Event Notification Report for September 23, 2021
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
09/22/2021 - 09/23/2021
EVENT NUMBERS
5486455464554655546655468554695528255470554715547255473554745547555476554775547855479554805548155484
5486455464554655546655468554695528255470554715547255473554745547555476554775547855479554805548155484
Power Reactor
Event Number: 54864
Facility: Vogtle
Region: 2 State: GA
Unit: [3] [4] []
RX Type: [3] W-AP1000,[4] W-AP1000
NRC Notified By: Nick Kellenberger
HQ OPS Officer: Ossy Font
Region: 2 State: GA
Unit: [3] [4] []
RX Type: [3] W-AP1000,[4] W-AP1000
NRC Notified By: Nick Kellenberger
HQ OPS Officer: Ossy Font
Notification Date: 08/28/2020
Notification Time: 00:00 [ET]
Event Date: 08/26/2020
Event Time: 00:00 [EDT]
Last Update Date: 09/22/2021
Notification Time: 00:00 [ET]
Event Date: 08/26/2020
Event Time: 00:00 [EDT]
Last Update Date: 09/22/2021
Emergency Class: Non Emergency
10 CFR Section:
Other Unspec Reqmnt
10 CFR Section:
Other Unspec Reqmnt
Person (Organization):
MARK MILLER (R2DO)
MARK MILLER (R2DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 3 | N | N | 0 | Under Construction | 0 | Under Construction |
| 4 | N | N | 0 | Under Construction | 0 | Under Construction |
EN Revision Imported Date: 9/23/2021
EN Revision Text: DESIGN CHANGE ALTERED BASIS FOR ITAAC
"In accordance with 10 CFR 52.99(c)(2), as described in NEI 08-01, 'Industry Guideline for the ITAAC Closure Process Under 10 CFR Part 52,' Vogtle Units 3 and 4 Construction is making this notification to the NRC for determining that Inspections, Tests, Analyses and Acceptance Criteria (ITAAC) 2.5.02.07a (Index No. 534) and ITAAC 2.5.02.07e (Index No. 538) for both units require additional actions to restore their completed status. The ITAAC Closure Notifications for ITAAC 534 were submitted on March 31, 2017 (Unit 3 ML17093A286, Unit 4 ML17093A535). The ITAAC Closure Notifications for ITAAC 538 were submitted on November 30, 2016 (Unit 3 ML16351A350, Unit 4 ML16351A334).
"On August 26, 2020, it was determined that a design change, issued for several Protection and Safety Monitoring System (PMS) isolation barrier assemblies (ISBs), materially altered the basis for determining that the ITAAC 534 and ITAAC 538 Acceptance Criteria were met. The modified ISBs will require testing per IEEE 384-1981, Standard Criteria for Independence of Class 1E Equipment and Circuits, to demonstrate that the Acceptance Criteria is met. System function is not required while the plant is under construction.
"ITAAC Post Closure Notifications in accordance with 10 CFR 52.99(c)(2) will be submitted following completion of corrective actions.
"The 10 CFR 52.99(c)(4) All ITAAC Complete Notification has not been submitted for VEGP [(Vogtle Electric Generating Plant)] 3 and 4.
"The NRC Resident Inspector has been notified."
* * * UPDATE ON 9/22/21 AT 1534 EDT FROM NICK KELLENBERGER TO HOWIE CROUCH * * *
"Upon successful completion of the work to correct the identified impact to ITAAC 534, it has been determined there was no material impact to ITAAC 538. Confirmation was made that the credible fault only affected PMS to PLS analog ISBs and not PMS to PLS relay isolation ISBs. It was also confirmed that the relay isolation ISB testing and qualification summary information was unaffected by the modifications made to the analog ISBs to correct the credible fault scenario condition. Resolution of the credible fault scenario did not result in modifications to the relay isolation ISBs which are the subject of ITAAC 538. Therefore, the ITAAC Closure Notifications submitted for ITAAC 538 on November 30, 2016 (Unit 3 ML16351A350, Unit 4 ML16351A334) continue to be valid and ITAAC Post Closure Notifications are not required."
The licensee has notified NRC Region 2. Notified R2DO (Miller) and NRR Vogtle Project Office (via email).
EN Revision Text: DESIGN CHANGE ALTERED BASIS FOR ITAAC
"In accordance with 10 CFR 52.99(c)(2), as described in NEI 08-01, 'Industry Guideline for the ITAAC Closure Process Under 10 CFR Part 52,' Vogtle Units 3 and 4 Construction is making this notification to the NRC for determining that Inspections, Tests, Analyses and Acceptance Criteria (ITAAC) 2.5.02.07a (Index No. 534) and ITAAC 2.5.02.07e (Index No. 538) for both units require additional actions to restore their completed status. The ITAAC Closure Notifications for ITAAC 534 were submitted on March 31, 2017 (Unit 3 ML17093A286, Unit 4 ML17093A535). The ITAAC Closure Notifications for ITAAC 538 were submitted on November 30, 2016 (Unit 3 ML16351A350, Unit 4 ML16351A334).
"On August 26, 2020, it was determined that a design change, issued for several Protection and Safety Monitoring System (PMS) isolation barrier assemblies (ISBs), materially altered the basis for determining that the ITAAC 534 and ITAAC 538 Acceptance Criteria were met. The modified ISBs will require testing per IEEE 384-1981, Standard Criteria for Independence of Class 1E Equipment and Circuits, to demonstrate that the Acceptance Criteria is met. System function is not required while the plant is under construction.
"ITAAC Post Closure Notifications in accordance with 10 CFR 52.99(c)(2) will be submitted following completion of corrective actions.
"The 10 CFR 52.99(c)(4) All ITAAC Complete Notification has not been submitted for VEGP [(Vogtle Electric Generating Plant)] 3 and 4.
