, Braidwood Project Manager, NRR G. Dick, Byron Project Manager, NRR R. Pulsifer, Quad Cities Project Manager, NRR W. Reckley, LaSalle County Project Manager, NRR C. Shiraki, Zion Project Manager, NRR J. Stang, Dresden Project Manager, NRR S. DuPont, Senior Resident Inspector - Braidwood H. Peterson, Senior Resident Inspector - Byron J. Roton, Senior Resident Inspector - Zion M. Leach, Senior Resident Inspector - Dresden C. Miller, Senior Resident Inspector - Quad Cities P. Brochman, Senior Resident Inspector - LaSalle Office of Nuclear Facility Safety - IDNS (illegible print) Attachment 10 CFR Part 21 File No. 9412 Limitorque Actuator Potential Motor Pinion Key Failure Test Methods and Results 1.0 PURPOSE The purpose of this test program is to perform torque testing of SMB-0 Limitorque actuators to validate the capability of AISI Type 1018 keys for 2000 cycles. Specifically this testing will: 1. Verify motor pinion key capability under worst case conditions for SMB, SB, and SBD actuators. Failure has been attributed to impact loads at the actuator worm clutch. 2. If motor pinion key failure occurs, establish criteria to extrapolate failures to other actuator configurations. 2.0 RESULTS Testing of the predicted worst case SMB-0 and the KALSI configuration were completed without any visible signs of key deformation. Inspection of the KALSI motor found that the motor shaft was not spot drilled in accordance with the Limitorque guidance. Additional testing without the set screw will be performed to determine the criticality of the set screw. 3.0 SCOPE Failure of AISI Type 1018 keys has been attributed to insufficient material strength for certain Limitorque actuators. In 1983 Limitorque notified the industry that 4140 keys are required in size 3 and 4 actuators. Industry failures and the failure of a SMB-0 during the KALSI Limitorque Actuator Testing Program, indicate that size 0 and 2 actuators may also require 4140 key material. Review of the key sizes for all actuators reveals that the size 0 actuator uses the same size key as the size 00 actuators, whereas the key size increases with increasing actuator size for all other actuators. This results in higher relative stress for the size 0 actuator key. Furthermore, the size 0 and larger actuators (illegible print) 10 CFR Part 21 File No. 9412 Limitorque Actuator Potential Motor Pinion Key Failure Test Methods and Results have a worm shaft clutch resulting in higher impact loads. Shear and bending stresses at the motor pinion key generated during the KALSI testing were well below the stresses needed to fail 1018 keys. Yet, the key failed three consecutive times. Subsequently, KALSI and ComEd have reviewed motor torque data gathered during recent KALSI tests and identified significant impact loads at the worm clutch just after starting. The following actuator attributes will affect impact loads: Attributes Worst Case Motor speed High speed Motor size Larger motors, increased mass Worm set Lower ratio, higher speed drive sleeve and higher torque at key for the same thrust Motor set ratio Lower ratio, higher worm shaft speed and higher torque at key Spring pack stiffness Heavier pack, higher impact loads Soft clutch vs. hard Hard clutch, higher impact loads clutch Release torque Locking gear sets may impose higher impact torques due to higher release torques. However, motor torque data from KALSI indicates that the release torque may not affect impact loads. 3.1 ComEd POPULATION The worst case conditions for impact loads are identified in the table above. Table 1, on page 5 of this Attachment, summarizes the GL 89-10 MOV actuator configurations installed at ComEd facilities. The shaded configurations in Table 1 should bound all SMB-O applications at ComEd facilities. Page 2 of 5 10 CFR Part 21 File No. 9412 Limitorque Actuator Potential Motor Pinion Key Failure Test Methods and Results 3.2 TEST POPULATION Table 2, on page 5 of this Attachment, provides a list of the actuator configurations identified for testing. Testing started with the worst case configuration, utilizing a 40 ft-lb motor and a 39:1 OAR. Testing of SMB actuators is believed to be bounding for SB and SBD actuators (except SB/SBD actuators with hammer blow devices) since these actuators are supplied with compensators that dampen impact loads and typically have lower seating/unseating loads. 4.0 TEST PLAN 4.1 TEST OBJECTIVES 1. Simulate the worst case conditions for motor pinion key stresses. 2. Perform 2000 cycles at these conditions. 3. Test several representative configurations for SMB-0 actuators. 4.2 TEST BENCH/HARDWARE/EQUIPMENT One test bench was built for the SMB-0 MOV. The tested configuration has a SMB-0 actuator mounted on a 6" Velan gate valve The 1018 keys were obtained and tested to identify specific material properties. The specified motors, gears, worm clutches, and spring packs were obtained as specified in Table 2 of this Attachment. VOTES torque cartridge (VTC) and motor power monitor (MPM) equipment for torque, thrust, and motor power monitoring were obtained. 4.3 TEST METHODS 4.3.1 Facilities The Quad Cities training facility was used for the testing. 4.3.2 Procedure 4.3.2.1 Prerequisites Page 3 of 5 10 CFR Part 21 File No. 9412 Limitorque Actuator Potential Motor Pinion Key Failure Test Methods and Results MOV thermal overloads were set as low as possible to prevent motor damage without causing spurious tripping. 4.3.3.2 Methods Table 2 of this Attachment provides a list of the actuator test configurations. The first test configuration is considered the worst case. If key failure occurred during this test, this test configuration should bound all other actuator configurations. Each test consisted of approximately 2500 cycles at approximately 110% of the Limitorque actuator torque rating. The test program would have been considered to be complete if the first configuration completes a successful 2000 cycle test (i.e., key deformation occurred within 2000 cycles). A new motor pinion key was installed after each test. Each 2500 cycle test sequence was conducted as follows: 1. The actuator configuration was verified that it is as specified for the configuration to be tested. 2. The new motor pinion key was installed in accordance with Limitorque guidelines. 3. The appropriate torque output was established, two strokes were performed to acquire VTC and MPM data, and the 2500 cycle test was initiated. 4. At approximately 500, 1500, 2000, and 2500 cycles, the test was stopped and: a) The torque output was verified. b) The valve was stroked two to three times to acquire VTC and MPM data. The results were documented. c) The MOV cycling was continued. 5. The MOV cycling was stopped at approximately 2500 cycles. At this time, three valve strokes were performed to acquire VTC and MPM data. The results were documented. The motor, motor pinion, motor pinion key and the worm shaft gear were removed and inspected. The results were documented. Page 4 of 5 10 CFR Part 21 File No. 9412 Limitorque Actuator Potential Motor Pinion Key Failure Test Methods and Results If failure occurs prior to 2000 cycles for any configuration, the next configuration will be immediately tested to establish extrapolation criteria. In addition, the first actuator configuration to fail will be reassembled and retested at consecutively lower output torques (e.g., 80%, 50%, 20% of MATR) to determine the effect of release torque. Table 1 "ComEd Valves" omitted Table 2 "Test Sequence/Configurations" omitted. Page 5 of 5 *** END OF DOCUMENT ***
Page Last Reviewed/Updated Wednesday, March 24, 2021
Page Last Reviewed/Updated Wednesday, March 24, 2021