The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

Event Notification Report for January 12, 2024

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/11/2024 - 01/12/2024

EVENT NUMBERS
56919 56920
Part 21
Event Number: 56919
Rep Org: V. C. Summer
Licensee: V. C. Summer
Region: 2
City: Jenkinsville   State: SC
County: Franklin
License #:
Agreement: Y
Docket:
NRC Notified By: Justin booknight
HQ OPS Officer: Thomas Herrity
Notification Date: 01/10/2024
Notification Time: 08:18 [ET]
Event Date: 11/12/2021
Event Time: 00:00 [EST]
Last Update Date: 01/10/2024
Emergency Class: Non Emergency
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
Person (Organization):
Miller, Mark (R2DO)
Part 21/50.55 Reactors, - (EMAIL)
Event Text
PART 21 - EATON-CUTLER HAMMER RELAY ON EMERGENCY DIESEL FAILED

The following information was provided by the licensee via email and phone call:

"On January 9, 2024, VC Summer Nuclear Station (VCSNS) determined a manufacturing defect affecting a control power circuit monitor (CP1) relay on its 'B' emergency diesel generator (EDG) was reportable under Part 21.

"On November 12, 2021, the 'B' EDG was rendered inoperable when its CP1 relay de-energized due to mechanical binding of the magnet carrier assembly. The binding was caused by a manufacturing defect that allowed heat-induced shrinkage to reduce the clearance between the magnet carrier and adjacent coil housing and base, preventing it from moving freely. VCSNS replaced the effected relay and restored operability of its 'B' EDG.

"Manufacturer/Model: Eaton-Cutler Hammer D26MRD30A1

"A written notification in accordance with 10 CFR 21.21(d)(3)(ii) will be provided within 30 days. The NRC Senior Resident Inspector has been notified."

The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:

The plant has notified the manufacturer. It is not known if any other plants are affected by this defect.


Part 21
Event Number: 56920
Rep Org: V. C. Summer
Licensee: V. C. Summer
Region: 2
City: Jenkinsville   State: SC
County: Franklin
License #:
Agreement: Y
Docket:
NRC Notified By: Justin BoUkknight
HQ OPS Officer: Thomas Herrity
Notification Date: 01/10/2024
Notification Time: 08:18 [ET]
Event Date: 05/05/2021
Event Time: 00:00 [EST]
Last Update Date: 01/10/2024
Emergency Class: Non Emergency
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
Person (Organization):
Miller, Mark (R2DO)
Part 21/50.55 Reactors, - (EMAIL)
Event Text
PART 21 - GOULD FIELD FLASH RELAY ON EMERGENCY DIESEL FAILED

The following information was provided by the licensee via email and phone call:

"On January 9, 2024, VC Summer Nuclear Station (VCSNS) determined a manufacturing defect affecting a field flash contactor (K2) relay on its 'B' emergency diesel generator (EDG) was reportable under Part 21.

"During testing on May 5, 2021, the 'B' EDG was rendered inoperable when its K2 relay coil switch exhibited intermittent binding due to insufficient clearances of the switch actuator from the protective case and plastic switch molding. The inadequate clearances resulted in accelerated loss of graphite lubrication at these locations, which led to mechanical binding. VCSNS replaced the effected relay and restored operability of its 'B' EDG.

"Manufacturer/Model: Gould F10NOCLD1 DC coil switch

"A written notification in accordance with 10 CFR 21.21(d)(3)(ii) will be provided within 30 days. The NRC Senior Resident Inspector has been notified."

The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:

The licensee did not notify the intellectual property owner because the manufacturer is no longer operating or in business. They are not aware of other plants that utilize this coil switch.