Cable Heat Release, Ignition, and Spread in Tray Installations During Fire (CHRISTIFIRE), Phase 2: Vertical Shafts and Corridors (NUREG/CR-7010, Volume 2)
On this page:
Download complete document
For information about how the NRC handles your comments, see our Privacy Policy.
Publication Information
Manuscript Completed: January 2013
Date Published: December 2013
Prepared by:
Kevin McGrattan
Scott Bareham
National Institute of Standards and Technology
Building and Fire Research Laboratory
Gaithersburg, MD 20899-8663
David Stroup, NRC Project Manager
NRC Job Code N6983
Office of Nuclear Regulatory Research
U.S. Nuclear Regulatory Commission
Washington DC 20555-0001
Abstract
This report documents the second phase of a multi-year program called CHRISTIFIRE (Cable Heat Release, Ignition, and Spread in Tray Installations during Fire). The overall goal of the program is to quantify the burning characteristics of grouped electrical cables. This second phase of the program involved bench-scale and large-scale experiments. Bench-scale experiments were performed using a cone calorimeter in which 10 cm (4 in) by 10 cm (4 in) cable segments were exposed to a relatively high heat flux to determine their burning rate, heat of combustion, and other properties. The large scale experiments consisted of loaded cable trays situated in vertical and horizontal configurations. For the vertical experiments, two cable trays were positioned either in the open air, or in a vertical shaft that was open at the top and bottom. For the horizontal experiments, from one to four loaded cable trays were positioned horizontally with a 30 cm (1 ft) separation from the ceiling and tray to tray. The purpose of both sets of fullscale experiments was to determine the heat release and spread rates of burning cables in a variety of realistic configurations.
Page Last Reviewed/Updated Wednesday, March 24, 2021
Page Last Reviewed/Updated Wednesday, March 24, 2021