"The NRC Resident Inspector has been notified."
* * * UPDATE ON 9/22/21 AT 1534 EDT FROM NICK KELLENBERGER TO HOWIE CROUCH * * *
"Upon successful completion of the work to correct the identified impact to ITAAC 534, it has been determined there was no material impact to ITAAC 538. Confirmation was made that the credible fault only affected PMS to PLS analog ISBs and not PMS to PLS relay isolation ISBs. It was also confirmed that the relay isolation ISB testing and qualification summary information was unaffected by the modifications made to the analog ISBs to correct the credible fault scenario condition. Resolution of the credible fault scenario did not result in modifications to the relay isolation ISBs which are the subject of ITAAC 538. Therefore, the ITAAC Closure Notifications submitted for ITAAC 538 on November 30, 2016 (Unit 3 ML16351A350, Unit 4 ML16351A334) continue to be valid and ITAAC Post Closure Notifications are not required."
The licensee has notified NRC Region 2. Notified R2DO (Miller) and NRR Vogtle Project Office (via email).
Agreement State
Event Number: 55464
Rep Org: WA OFFICE OF RADIATION PROTECTION
Licensee: University of Washington Environmental Health and Safety
Region: 4
City: Seattle State: WA
County:
License #: C001
Agreement: Y
Docket:
NRC Notified By: Tristan Hay
HQ OPS Officer: Brian Lin
Licensee: University of Washington Environmental Health and Safety
Region: 4
City: Seattle State: WA
County:
License #: C001
Agreement: Y
Docket:
NRC Notified By: Tristan Hay
HQ OPS Officer: Brian Lin
Notification Date: 09/15/2021
Notification Time: 14:19 [ET]
Event Date: 08/13/2021
Event Time: 00:00 [PDT]
Last Update Date: 09/15/2021
Notification Time: 14:19 [ET]
Event Date: 08/13/2021
Event Time: 00:00 [PDT]
Last Update Date: 09/15/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
CNSC (CANADA), - (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
CNSC (CANADA), - (EMAIL)
EN Revision Imported Date: 9/23/2021
EN Revision Text: AGREEMENT STATE REPORT - MISSING RADIOACTIVE SOURCES
The following is summary of information received from the state of Washington via email:
On August 13, 2021, the University of Washington Radiation Safety concluded that it was unable to locate two Gd-148 sources with activity totaling 0.0882 microCi and one Am-241 source with activity 0.982 microCi. Internal radiation exposure to these sources is highly unlikely, and any external exposure to the sources would not be considered a public health and safety concern. It is probable that the sources are still in the facility, but since they cannot be located they are considered missing. The root cause of the problem is a lack of documentation of source use and storage locations. Corrective actions were taken by Radiation Safety to prevent future loss of material.
WA incident no.: WA-21-021
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - MISSING RADIOACTIVE SOURCES
The following is summary of information received from the state of Washington via email:
On August 13, 2021, the University of Washington Radiation Safety concluded that it was unable to locate two Gd-148 sources with activity totaling 0.0882 microCi and one Am-241 source with activity 0.982 microCi. Internal radiation exposure to these sources is highly unlikely, and any external exposure to the sources would not be considered a public health and safety concern. It is probable that the sources are still in the facility, but since they cannot be located they are considered missing. The root cause of the problem is a lack of documentation of source use and storage locations. Corrective actions were taken by Radiation Safety to prevent future loss of material.
WA incident no.: WA-21-021
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 55465
Rep Org: ARKANSAS DEPARTMENT OF HEALTH
Licensee: 3D Imaging Drug Design Development
Region: 4
City: Little Rock State: AR
County:
License #: ARK-1008-03214
Agreement: Y
Docket:
NRC Notified By: Chris Talley
HQ OPS Officer: Brian Lin
Licensee: 3D Imaging Drug Design Development
Region: 4
City: Little Rock State: AR
County:
License #: ARK-1008-03214
Agreement: Y
Docket:
NRC Notified By: Chris Talley
HQ OPS Officer: Brian Lin
Notification Date: 09/15/2021
Notification Time: 15:17 [ET]
Event Date: 06/16/2021
Event Time: 00:00 [CDT]
Last Update Date: 09/15/2021
Notification Time: 15:17 [ET]
Event Date: 06/16/2021
Event Time: 00:00 [CDT]
Last Update Date: 09/15/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/23/2021
EN Revision Text: AGREEMENT STATE REPORT - MISSING RADIOACTIVE SHIPMENT
The following information was received from the state of Arkansas (the Department) via email:
"The Department received notification on June 16, 2021, from licensee 3D Imaging Drug Design and Development, 3DI, that a package containing 87 milliCi of Zr-89 did not reach its shipping destination.
"Upon review of the event, the Licensee transferred the package via [common carrier] pick-up from its Little Rock, Arkansas campus on Saturday June 12, 2021, with a scheduled delivery date of June 14, 2021. The package destination was:
"Memorial Sloan Kettering
1275 York Avenue
New York City, New York
"On June 16, 2021, the package was reported missing to the Department and the activity of the package was estimated to be approximately 30 milliCi based on the 3.2 day half-life of Zr-89.
"The licensee had contacted the [common carrier] and the [common carrier] stated that they were unable to locate the package. Department inspectors visited the 3DI campus on June 18, 2021 and questioned the Licensee about the lost package. At that time, and currently, the [common carrier] has been unable to locate the package. The Department has spoken with multiple individuals associated with the [common carrier], both at the Little Rock location and with the companies Dangerous Goods Administration Department, about the lost package. The Department has also followed up with 3DI.
