Part 21 Report - 1997-660
LICENSEE: BW/IP INTERNATIONAL, INC.
SITE: BW/IP INTERNATIONAL, INC. EN NUMBER:32985
DOCKET: EVENT DATE: 09-24-97
RX TYPE: EVENT TIME: 08:55
VENDORS: NOTIFY DATE: 09-24-97
EMERGENCY CLASS: N/A REGION: 4 STATE: CA TIME: 12:00
OPS OFFICER: STEVE SANDIN
10 CFR SECTION: CCCC 21.21 UNSPECIFIED PARAGRAPH
PART 21 NOTIFICATION
THE EMERGENCY SERVICE WATER PUMP, BW/IP MODEL 16-GH 4-STAGE VTP
FAILED DURING A SITE OPERABILITY TEST AT THE OYSTER CREEK
GENERATING STATION. AN INSPECTION REVEALED THAT THE THREADED
FLANGE ATTACHING THE COLUMN TO THE TOP SERIES CASE HAD FAILED.
THE UTILITY (GPU) ATTRIBUTED THE FAILURE TO DISSIMILAR METALS; A
CAST IRON FLANGE WAS INSTALLED BETWEEN THE STAINLESS STEEL COLUMN
PIPE AND A STAINLESS STEEL TOP CASE. BW/IP REVIEWED THE
UTILITIES EVALUATION AND RECOMMENDED THAT ALL SUCH PUMPS IN HIGH
ION SERVICES BE UPGRADED TO 316 STAINLESS STEEL MATERIAL.
Page Last Reviewed/Updated Wednesday, March 24, 2021