The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
IE Circular No. 81-12, Inadequate Periodic Test Procedure of PWR Protection System
SSINS No.: 6830
Accession No.:
8103300406
IEC 81-12
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF INSPECTION AND ENFORCEMENT
WASHINGTON, D.C. 20555
July 22, 1981
IE Circular No. 81-12: INADEQUATE PERIODIC TEST PROCEDURE OF PWR
PROTECTION SYSTEM
Description of Circumstances:
On November 30, 1980, ground isolation procedures were being carried out to
locate an electrical ground in the 125V dc bus No. 1 at the St. Lucie
Nuclear Power Plant. Part of the procedure requires deenergizing the dc
control power to the reactor trip circuit breakers (TCBs). These breakers
are designed to trip (fail-safe mode) on undervoltage upon loss of dc
control power. Referring to Figure 1, the four TCBs (TCB 1,3,5, and 7) that
are supplied control power from dc bus No. 1 did not trip immediately
(because of binding) on undervoltage when control power was deenergized. The
operators did verify that the shunt trip for each of the four TCBs was
functioning. Operators also verified that the redundant TCBs from dc bus No.
2 (TCB 2,4,6, and 8) tripped on similar undervoltage conditions, and, in
fact, inadvertently caused a plant trip while testing. Investigation into
the problem by the licensee identified the cause of failure as an
out-of-adjustment condition in the linkage mechanism of the undervoltage
trip device. This adjustment problem, together with the lack of cleaning and
periodic relubricating of the trip shaft mechanism, is the subject of IE
Bulletin 79-09 which was issued April 17, 1979. While shutdown, the
undervoltage trip mechanism on each of the above four faulty TCBs was
adjusted and verified to operate satisfactorily.
Investigation by the licensee revealed that the reactor protection system
(RPS) periodic test procedure in use at the time did not verify the trip
function of the undervoltage trip coil independent of the shunt trip coil.
Referring to Figure 1, it can be seen that during a reactor trip test at
this facility, these coils operate simultaneously causing the trip opening
of the associated TCBs. This arrangement of the RPS and the trip test
procedure may be similar for other PWRs.
BWRs may use similar circuit breakers in safety systems; therefore, similar
inadequacies in their circuit breaker test procedures may exist.
Following adjustment of the linkage mechanism of the undervoltage trip
device the licensee instituted a revised surveillance test procedure to
check the undervoltage and shunt trip devices independently and to insure
proper breaker operation. Although not shown in Figure 1, the undervoltage
trip coil and the shunt trip coil are separately fused so that test
procedure changes resolved the problem at St. Lucie.
.
IEC 81-12
July 22, 1981
Page 2 of 2
Recommended Action for Holders of Operating Licenses and Construction
Permits:
It is recommended that holders of operating licenses and construction
permits review for applicability the specific items presented in the
"Description of Circumstances." It is further recommended that the procedure
for surveillance testing of trip circuit breakers be reviewed and revised as
necessary to provide independent testing of each trip function, including
position verification to ensure that the breaker actually trips.
If the trip circuit breakers do not have provisions for independent testing
of each trip function, including position verification, then appropriate
modifications should be made to include such features (e.g., local
pushbuttons for the shunt and undervoltage trip coils, separately fused
circuits for the shunt and undervoltage trip coils, etc).
No written response to this circular is required. If you need additional
information with regard to this subject, please contact the director of the
appropriate NRC Regional Office.
Attachments:
1. Figure 1
2. Recently issued IE Circulars
Page Last Reviewed/Updated Tuesday, March 09, 2021
Page Last Reviewed/Updated Tuesday, March 09, 2021