"The associates at the [common carrier] were able to confirm that the package was received and scanned. After acceptance, and the initial scan of the package, there are no other scans available to determine what has happened to the package. 3DI stated that the company has experienced additional shipping problems since the lost package. 3DI has had additional packages that have been scanned and shipped to Licensees other than the intended recipient. All additional packages have been able to be located and recovered or reach their final destination successfully.
"The initial package of Zr-89 remains missing. The Department has requested and is awaiting the 30 Day report from 3DI as required. The Department considers this incident open pending location of the missing package and will update this report as information is received. "
AR incident no.: AR-2021-007
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf"
EN Revision Text: AGREEMENT STATE REPORT - MISSING RADIOACTIVE SHIPMENT
The following information was received from the state of Arkansas (the Department) via email:
"The Department received notification on June 16, 2021, from licensee 3D Imaging Drug Design and Development, 3DI, that a package containing 87 milliCi of Zr-89 did not reach its shipping destination.
"Upon review of the event, the Licensee transferred the package via [common carrier] pick-up from its Little Rock, Arkansas campus on Saturday June 12, 2021, with a scheduled delivery date of June 14, 2021. The package destination was:
"Memorial Sloan Kettering
1275 York Avenue
New York City, New York
"On June 16, 2021, the package was reported missing to the Department and the activity of the package was estimated to be approximately 30 milliCi based on the 3.2 day half-life of Zr-89.
"The licensee had contacted the [common carrier] and the [common carrier] stated that they were unable to locate the package. Department inspectors visited the 3DI campus on June 18, 2021 and questioned the Licensee about the lost package. At that time, and currently, the [common carrier] has been unable to locate the package. The Department has spoken with multiple individuals associated with the [common carrier], both at the Little Rock location and with the companies Dangerous Goods Administration Department, about the lost package. The Department has also followed up with 3DI.
"The associates at the [common carrier] were able to confirm that the package was received and scanned. After acceptance, and the initial scan of the package, there are no other scans available to determine what has happened to the package. 3DI stated that the company has experienced additional shipping problems since the lost package. 3DI has had additional packages that have been scanned and shipped to Licensees other than the intended recipient. All additional packages have been able to be located and recovered or reach their final destination successfully.
"The initial package of Zr-89 remains missing. The Department has requested and is awaiting the 30 Day report from 3DI as required. The Department considers this incident open pending location of the missing package and will update this report as information is received. "
AR incident no.: AR-2021-007
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf"
Agreement State
Event Number: 55466
Rep Org: OK DEQ RAD MANAGEMENT
Licensee: CEC Corporation
Region: 4
City: Oklahoma City State: OK
County:
License #: OK-31047-01
Agreement: Y
Docket:
NRC Notified By: Kevin Sampson
HQ OPS Officer: Howie Crouch
Licensee: CEC Corporation
Region: 4
City: Oklahoma City State: OK
County:
License #: OK-31047-01
Agreement: Y
Docket:
NRC Notified By: Kevin Sampson
HQ OPS Officer: Howie Crouch
Notification Date: 09/13/2021
Notification Time: 14:53 [ET]
Event Date: 09/13/2021
Event Time: 00:00 [CDT]
Last Update Date: 09/16/2021
Notification Time: 14:53 [ET]
Event Date: 09/13/2021
Event Time: 00:00 [CDT]
Last Update Date: 09/16/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - DAMAGED TROXLER MOISTURE DENSITY GAUGE
The following information was received from the state of Oklahoma via email:
"We [Oklahoma Department of Environmental Quality] have been informed that earlier today a Troxler Model 3440 gauge was struck by a truck in Oklahoma City. The gauge belonged to CEC Corp. (OK-31047-01). Surveys of the gauge indicated that the shielding was intact. [The State] will provide more information as it becomes available."
Troxler Model 3440 gauges contain 40 mCi Am241:Be and 8 mCi Cs-137 sources.
EN Revision Text: AGREEMENT STATE REPORT - DAMAGED TROXLER MOISTURE DENSITY GAUGE
The following information was received from the state of Oklahoma via email:
"We [Oklahoma Department of Environmental Quality] have been informed that earlier today a Troxler Model 3440 gauge was struck by a truck in Oklahoma City. The gauge belonged to CEC Corp. (OK-31047-01). Surveys of the gauge indicated that the shielding was intact. [The State] will provide more information as it becomes available."
Troxler Model 3440 gauges contain 40 mCi Am241:Be and 8 mCi Cs-137 sources.
Agreement State
Event Number: 55468
Rep Org: CALIFORNIA RADIATION CONTROL PRGM
Licensee: Mistras Group
Region: 4
City: Richmond State: CA
County:
License #: 4886-48
Agreement: Y
Docket:
NRC Notified By: K. Arunika Hewadikaram
HQ OPS Officer: Brian Lin
Licensee: Mistras Group
Region: 4
City: Richmond State: CA
County:
License #: 4886-48
Agreement: Y
Docket:
NRC Notified By: K. Arunika Hewadikaram
HQ OPS Officer: Brian Lin
Notification Date: 09/16/2021
Notification Time: 14:01 [ET]
Event Date: 09/13/2021
Event Time: 00:00 [PDT]
Last Update Date: 09/16/2021
Notification Time: 14:01 [ET]
Event Date: 09/13/2021
Event Time: 00:00 [PDT]
Last Update Date: 09/16/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - RADIOGRAPHY DEVICE MALFUNCTION
The following information was received from the state of California via email:
"On 9/14/2021, the licensee contacted the Radiation Health Branch (RHB) to report an incident that occurred on 9/13/2021 in which a radiography exposure device failed to retract to the fully shielded position. The licensee reported that after completing their second exposure shot, the radiography crew cranked the source to the fully shielded position which actuated the fully shielded source position indicator. The crew reverse cranked the source to confirm that the source was locked into the fully shielded position and discovered that the source was still exposed. The radiographers were able to lock the source into the final position after manipulating the locking mechanism manually. The licensee reported an exposure maximum of 33 millirem to one of the radiographers due to this incident. At this time, the licensee does not expect an overexposure to either radiographers nor members of the public. RHB will be investigating this incident further."
