Bulletin 83-04: Failure of The UnderVoltage Trip Function of Reactor Trip Breakers
SSINS No.: 6820
OMB No.: 3150-00012
Expiration Date: 04/30/85
IEB 83-04
UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF INSPECTION AND ENFORCEMENT
WASHINGTON, D.C. 20555
March 11, 1983
IE BULLETIN NO. 83-04: FAILURE OF THE UNDERVOLTAGE TRIP FUNCTION OF
REACTOR TRIP BREAKERS
Addressees:
All pressurized water nuclear power reactor facilities holding an operating
license (OL) except those with Westinghouse DB type breakers for action and
to other nuclear power reactor facilities for information.
Purpose:
The purpose of this bulletin is to inform CP holders and licensees about
recent failures of General Electric AK-2 type circuit breakers to trip open
during testing of the undervoltage (UV) trip function and to require action
of operating pressurized water reactors to assure proper operation of all
reactor trip breakers in the future.
Description of Circumstances:
On March 11, 1983, Southern California Edison reported that during testing
on March 3 and 8, 1983 of reactor protective system (RPS) breakers at San
Onofre Nuclear Generating Station (SONGS) Units 2 and 3, three reactor trip
breakers on Unit 2 and one reactor trip breaker on Unit 3 failed to open on
activation of the undervoltage trip coil. Both units were shutdown at the
time of the tests. The SONGS RPS systems are designed such that a reactor
trip signal energizes the shunt trip coil and deenergizes the undervoltage
trip coil. All tests of the reactor trip breakers using the shunt trip coil
were satisfactory. A reactor scram would have occurred if an automatic or
manual signal had been generated during operation from the redundant
undervoltage and/or the shunt coils.
Background:
In some RPS designs, the automatic protection signals are fed only to the
undervoltage (UV) trip attachment of the reactor trip breakers. Other plants
may actuate both the UV device and the shunt trip coil on RPS trip.
As described above, four RPS breakers at the SONGS Units 2 and 3 failed to
open during testing. Other failures involving the GE type UV trip attachment
to the RPS have been reported to the NRC. These failures were due to either
binding or
8212060380
.
IEB 83-04
March 11, 1983
Page 2 of 3
out-of-adjustment within the linkage mechanism of the UV trip device
installed in General Electric (GE) type AK-2 (i.e., AK2A-15, 25, 50, 75,
100) circuit breakers. Failures have occurred at ANO-1, Crystal River-3,
Oconee Units 1 and 3, TMI-1, and St. Lucie. As a result of these events, the
NRC issued IE Bulletin No. 79-09 dated April 17, 1979 and I-E Circular,
81-12 dated July 20, 1981. Subsequently, failures have been reported at
ANO-1 and Rancho Seco.
Required Actions for Holders of Operating Licenses for Pressurized Water
Reactors:
PWR licensees with other than W DB type breakers in Reactor Protective
System applications are requested to:
1. Perform surveillance tests of undervoltage trip function independent of
the shunt trip function within 5 days of receipt of this Bulletin
unless equivalent testing has been performed within 10 days. Those
plants currently shutdown should complete this item before resuming
operation or within 10 days, whichever is sooner. Those plants for
which on-line testability is not provided should complete this item at
the next plant shutdown if currently operating.
2. Review the maintenance program for conformance to the latest
manufacturer's recommendation, including frequency and lubrication.
Verify actual implementation of the program. If maintenance does
not conform, initiate such maintenance within 5 days of receipt of this
bulletin or provide an alternate maintenance program. Repeat the
testing required in item 1 prior to declaring the breaker OPERABLE.
3. Notify all licensed operators of the failure-to-trip event which
occurred at Salem (see IE Bulletin 83-01) and the testing failures at
San Onofre Units 2 and 3 described above. Review the appropriate
emergency operating procedures for the event of failure-to-trip with
each operator upon his arrival on-shift.
4. Provide a written reply within 10 days of receipt of this bulletin:
a. Identify results of testing performed in response to item 1.
Plants without on-line testability should report the date and
results of the most recent test.
b. Identify conformance of the maintenance program to manufacturer's
recommendation and describe results of maintenance performed
directly as a result of this Bulletin in response to item 2.
IE Bulletin 79-09, dated April 17, 1979, had as an attachment an
extract of General Electric (GE) Service Advice Letter No. 175(CPDD)9.3
which is applicable to GE type AK-2 breakers.
.
IEB 83-04
March 11, 1983
Page 3 of 3
c. Provide a statement that provisions are in place to notify
licensed operators of the Salem and San Onofre events and bring to
their attention appropriate failure-to-trip emergency procedures
upon their arrival on-shift.
d. Provide a description of all RPS breaker malfunctions not
previously reported to the NRC.
e. Verify that procurement, testing and maintenance activities treat
the RPS breaker and UV devices as safety related. Report the
results of this verification to the NRC.
5. Any RPS breaker failure identified as a result of testing requested by
this bulletin should be promptly reported to the NRC via the emergency
notification system, regardless of the operating mode of the plant at
the time of the failure.
The written report required shall be telefaxed to Richard C. DeYoung,
Director, Office of Inspection and Enforcement within 10 days of receipt of
this bulletin. At the same time, the report shall be submitted to the
appropriate Regional Administrator under oath or affirmation under
provisions of Section 182a, Atomic Energy Act of 1954, as amended. The
original copy of the cover letters and a copy of the reports shall be
transmitted to the U. S. Nuclear Regulatory Commission, Document Control
Desk, Washington, D.C. 20555 for reproduction and distribution.
This request for information was approved by the Office of Management and
Budget under a blanket clearance number 3150-00012 which expires April 30,
1985. Comments on burden and duplication may be directed to the Office of
Management and Budget, Reports Management, Room 3208, New Executive Office
Building, Washington, D.C. 20503.
If you have any questions regarding this matter, please contact the Regional
Administrator of the NRC Regional Office or the technical contact listed
below.
Richard C. DeYoung, Director
Office of Inspection and Enforcement
Technical Contact: I. Villalva, IE V. Thomas, IE
301-492-9635 301-492-4755
Attachment:
1. List of Recently Issued IE Bulletins
Rapidfax (301) 492-8187 or (301) 492-7376
3M Remote Copies (301) 492-7285
**> **> *> *> Page Last Reviewed/Updated Tuesday, March 09, 2021
Page Last Reviewed/Updated Tuesday, March 09, 2021