Skip to main content

Alert

Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Part 21 Report - 1998-142

LICENSEE: CLINTON POWER STATION SITE: CLINTON POWER STATION EN NUMBER:33731 DOCKET: EVENT DATE: 01-16-98 RX TYPE: EVENT TIME: 12:00 VENDORS: NOTIFY DATE: 02-17-98 EMERGENCY CLASS: N/A REGION: 3 STATE: IL TIME: 16:46 OPS OFFICER: DOUG WEAVER 10 CFR SECTION: CCCC 21.21 UNSPECIFIED PARAGRAPH 10 CFR PART 21 - DEFECTIVE SOLDERING IN A SAFETY-RELATED BATTERY CHARGER THE BASIC COMPONENTS INVOLVED ARE THE DIVISION 2 SAFETY-RELATED BATTERY CHARGER, MODEL 3SC-130-300, AND THE HIGH VOLTAGE CIRCUIT CARD, MODEL DSHV120T2-01. THESE COMPONENTS WERE SUPPLIED TO CLINTON POWER STATION BY POWER CONVERSION PRODUCTS. THE LICENSEE HAS IDENTIFIED INADEQUATE SOLDERED CONNECTIONS THROUGHOUT THE DIVISION 2 BATTERY CHARGER. IT WAS ALSO NOTED THAT THE TIME DELAY FOR THE INSTALLED DSHV CIRCUIT CARD WAS APPROXIMATELY 16 SECONDS, THE TIME DELAY FOR THE REPLACEMENT CIRCUIT CARD WAS 6 SECONDS, AND THE PURCHASE SPECIFICATION REQUIRED A 30-SECOND TIME DELAY.

Page Last Reviewed/Updated Wednesday, March 24, 2021