EN Revision Text: AGREEMENT STATE REPORT - RADIOGRAPHY DEVICE MALFUNCTION
The following information was received from the state of California via email:
"On 9/14/2021, the licensee contacted the Radiation Health Branch (RHB) to report an incident that occurred on 9/13/2021 in which a radiography exposure device failed to retract to the fully shielded position. The licensee reported that after completing their second exposure shot, the radiography crew cranked the source to the fully shielded position which actuated the fully shielded source position indicator. The crew reverse cranked the source to confirm that the source was locked into the fully shielded position and discovered that the source was still exposed. The radiographers were able to lock the source into the final position after manipulating the locking mechanism manually. The licensee reported an exposure maximum of 33 millirem to one of the radiographers due to this incident. At this time, the licensee does not expect an overexposure to either radiographers nor members of the public. RHB will be investigating this incident further."
Agreement State
Event Number: 55469
Rep Org: MA RADIATION CONTROL PROGRAM
Licensee: Radiation Monitoring Devices Inc.
Region: 1
City: Watertown State: MA
County:
License #: 41-0171
Agreement: Y
Docket:
NRC Notified By: Kenath Traegde
HQ OPS Officer: Brian Lin
Licensee: Radiation Monitoring Devices Inc.
Region: 1
City: Watertown State: MA
County:
License #: 41-0171
Agreement: Y
Docket:
NRC Notified By: Kenath Traegde
HQ OPS Officer: Brian Lin
Notification Date: 09/16/2021
Notification Time: 17:05 [ET]
Event Date: 08/16/2021
Event Time: 00:00 [EDT]
Last Update Date: 09/16/2021
Notification Time: 17:05 [ET]
Event Date: 08/16/2021
Event Time: 00:00 [EDT]
Last Update Date: 09/16/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
BOWER, FRED (R1)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
BOWER, FRED (R1)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - MISSING RADIOACTIVE SOURCE
The following information was received from the Commonwealth of Massachusetts via email:
"On September 16, 2021, at 1020 [EDT], the licensee notified the Massachusetts Radiation Control Program (RCP) via telephone of a missing 5 millicurie Cs-137 sealed source. The source has been missing since the last inventory performed by the licensee on August 16, 2021. Upon discovery, the licensee subsequently searched for the source with survey meters on their licensed premises and could not locate it. Personnel involved with the use of the source were immediately interviewed and later all employees were interviewed. To the date of this report the licensee has not found the source.
"The only item related to the source that was discovered was the top cover to the lead shielding container. The shielding cylinder and the sealed Cs-137 source are still missing.
"The licensee written report and RCP on-site inspection are pending. The Agency considers this matter still OPEN."
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - MISSING RADIOACTIVE SOURCE
The following information was received from the Commonwealth of Massachusetts via email:
"On September 16, 2021, at 1020 [EDT], the licensee notified the Massachusetts Radiation Control Program (RCP) via telephone of a missing 5 millicurie Cs-137 sealed source. The source has been missing since the last inventory performed by the licensee on August 16, 2021. Upon discovery, the licensee subsequently searched for the source with survey meters on their licensed premises and could not locate it. Personnel involved with the use of the source were immediately interviewed and later all employees were interviewed. To the date of this report the licensee has not found the source.
"The only item related to the source that was discovered was the top cover to the lead shielding container. The shielding cylinder and the sealed Cs-137 source are still missing.
"The licensee written report and RCP on-site inspection are pending. The Agency considers this matter still OPEN."
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Part 21
Event Number: 55282
Rep Org: FRAMATOME ANP
Licensee: Framatome Inc.
Region: 1
City: Lynchburg State: VA
County:
License #:
Agreement: Y
Docket:
NRC Notified By: Gayle Eliott
HQ OPS Officer: Kerby Scales
Licensee: Framatome Inc.
Region: 1
City: Lynchburg State: VA
County:
License #:
Agreement: Y
Docket:
NRC Notified By: Gayle Eliott
HQ OPS Officer: Kerby Scales
Notification Date: 05/28/2021
Notification Time: 16:36 [ET]
Event Date: 05/28/2021
Event Time: 00:00 [EDT]
Last Update Date: 09/23/2021
Notification Time: 16:36 [ET]
Event Date: 05/28/2021
Event Time: 00:00 [EDT]
Last Update Date: 09/23/2021
Emergency Class: Non Emergency
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
Person (Organization):
MILLER, MARK (R2DO)
PART 21/50.55 REACTORS, - (EMAIL)
MILLER, MARK (R2DO)
PART 21/50.55 REACTORS, - (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: PART 21 REPORT - VACUUM BREAKERS FAILURE TO CLOSE
The following is a summary of the report provided by Framatome Inc.:
Identification of Component: Siemens 5kV 1200A Vacuum Breakers - 5-DPU-350-1200-78
Nature of Defect:
Framtome reported during dedication testing / inspection that a batch of 5-DPU-350-1200-78 MV vacuum breakers exhibited sporadic failure to close upon both electrical and mechanical closure signals. This was entered in their Corrective Action Program and troubleshooting / testing was completed at the Siemens manufacturing facility. Using a high speed camera to troubleshoot, they determined the close latch does not have sufficient torsional force to consistently maintain the breaker close latch in the closed position during the closing cycle. In some instances the breaker will receive a close signal and the close latch will not maintain the breaker in a closed position and the breaker will fail to close. It has been observed in testing that this condition is sporadic and that subsequent attempts to close the breaker will result in a closed breaker. The issue has no impact on the breakers staying closed once they have successfully closed. The issue has no impact on the ability for the breakers to open.
