Part 21 Report - 1995-039
PRIORITY ATTENTION REQUIRED MORNING REPORT - REGION I FEBRUARY 1, 1995 Licensee/Facility: Notification: Niagara Mohawk Power Corp. MR Number: 1-95-0015 Nine Mile Point 2 Date: 02/01/95 Lycoming,New York SRI PC Dockets: 50-410 BWR/GE-5 Subject: INOPERABLE EMERGENCY DIESEL GENERATORS (UPDATE) Reportable Event Number: 28304 Discussion: On January 29, 1995, NMPC commenced a shutdown of Unit 2, and declared an Unusual Event as a result of both Emergency Diesel Generators (EDG) being inoperable. On January 26, 1995, during routine monthly surveillance testing, the Division I EDG exhibited instability in the engine control system and tripped when its output circuit breaker was tripped. Troubleshooting of the control system indicated a problem with the electric governor or the DC governor power supply (the engines are equipped with both electric and mechanical governors). The applicable Technical Specification (TS) limiting condition for operation (LCO) was entered, and the Division II EDG was tested. No instability was noted during the run of the Div II EDG. After replacing the Div I EDG electric governor control card, the Div I EDG was tested, and still exhibited instability. During subsequent troubleshooting, excessive temperatures were noted at the base of the governor, and it was determined that the mechanical governor was malfunctioning. The mechanical governor was replaced and on retest, the engine was noted to operate properly, but the governor was still experiencing excessive temperatures. The Div II EDG was run to obtain temperature profiles on its governor, and it was determined that its governor was also experiencing excessive temperatures. At the end of the test run, the Div II EDG failed to trip due to an air leak on the pneumatic controls. The Div II EDG was declared inoperable and a reactor shutdown was commenced (the Div II EDG was INOP, but available). NMPC has determined that the governor coolers were receiving inadequate flow from the jacket cooling water system, and has instituted a design change to rectify the problem. NMPC has also determined that the manufacturer (Cooper-Bessemer) has used several different jacket cooling water system designs, and notified the two facilities with similar systems (Byron and Braidwood) of the problem. The governor on the Div II EDG has been replaced due to having been subjected to excessive temperatures. The problem is believed to be long-term degradation of the governor oil and mechanical components due to the high temperatures. The governors from both engines will be sent out for failure analysis. As of 8:00 a.m. February 1, the modifications on both engines have been completed, and testing of the Div II EDG is in progress (Div I EDG
Page Last Reviewed/Updated Wednesday, March 24, 2021
Page Last Reviewed/Updated Wednesday, March 24, 2021