Part 21 Report - 1998-102
ACCESSION #: 9801160144
| POWER REACTOR | EVENT NUMBER: | 33536 | |
| FACILITY: INDIAN POINT | REGION: 1 | NOTIFICATION DATE: | 01/14/98 |
| UNIT: [2] [ ] [ ] | STATE: NY | NOTIFICATION TIME: | 17:14 (ET] |
| RX TYPE: [2]W-4-LP, [3] W-4-LP | EVENT DATE: | 01/14/98 | |
| EVENT TIME: | 15:00[EST] | ||
| NRC NOTIFIED BY: | PHIL SANTIANI | LAST UPDATE DATE: | 01/14/98 |
| HQ OPS OFFICER: | DICK JOLLIFFE | NOTIFICATIONS | |
| EMERGENCY CLASS: | NOT APPLICABLE | ||
| 10 CFR SECTION: | JOHN ROGGE | RDO | |
| CDEG 21.21(c)(3)(i) | DEFECTS/NONCOMPLIANCE | ||
| VERN HODGE | NRR |
| UNIT | SCRAM CODE | RX CRIT | INIT PWR | INIT RX MODE | CURR PWR | CURR RX MODE |
| 2 | N | N | 0 | COLD SHUTDOWN | 0 | COLD SHUTDOWN |
EVENT TEXT
- 10CFR PART 21 REPORT -
TWELVE SAFETY-RELATED 480-VOLT WESTINGHOUSE MODEL #DB-50 CIRCUIT BREAKERS WERE SENT TO WESTINGHOUSE REPAIR AND REPLACEMENT SERVICES, CHESWICK, PA, AN APPROVED 10CFR50, APPENDIX B QUALIFIED REPAIR FACILITY, FOR OVERHAUL.
DURING PRE-INSTALLATION TESTING, THE LICENSEE DETERMINED THAT LOW TRIP BAR FORCES AND THE WINDING OF THE TRIP PAN SPRING CONTRIBUTED TO BREAKER MIS-OPERATION. IF INSTALLED, THIS MIS-OPERATION MIGHT HAVE RESULTED IN THE BREAKERS MALFUNCTIONING WHEN CALLED UPON TO PERFORM THEIR SAFETY-RELATED FUNCTION.
THESE BREAKER ANOMALIES WERE PREVIOUSLY REPORTED TO THE NRC IN LER #97-024.
THE LICENSEE PLANS TO REPAIR AND TEST THESE BREAKERS (AND THE REMAINING 38 SAFETY-RELATED 480-VOLT BREAKERS) ON-SITE PRIOR TO INSTALLATION.
THE LICENSEE PLANS TO SUBMIT A WRITTEN PART 21 REPORT TO THE NRC.
THE LICENSEE WILL INFORM THE NRC RESIDENT INSPECTOR.
Attachment "CITRS Event Detail Report" (33536)
*** END OF DOCUMENT ***