Number and Location of Basic Components:
The reportable defect is similar to design on the 22 breakers delivered and 19 installed at St. Lucie Unit 1, during refueling cycle 30. St. Lucie was notified on May 28, 2021 by Framatome Inc. via telephone and email.
Corrective Actions to Date:
Preliminary evaluation determined a modification of the breakers is required to increase the torsion spring force acting on the close latch. Framatome is working with Siemens to develop a long-term solution to increase the torsional spring force acting on the close latch. An interim solution utilizing a revised spring retaining bracket could be deployed near-term.
Gayle Elliott
Deputy Director, Licensing & Regulatory Affairs
Framatome Inc.
3315 Old Forest Road
Lynchburg, Va. 24501
Office (434-832-3347)
Mobile (434-841-0306)
* * * UPDATE FROM GAYLE ELLIOT TO HOWIE CROUCH AT 1538 EDT ON 9/23/21 * * *
The following information was received from Framatome via email:
"The preliminary evaluation determined a modification of the breakers was required to increase the torsion spring force acting on the close latch. Framatome worked with Siemens to develop an interim and long-term solution. The interim solution utilized a revised spring retaining bracket that could be deployed near-term. The original long-term solution was a new torsion spring design which applied approximately 40 percent more torsional force on the trip latch.
"Following a reoccurrence of the failure-to-close issue, Framatome and Siemens identified the root cause of the trip latch bounce and [determined] the associated corrective actions. The solution developed will mitigate all main failure to close causes (low power to the closing mechanism, insufficient time for the trip latch to drop, and improper trip latch to jackshaft interaction) for the 5kV replacement circuit breakers. The solution consists of the following:
1) Circuit breakers comply with the following revised design performance parameters:
a. Jackshaft rotational speed (C speed #2)
b. Jackshaft overtravel
c. Jackshaft overtravel duration
2) Circuit breakers have the new torsion spring installed
3) Circuit breakers meet the revised bump stop gap
"By increasing the bump stop gap, the jackshaft is now able to rotate further before it hits the bump stop. This reduces the amount of force transferred to the bump stop and in turn the operating mechanism. This reduction significantly reduces the amount of latch bounce for this breaker design.
"St. Lucie was first notified of this 10CFR21 reportable defect on May 28, 2021 by Framatome Inc. via telephone and email."
Notified R2DO (Miller) and Part 21 group via email.
EN Revision Text: PART 21 REPORT - VACUUM BREAKERS FAILURE TO CLOSE
The following is a summary of the report provided by Framatome Inc.:
Identification of Component: Siemens 5kV 1200A Vacuum Breakers - 5-DPU-350-1200-78
Nature of Defect:
Framtome reported during dedication testing / inspection that a batch of 5-DPU-350-1200-78 MV vacuum breakers exhibited sporadic failure to close upon both electrical and mechanical closure signals. This was entered in their Corrective Action Program and troubleshooting / testing was completed at the Siemens manufacturing facility. Using a high speed camera to troubleshoot, they determined the close latch does not have sufficient torsional force to consistently maintain the breaker close latch in the closed position during the closing cycle. In some instances the breaker will receive a close signal and the close latch will not maintain the breaker in a closed position and the breaker will fail to close. It has been observed in testing that this condition is sporadic and that subsequent attempts to close the breaker will result in a closed breaker. The issue has no impact on the breakers staying closed once they have successfully closed. The issue has no impact on the ability for the breakers to open.
Number and Location of Basic Components:
The reportable defect is similar to design on the 22 breakers delivered and 19 installed at St. Lucie Unit 1, during refueling cycle 30. St. Lucie was notified on May 28, 2021 by Framatome Inc. via telephone and email.
Corrective Actions to Date:
Preliminary evaluation determined a modification of the breakers is required to increase the torsion spring force acting on the close latch. Framatome is working with Siemens to develop a long-term solution to increase the torsional spring force acting on the close latch. An interim solution utilizing a revised spring retaining bracket could be deployed near-term.
Gayle Elliott
Deputy Director, Licensing & Regulatory Affairs
Framatome Inc.
3315 Old Forest Road
Lynchburg, Va. 24501
Office (434-832-3347)
Mobile (434-841-0306)
* * * UPDATE FROM GAYLE ELLIOT TO HOWIE CROUCH AT 1538 EDT ON 9/23/21 * * *
The following information was received from Framatome via email:
"The preliminary evaluation determined a modification of the breakers was required to increase the torsion spring force acting on the close latch. Framatome worked with Siemens to develop an interim and long-term solution. The interim solution utilized a revised spring retaining bracket that could be deployed near-term. The original long-term solution was a new torsion spring design which applied approximately 40 percent more torsional force on the trip latch.
"Following a reoccurrence of the failure-to-close issue, Framatome and Siemens identified the root cause of the trip latch bounce and [determined] the associated corrective actions. The solution developed will mitigate all main failure to close causes (low power to the closing mechanism, insufficient time for the trip latch to drop, and improper trip latch to jackshaft interaction) for the 5kV replacement circuit breakers. The solution consists of the following:
1) Circuit breakers comply with the following revised design performance parameters:
a. Jackshaft rotational speed (C speed #2)
b. Jackshaft overtravel
c. Jackshaft overtravel duration
2) Circuit breakers have the new torsion spring installed
3) Circuit breakers meet the revised bump stop gap
"By increasing the bump stop gap, the jackshaft is now able to rotate further before it hits the bump stop. This reduces the amount of force transferred to the bump stop and in turn the operating mechanism. This reduction significantly reduces the amount of latch bounce for this breaker design.
