Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Morning Report for January 25, 1999

                       Headquarters Daily Report

                         JANUARY 25, 1999

***************************************************************************
                    REPORT             NEGATIVE            NO INPUT
                    ATTACHED           INPUT RECEIVED      RECEIVED

HEADQUARTERS        X
REGION I                               X
REGION II                              X
REGION III                             X
REGION IV                              X
PRIORITY ATTENTION REQUIRED  MORNING REPORT - HEADQUARTERS JANUARY 25, 1999

Licensee/Facility:                     Notification:

Ge-4                                   MR Number: H-99-0008
Duane Arnold 1                         Date: 01/25/99


Subject: Change in Technical Specification (TS) Rquirements on Emergency
         Diesel Generator (EDG) surveillance requirements


Discussion:

The version of the new standard technical specification adopted by the
licensee required semi-annual surveillance of EDGs to demonstrate
acceptable voltage between 3744v and 4576v, and the frequency to range
between 59.5 and 60.5Hz within 10 seconds of starting from standby
conditions.  The licensee was unable to meet this condition on EDG
performance.  The NRC had revised this requirement in later editions of
the standard TS to have the minimum voltage and frequency achieved in 10
seconds but without the 10 second limitation for reaching the steady
state voltage and frequency.

The EDG capability to achieve steady state voltage would still need to be
trended to identify degradation of governor and voltage regulator as
discussed in the standard TS bases but achieving steady state in a
specific time is no longer an LCO (limiting conditions for operation)
requirement.

The licensee was granted an enforcement discretion to remain at power
while the TS amendment was processed.

Contact:    Thomas Koshy, PECB
            (301) 415-1176
            E-mail: txk@nrc.gov

            James Luehman, TSB
            (301) 415-3150
            E-Mail: jgl@nrc.gov