The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

Part 21 Report - 1996-850

LICENSEE: ILLINOIS POWER CO. SITE: CLINTON 1 EN NUMBER:31496 DOCKET: 05000461 EVENT DATE: 12-20-96 RX TYPE: BWR EVENT TIME: 00:00 VENDORS: GE-6 NOTIFY DATE: 12-20-96 EMERGENCY CLASS: N/A REGION: 3 STATE: IL TIME: 21:54 OPS OFFICER: RUDY KARSCH 10 CFR SECTION: CDEG 21.21(c)(3)(i) DEFECTS/NONCOMPLIANCE UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE CODE CRIT PWR PWR 1 N N 0 REFUELING 0 REFUELING WESTINGHOUSE DHP CIRCUIT BREAKERS FAILED TO CLOSE ON DEMAND DUE TO A DIRTY AND BINDING MOTOR CUT-OFF SWITCH AND SPRING CHARGE INDICATOR MECHANISM. THE VENDOR LITERATURE FAILED TO PROVIDE GUIDANCE FOR INSPECTING, CLEANING, ADJUSTING, OR LUBRICATING THESE VITAL COMPONENTS. THE LICENSEE HAS EVALUATED THIS ISSUE AND CONCLUDES THAT IT IS REPORTABLE UNDER THE PROVISIONS OF 10 CFR PART 21.