"St. Lucie was first notified of this 10CFR21 reportable defect on May 28, 2021 by Framatome Inc. via telephone and email."
Notified R2DO (Miller) and Part 21 group via email.
Agreement State
Event Number: 55470
Rep Org: COLORADO DEPT OF HEALTH
Licensee: Cheddars Casual Caf‚
Region: 4
City: Colorado Springs State: CO
County:
License #: GL002038
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Ossy Font
Licensee: Cheddars Casual Caf‚
Region: 4
City: Colorado Springs State: CO
County:
License #: GL002038
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Ossy Font
Notification Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 07/06/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 07/06/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - TWO LOST TRITIUM EXIT SIGNS
The following was received from the Colorado Department of Health via email:
"Two exit signs, containing 7.09 Ci of tritium each, were reported as lost during annual registration. The owner recalled that the signs had been removed many years ago."
NMED No.: CO210020
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - TWO LOST TRITIUM EXIT SIGNS
The following was received from the Colorado Department of Health via email:
"Two exit signs, containing 7.09 Ci of tritium each, were reported as lost during annual registration. The owner recalled that the signs had been removed many years ago."
NMED No.: CO210020
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 55471
Rep Org: COLORADO DEPT OF HEALTH
Licensee: T-Mobile - Greeley
Region: 4
City: Greeley State: CO
County:
License #: GL002207
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Licensee: T-Mobile - Greeley
Region: 4
City: Greeley State: CO
County:
License #: GL002207
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Notification Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 08/04/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 08/04/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - FOUR LOST TRITIUM EXIT SIGNS
The following was received from the Colorado Department of Health via email:
"Four exit signs, each containing 6.2 Ci of tritium, were reported as lost during annual registration. New owner as of 04/01/2021. Upon inspecting the property, unable to locate signs registered with the State."
NMED No.: CO210029
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - FOUR LOST TRITIUM EXIT SIGNS
The following was received from the Colorado Department of Health via email:
"Four exit signs, each containing 6.2 Ci of tritium, were reported as lost during annual registration. New owner as of 04/01/2021. Upon inspecting the property, unable to locate signs registered with the State."
NMED No.: CO210029
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 55472
Rep Org: COLORADO DEPT OF HEALTH
Licensee: Davis Partnership Architects PC
Region: 4
City: Denver State: CO
County:
License #: GL000674
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Licensee: Davis Partnership Architects PC
Region: 4
City: Denver State: CO
County:
License #: GL000674
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Notification Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/16/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/16/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following was received from the Colorado Department of Health via email:
"One exit sign, containing 7.5 Ci of tritium, was reported as lost during annual registration."
NMED No.: CO210028
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following was received from the Colorado Department of Health via email:
"One exit sign, containing 7.5 Ci of tritium, was reported as lost during annual registration."
NMED No.: CO210028
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 55473
Rep Org: COLORADO DEPT OF HEALTH
Licensee: University of Colorado - Denver
Region: 4
City: Denver State: CO
County:
License #: GL002538
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Licensee: University of Colorado - Denver
Region: 4
City: Denver State: CO
County:
License #: GL002538
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Notification Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/30/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/30/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following was received from the Colorado Department of Health via email:
"One exit sign, containing 17.5 Ci of tritium, was reported as lost during annual registration. An exhaustive search resulted in the belief that the contractor never installed the sign."
NMED No.: CO210027
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following was received from the Colorado Department of Health via email:
"One exit sign, containing 17.5 Ci of tritium, was reported as lost during annual registration. An exhaustive search resulted in the belief that the contractor never installed the sign."
NMED No.: CO210027
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 55474
Rep Org: COLORADO DEPT OF HEALTH
Licensee: Westin Hotel - Wildwood Lodge
Region: 4
City: Snowmass Village State: CO
County:
License #: GL002217
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Licensee: Westin Hotel - Wildwood Lodge
Region: 4
City: Snowmass Village State: CO
County:
License #: GL002217
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Notification Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/27/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/27/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following was received from the Colorado Department of Health via email:
"One exit sign, containing 9.2 Ci of Tritium, was reported as lost during annual registration. The owner was not able to locate the sign on the property and the owner was unsure of when the sign was removed."
NMED No.: CO210026
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following was received from the Colorado Department of Health via email:
"One exit sign, containing 9.2 Ci of Tritium, was reported as lost during annual registration. The owner was not able to locate the sign on the property and the owner was unsure of when the sign was removed."
NMED No.: CO210026
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 55475
Rep Org: COLORADO DEPT OF HEALTH
Licensee: Brodie Management
Region: 4
City: Westminster State: CO
County:
License #: GL002447
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Licensee: Brodie Management
Region: 4
City: Westminster State: CO
County:
License #: GL002447
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Notification Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 07/09/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 07/09/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following was received from the Colorado Department of Health via email:
"One exit sign, containing 7.5 Ci of tritium, was reported as lost during annual registration. There was a change of ownership in 2019. The sign was lost or replaced prior to new ownership."
NMED No.: CO210025
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following was received from the Colorado Department of Health via email:
"One exit sign, containing 7.5 Ci of tritium, was reported as lost during annual registration. There was a change of ownership in 2019. The sign was lost or replaced prior to new ownership."
NMED No.: CO210025
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 55476
Rep Org: COLORADO DEPT OF HEALTH
Licensee: Town of Lyons
Region: 4
City: Lyons State: CO
County:
License #: GL002040
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Ossy Font
Licensee: Town of Lyons
Region: 4
City: Lyons State: CO
County:
License #: GL002040
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Ossy Font
Notification Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/09/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/09/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following was received from the Colorado Department of Health via email:
"One exit sign, containing 7.03 Ci of tritium, reported as lost during annual registration. The business moved to a new location. It was most likely disposed of with other demolition debris when vacated."
