Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Part 21 Report - 1999-370

LICENSEE: CD TECHNOLOGIES

SITE: CD TECHNOLOGIES EN NUMBER: 36073
DOCKET: EVENT DATE: 08-25-99
RX TYPE: EVENT TIME:
VENDORS: NOTIFY DATE: 08-25-99
EMERGENCY CLASS: N/A REGION: 1 STATE: PA TIME: 18:00
OPS OFFICER: FANGIE JONES
10 CFR SECTION: CCCC UNSPECIFIED PARAGRAPH
10CFR PART 21 REPORT DUE TO SAFETY RELATED LEAD ACID BATTERY CELL NONCONFORMANCE

A nonconformance within LCR-25 safety related lead acid battery cells manufactured by C&D for Nebraska Public Power District's(NPPD's) Cooper Nuclear facility has been discovered. The cells were purchased by NPPD and they reported to C&D that they have seen growth in the positive plates within some cells and at least one cell was removed when a short developed. Analysis of the cells has been completed by C&D, in conjunction with NPPD personnel, showing nonconforming levels of calcium within the positive grid alloy.

To the best of C&D's knowledge, no other utility has been effected by this nonconformance besides NPPD.

A final evaluation will be delivered to the NRC and to effected utilities within 30 days.