Part 21 Report - 1996-660

LICENSEE: NIAGARA MOHAWK POWER CORP. SITE: NINE MILE POINT 2 EN NUMBER:30775 DOCKET: 05000410 EVENT DATE: 07-23-96 RX TYPE: BWR EVENT TIME: 00:00 VENDORS: GE-5 NOTIFY DATE: 07-23-96 EMERGENCY CLASS: N/A REGION: 1 STATE: NY TIME: 09:00 OPS OFFICER: STEVE SANDIN 10 CFR SECTION: CCCC 21.21 UNSPECIFIED PARAGRAPH UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE CODE CRIT PWR PWR 2 N Y 100 POWER OPERATION 100 POWER OPERATION DISCOVERY OF A CONDITION AFFECTING THE OPERABILITY OF CLOW (MANUFACTURER) VALVES INSTALLED IN THE UNIT 2 STANDBY GAS TREATMENT SYSTEM THE LICENSEE DETERMINED THAT CLOW (MANUFACTURER) VALVES IN THE STANDBY GAS TREATMENT SYSTEM HAVE A DOWEL PIN INSTALLED WHICH IS NOT PEENED IN PLACE. SHOULD THESE DOWELS COME LOOSE, IT COULD INTERFERE WITH THE VALVE LIMIT SWITCHES AND PREVENT THE MAKEUP OF CIRCUIT PERMISSIVES.

Page Last Reviewed/Updated Wednesday, March 24, 2021