NMED No.: CO210021
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following was received from the Colorado Department of Health via email:
"One exit sign, containing 7.03 Ci of tritium, reported as lost during annual registration. The business moved to a new location. It was most likely disposed of with other demolition debris when vacated."
NMED No.: CO210021
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 55477
Rep Org: COLORADO DEPT OF HEALTH
Licensee: One Renaissance LLC
Region: 4
City: Denver State: CO
County:
License #: GL002564
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Licensee: One Renaissance LLC
Region: 4
City: Denver State: CO
County:
License #: GL002564
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Donald Norwood
Notification Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 07/01/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 07/01/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following information was received via email:
"One exit sign, containing 12.57 Ci of tritium, was reported as lost during annual registration. The location of the sign is unknown."
NMED No.: CO210024
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - LOST TRITIUM EXIT SIGN
The following information was received via email:
"One exit sign, containing 12.57 Ci of tritium, was reported as lost during annual registration. The location of the sign is unknown."
NMED No.: CO210024
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 55478
Rep Org: COLORADO DEPT OF HEALTH
Licensee: Rocky Mountain Bottling Co.
Region: 4
City: Wheat Ridge State: CO
County:
License #: GL000979
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Ossy Font
Licensee: Rocky Mountain Bottling Co.
Region: 4
City: Wheat Ridge State: CO
County:
License #: GL000979
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Ossy Font
Notification Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/22/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/22/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - TWO LOST TRITIUM EXIT SIGNS
The following was received from the Colorado Department of Health via email:
"Two exit signs, containing 9.2 Ci and 10 Ci of tritium, reported as lost during the annual registration. The timeframe of removal is unknown."
NMED No.: CO210022
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - TWO LOST TRITIUM EXIT SIGNS
The following was received from the Colorado Department of Health via email:
"Two exit signs, containing 9.2 Ci and 10 Ci of tritium, reported as lost during the annual registration. The timeframe of removal is unknown."
NMED No.: CO210022
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 55479
Rep Org: COLORADO DEPT OF HEALTH
Licensee: Five Rivers Cattle Feeding
Region: 4
City: LaSalle State: CO
County:
License #: GL002226
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Ossy Font
Licensee: Five Rivers Cattle Feeding
Region: 4
City: LaSalle State: CO
County:
License #: GL002226
Agreement: Y
Docket:
NRC Notified By: Kathryn Mote
HQ OPS Officer: Ossy Font
Notification Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/30/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Notification Time: 13:46 [ET]
Event Date: 06/30/2021
Event Time: 00:00 [MDT]
Last Update Date: 09/17/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - TWO LOST TRITIUM EXIT SIGNS
The following was received from the Colorado Department of Health via email:
"Two exit signs, containing 6.2 Ci of tritium each, reported as lost during the annual registration. Licensee is unable to locate."
NMED No.: CO210023
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - TWO LOST TRITIUM EXIT SIGNS
The following was received from the Colorado Department of Health via email:
"Two exit signs, containing 6.2 Ci of tritium each, reported as lost during the annual registration. Licensee is unable to locate."
NMED No.: CO210023
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Fuel Cycle Facility
Event Number: 55480
Facility: Louisiana Energy Services
Region: 2 State: NM
Unit: [] [] []
RX Type:
NRC Notified By: Blake Bixenman
HQ OPS Officer: Ossy Font
Region: 2 State: NM
Unit: [] [] []
RX Type:
NRC Notified By: Blake Bixenman
HQ OPS Officer: Ossy Font
Notification Date: 09/17/2021
Notification Time: 16:55 [ET]
Event Date: 07/20/2021
Event Time: 14:01 [MDT]
Last Update Date: 09/17/2021
Notification Time: 16:55 [ET]
Event Date: 07/20/2021
Event Time: 14:01 [MDT]
Last Update Date: 09/17/2021
Emergency Class: Non Emergency
10 CFR Section:
70.50(b)(2) - Safety Equipment Failure
10 CFR Section:
70.50(b)(2) - Safety Equipment Failure
Person (Organization):
NMSS_EVENTS_NOTIFICATION (EMAIL)
MILLER, MARK (R2DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
MILLER, MARK (R2DO)
EN Revision Imported Date: 9/24/2021
EN Revision Text: CAAS ALARM NOT CLEARLY AUDIBLE
During routine Criticality Accident Alarm System (CAAS) maintenance on July 20, 2021, UUSA [(URENCO USA)] staff identified an area in which the CAAS alarm was not clearly audible. The alarm was (and is) functioning, but not at an adequate level of sound pressure to meet the acceptance criteria. UUSA arranged compensatory measures which achieve an equivalent safety function within 24 hours in the affected area. The affected area was in the Immediate Evacuation Zone (IEZ), outside of the area in which licensed special nuclear material is handled, used, or stored.
On September 16, 2021, an NRC inspector conducting an onsite inspection informed UUSA staff that given the potential that the alarm had not been clearly audible for a period of time between surveillances, this event should have been reported within 24 hours to the NRC in accordance with 10 CFR 70.50(b)(2) in which equipment is disabled or fails to function as designed when required by regulation (10 CFR 70.24).
The licensee will notify the NRC Region 2.
EN Revision Text: CAAS ALARM NOT CLEARLY AUDIBLE
During routine Criticality Accident Alarm System (CAAS) maintenance on July 20, 2021, UUSA [(URENCO USA)] staff identified an area in which the CAAS alarm was not clearly audible. The alarm was (and is) functioning, but not at an adequate level of sound pressure to meet the acceptance criteria. UUSA arranged compensatory measures which achieve an equivalent safety function within 24 hours in the affected area. The affected area was in the Immediate Evacuation Zone (IEZ), outside of the area in which licensed special nuclear material is handled, used, or stored.
