Part 21 Report - 1998-500

LICENSEE: INDIANA & MICHIGAN ELECTRIC CO. SITE: COOK 1 2 EN NUMBER:34427 DOCKET: 05000315 05000316 EVENT DATE: 06-23-98 RX TYPE: PWR PWR EVENT TIME: 08:07 VENDORS: W-4-LP W-4-LP NOTIFY DATE: 06-23-98 EMERGENCY CLASS: N/A REGION: 3 STATE: MI TIME: 10:19 OPS OFFICER: FANGIE JONES 10 CFR SECTION: ADAS 50.72(b)(2)(i) DEG/UNANALYZED COND CCCC 21.21 UNSPECIFIED PARAGRAPH UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE CODE CRIT PWR PWR 1 N N 0 COLD SHUTDOWN 0 COLD SHUTDOWN 2 N N 0 COLD SHUTDOWN 0 COLD SHUTDOWN ICE CONDENSER BASKETS FOUND IN UNANALYZED CONDITION THE LICENSEE DISCOVERED, DURING AN INSPECTION OF UNIT ONE ICE CONDENSER, MISSING AND OR DEFECTIVE WELDS ON THE BOTTOM CROSSBAR AND BOTTOM BASKET GRIDS OF THE ICE CONDENSER BASKETS. THE LICENSEE EXPECTS TO FIND SIMILAR CONDITIONS IN THE UNIT TWO ICE CONDENSER. THIS CONDITION IS UNANALYZED AND AN INVESTIGATION WILL CONTINUE INTO THE CAUSE OF THESE CONDITIONS. THE CONDITION IS BEING REVIEWED FOR REPORTABILITY UNDER 10CFR PART 21. THE DEFECTIVE ICE BASKET BOTTOM RIMS WILL BE REPAIRED OR REPLACED AS APPROPRIATE BEFORE ENTERING PLANT STARTUP. THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR. *** UPDATE ON 7/10/98 @ 1704 BY KELLY TO GOULD *** THE LICENSEE IS CONSIDERING THIS CONDITION TO BE A PART 21 REPORT SINCE THEY DETERMINED THE REPORTED ICE CONDENSER DAMAGE IS MORE OF A MANUFACTURING DEFECT THAN DAMAGE. IT IS EXPECTED THAT SIMILAR CONDITIONS WILL BE FOUND ON UNIT 2. THE RESIDENT INSPECTOR WAS INFORMED. THE REG 3 RDO(GARDNER) WAS NOTIFIED. VERN HODGE(NRR) WAS NOTIFIED.

Page Last Reviewed/Updated Wednesday, March 24, 2021