The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

Part 21 Report - 1996-180

LICENSEE: COMMONWEALTH EDISON CO. SITE: BRAIDWOOD 1 2 EN NUMBER:29906 DOCKET: 05000456 05000457 EVENT DATE: 01-30-96 RX TYPE: PWR PWR EVENT TIME: 00:00 VENDORS: W-4-LP W-4-LP NOTIFY DATE: 01-30-96 EMERGENCY CLASS: N/A REGION: 3 STATE: IL TIME: 14:48 OPS OFFICER: RUDY KARSCH 10 CFR SECTION: CDEG 21.21(c)(3)(i) DEFECTS/NONCOMPLIANCE UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE CODE CRIT PWR PWR 1 N Y 100 POWER OPERATION 100 POWER OPERATION 2 N Y 100 POWER OPERATION 100 POWER OPERATION THE LICENSEE REPORTED SOLDERING DEFECTS IN RELAYS USED IN EMERGENCY DIESEL GENERATORS (EDGs) AT BYRON AND BRAIDWOOD STATIONS. RELAYS MANUFACTURED BY THE AMERACE CORPORATION HAVE A COMMERCIAL GRADE ADD-ON BOARD WITH COMPONENTS TO SUPPRESS A COIL DEENERGIZATION TRANSIENT. THE LICENSEE DISCOVERED THAT THE SOLDER CONNECTION BETWEEN THE RELAY AND THIS ADD-ON BOARD IS DEFECTIVE. THE FAILURE OF THIS RELAY COULD CAUSE THE EDG TO FAIL TO START. THE LICENSEE HAS REPAIRED THE DEFECTIVE SOLDER JOINTS AND REINSTALLED THE RELAYS. DEFECTIVE RELAYS COULD BE INSTALLED AT OTHER NUCLEAR PLANTS.