On September 16, 2021, an NRC inspector conducting an onsite inspection informed UUSA staff that given the potential that the alarm had not been clearly audible for a period of time between surveillances, this event should have been reported within 24 hours to the NRC in accordance with 10 CFR 70.50(b)(2) in which equipment is disabled or fails to function as designed when required by regulation (10 CFR 70.24).
The licensee will notify the NRC Region 2.
Agreement State
Event Number: 55481
Rep Org: TEXAS DEPT OF STATE HEALTH SERVICES
Licensee: T S I Laboratories INC
Region: 4
City: Victoria State: TX
County:
License #: L 04767
Agreement: Y
Docket:
NRC Notified By: Art Tucker
HQ OPS Officer: Ossy Font
Licensee: T S I Laboratories INC
Region: 4
City: Victoria State: TX
County:
License #: L 04767
Agreement: Y
Docket:
NRC Notified By: Art Tucker
HQ OPS Officer: Ossy Font
Notification Date: 09/17/2021
Notification Time: 22:14 [ET]
Event Date: 09/17/2021
Event Time: 00:00 [CDT]
Last Update Date: 09/20/2021
Notification Time: 22:14 [ET]
Event Date: 09/17/2021
Event Time: 00:00 [CDT]
Last Update Date: 09/20/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
AZUA, RAY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
EN Revision Imported Date: 9/24/2021
EN Revision Text: AGREEMENT STATE REPORT - DAMAGED MOISTURE DENSITY GAUGE
The following was received from the Texas Department of State Health Services (the Agency) via email:
"On September 17, 2021, the Agency was notified by the licensee that a Troxler 3411 moisture density gauge containing a 40 milliCurie americium - 241 source and an 8 milliCurie cesium - 137 source was damaged at a temporary job site. The licensee reported that while the gauge was sitting on the ground and not being used it was run over by a bulldozer, snapping the operating arm of the cesium source. The source was in the shielded position when the event occurred and a radiation survey of the gauge after the event verified it was still fully shielded. The licensee stated the gauge would be returned to its storage location and arrangements would be made to have the gauge disposed of. No individual received an exposure that exceeded any limit. Additional information will be provided as it is received in accordance with SA-300."
Texas Incident No.: 9885
* * * UPDATE FROM ART TUCKER TO THOMAS HERRITY AT 11:23 ON 09/20/21 * * *
The following information was received via e-mail:
"Received pictures of the gauge. Pictures show the rod for the cesium source was bent. The dose rate meter appears to be reading 0.8 millirem per hour."
Notified R4DO (YOUNG) and NMSS Events Notification group.
EN Revision Text: AGREEMENT STATE REPORT - DAMAGED MOISTURE DENSITY GAUGE
The following was received from the Texas Department of State Health Services (the Agency) via email:
"On September 17, 2021, the Agency was notified by the licensee that a Troxler 3411 moisture density gauge containing a 40 milliCurie americium - 241 source and an 8 milliCurie cesium - 137 source was damaged at a temporary job site. The licensee reported that while the gauge was sitting on the ground and not being used it was run over by a bulldozer, snapping the operating arm of the cesium source. The source was in the shielded position when the event occurred and a radiation survey of the gauge after the event verified it was still fully shielded. The licensee stated the gauge would be returned to its storage location and arrangements would be made to have the gauge disposed of. No individual received an exposure that exceeded any limit. Additional information will be provided as it is received in accordance with SA-300."
Texas Incident No.: 9885
* * * UPDATE FROM ART TUCKER TO THOMAS HERRITY AT 11:23 ON 09/20/21 * * *
The following information was received via e-mail:
"Received pictures of the gauge. Pictures show the rod for the cesium source was bent. The dose rate meter appears to be reading 0.8 millirem per hour."
Notified R4DO (YOUNG) and NMSS Events Notification group.
Power Reactor
Event Number: 55484
Facility: Limerick
Region: 1 State: PA
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: Kris Strausser
HQ OPS Officer: Howie Crouch
Region: 1 State: PA
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: Kris Strausser
HQ OPS Officer: Howie Crouch
Notification Date: 09/23/2021
Notification Time: 18:46 [ET]
Event Date: 09/23/2021
Event Time: 14:43 [EDT]
Last Update Date: 09/23/2021
Notification Time: 18:46 [ET]
Event Date: 09/23/2021
Event Time: 14:43 [EDT]
Last Update Date: 09/23/2021
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(3)(v)(D) - Accident Mitigation
10 CFR Section:
50.72(b)(3)(v)(D) - Accident Mitigation
Person (Organization):
LALLY, CHRISTOPHER (R1)
LALLY, CHRISTOPHER (R1)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
EN Revision Imported Date: 9/24/2021
EN Revision Text: HIGH PRESSURE COOLANT INJECTION SYSTEM DECLARED INOPERABLE
"During planned testing of the Unit 1 HPCI [high pressure coolant injection] system, flow controller oscillations occurred which prevented successful completion of the surveillance test. Operators secured Unit 1 HPCI and declared the system inoperable."
HPCI inoperable placed the licensee in a 14-day limiting condition for operation that was extended to 30 days after their risk-informed completion time evaluation was done.
The licensee has notified the NRC Resident Inspector.
EN Revision Text: HIGH PRESSURE COOLANT INJECTION SYSTEM DECLARED INOPERABLE
"During planned testing of the Unit 1 HPCI [high pressure coolant injection] system, flow controller oscillations occurred which prevented successful completion of the surveillance test. Operators secured Unit 1 HPCI and declared the system inoperable."
HPCI inoperable placed the licensee in a 14-day limiting condition for operation that was extended to 30 days after their risk-informed completion time evaluation was done.
The licensee has notified the NRC Resident Inspector.