Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Part 21 Report - 1998-140

LICENSEE: ILLINOIS POWER CO. SITE: CLINTON 1 EN NUMBER:33618 DOCKET: 05000461 EVENT DATE: 01-28-98 RX TYPE: BWR EVENT TIME: 00:00 VENDORS: GE-6 NOTIFY DATE: 01-28-98 EMERGENCY CLASS: N/A REGION: 3 STATE: IL TIME: 18:08 OPS OFFICER: BOB STRANSKY 10 CFR SECTION: CCCC 21.21 UNSPECIFIED PARAGRAPH UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE CODE CRIT PWR PWR 1 N N 0 COLD SHUTDOWN 0 COLD SHUTDOWN 10 CFR PART 21 REPORT - DEVIATIONS IN SAFETY RELATED BATTERY CHARGERS THE LICENSEE HAS IDENTIFIED SEVERAL DEVIATIONS IN POWER CONVERSION PRODUCTS, INC. MODEL 3SC-130-130 BATTERY CHARGERS USED IN SAFETY-RELATED APPLICATIONS. THESE DEVIATIONS INCLUDE INADEQUATE SOLDER CONNECTIONS AND INCORRECT TIME DELAY ON A HIGH VOLTAGE ALARM (DSHV) CIRCUIT CARD. IN ADDITION, AN INCORRECT DSHV RESET VOLTAGE SETPOINT WAS SPECIFIED BY SARGENT AND LUNDY.

Page Last Reviewed/Updated Wednesday, March 24, 2021

Page Last Reviewed/Updated Wednesday, March 24, 2021