Event Notification Report for September 09, 2021
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
09/08/2021 - 09/09/2021
Power Reactor
Event Number: 55451
Facility: Grand Gulf
Region: 4 State: MS
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: Gabe Hargrove
HQ OPS Officer: Kerby Scales
Region: 4 State: MS
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: Gabe Hargrove
HQ OPS Officer: Kerby Scales
Notification Date: 09/09/2021
Notification Time: 04:19 [ET]
Event Date: 09/09/2021
Event Time: 00:33 [CDT]
Last Update Date: 09/09/2021
Notification Time: 04:19 [ET]
Event Date: 09/09/2021
Event Time: 00:33 [CDT]
Last Update Date: 09/09/2021
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(3)(v)(D) - Accident Mitigation
10 CFR Section:
50.72(b)(3)(v)(D) - Accident Mitigation
Person (Organization):
TAYLOR, NICK (R4)
TAYLOR, NICK (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 70 | Power Operation | 80 | Power Operation |
EN Revision Imported Date: 10/8/2021
EN Revision Text: HIGH PRESSURE CORE SPRAY INOPERABLE
At 0033 CDT on September 9, 2021, Grand Gulf Nuclear Station (GGNS) was operating at 70 percent power when the High Pressure Core Spray (HPCS) was declared inoperable. The inoperability determination was made due to control room annunciations. In accordance with GGNS Technical Specification 3.5.1.B.1, the Reactor Core Isolation Cooling system was verified to be operable. Troubleshooting is in progress.
This event is being reported in accordance with 10 CFR 50.72(b)(3)(v)(D) as an event or condition which could have prevented the fulfillment of a safety function.
The NRC Resident Inspector has been notified.
EN Revision Text: HIGH PRESSURE CORE SPRAY INOPERABLE
At 0033 CDT on September 9, 2021, Grand Gulf Nuclear Station (GGNS) was operating at 70 percent power when the High Pressure Core Spray (HPCS) was declared inoperable. The inoperability determination was made due to control room annunciations. In accordance with GGNS Technical Specification 3.5.1.B.1, the Reactor Core Isolation Cooling system was verified to be operable. Troubleshooting is in progress.
This event is being reported in accordance with 10 CFR 50.72(b)(3)(v)(D) as an event or condition which could have prevented the fulfillment of a safety function.
The NRC Resident Inspector has been notified.
Part 21
Event Number: 55453
Rep Org: AMETEK SOLIDSTATE CONTROLS
Licensee: AMETEK SOLIDSTATE CONTROLS
Region: 3
City: Columbus State: OH
County:
License #:
Agreement: Y
Docket:
NRC Notified By: Ethan Salsbury
HQ OPS Officer: Donald Norwood
Licensee: AMETEK SOLIDSTATE CONTROLS
Region: 3
City: Columbus State: OH
County:
License #:
Agreement: Y
Docket:
NRC Notified By: Ethan Salsbury
HQ OPS Officer: Donald Norwood
Notification Date: 09/09/2021
Notification Time: 13:53 [ET]
Event Date: 09/09/2021
Event Time: 00:00 [EDT]
Last Update Date: 09/09/2021
Notification Time: 13:53 [ET]
Event Date: 09/09/2021
Event Time: 00:00 [EDT]
Last Update Date: 09/09/2021
Emergency Class: Non Emergency
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
Person (Organization):
DENTEL, GLENN (R1DO)
MILLER, MARK (R2DO)
RIEMER, KENNETH (R3DO)
TAYLOR, NICK (R4DO)
PART 21/50.55 REACTORS, - (EMAIL)
DENTEL, GLENN (R1DO)
MILLER, MARK (R2DO)
RIEMER, KENNETH (R3DO)
TAYLOR, NICK (R4DO)
PART 21/50.55 REACTORS, - (EMAIL)
EN Revision Imported Date: 10/8/2021
EN Revision Text: PART 21 REPORT - NONCONFORMING RELAY LED TO FAILURES OF BATTERY CHARGERS
The following is a synopsis of information received via E-mail:
Component Description:
AMETEK Part Number 07-740108-00, K306 relay, used in the float/equalize circuit of AMETEK Battery Chargers. The relay is a solid-state timer manufactured by Omron with manufacturer part number H3CR-A-AC100-240/DC100125.
Problem You Could See:
AMETEK was notified of a condition of a nonconforming K306 relay that led to failures of battery chargers. AEP DC Cook reported a single failure of a K306 Float/Equalize timer relay in a controlled environment where the relay failed to transfer from float to equalize and caused the DC output to fail. Transferring the battery charger to equalize mode is always a manual operation and the float/equalize function is typically used after an outage or a discharge test in order to bring the batteries back to full charge. Before performing a discharge test, the charger should be put in equalize mode. AMETEK was not able to evaluate this specific instance of failure, but it was determined the circuit does not meet the minimum contact current rating. As a result, the operation of the relay may be unreliable and the charger may experience a loss of output when equalize is initiated, failing to charge the batteries. The failed relay was installed in 2017 and was original to the equipment.
Effect on System Performance:
If the charger fails to transfer between float and equalize, the equalize light may turn on, the charger output will fail, voltage will drop below float voltage or to 0, and there will be no charging capabilities. An alarm will indicate Low DC voltage in the event the charger does not transfer between float and equalize. The charger will restart after the AC input breaker is cycled Off and On. The relay should be replaced if the charger output is lost. Other alarm(s) may be included with the design:
- Battery Discharge Alarm
- Low Current Alarm
The battery will charge with float voltage, but will take longer than with equalize voltage (~8-24 hours after charging current stabilizes).
The safety impact is a loss of battery charger output after an event where the float/equalize button is utilized and does not retransfer to equalize for charging. If the charger fails to transfer and the output is lost prior to a safety event, the battery may not be at full capacity for a shutdown. Each utility will need to evaluate the application of the battery charger and the battery it is charging.
Affected Entities:
Alabama Power Company; Arkansas Nuclear One; Atomic Energy of Canada; Constellation Energy; Consumer's Power, Palisades; Dominion - Kewaunee; Dominion Energy; Dominion Inc.; Duke Energy; Duke Power Co.; EM Test (Switzerland) GMBH; Engine Systems; Ergytech Inc.; Exelon; Exelon Generation Co.; First Energy; Formosa Nextech Co.; Framatome Technologies; Georgia Power; Indiana Michigan Power Co.; Millstone Nuclear Power Station; Niagara Mohawk; NPP Krsko; Progress Energy; TVA; TVA Watts Bar; Ulysses - Taiwan Power; and Ulysses System Development.
Ametek Contact: Ametek Solidstate Controls Client Services group, 1-800-222-9079 or 614-846-7500, extension 1.
EN Revision Text: PART 21 REPORT - NONCONFORMING RELAY LED TO FAILURES OF BATTERY CHARGERS
The following is a synopsis of information received via E-mail:
Component Description:
AMETEK Part Number 07-740108-00, K306 relay, used in the float/equalize circuit of AMETEK Battery Chargers. The relay is a solid-state timer manufactured by Omron with manufacturer part number H3CR-A-AC100-240/DC100125.
Problem You Could See:
AMETEK was notified of a condition of a nonconforming K306 relay that led to failures of battery chargers. AEP DC Cook reported a single failure of a K306 Float/Equalize timer relay in a controlled environment where the relay failed to transfer from float to equalize and caused the DC output to fail. Transferring the battery charger to equalize mode is always a manual operation and the float/equalize function is typically used after an outage or a discharge test in order to bring the batteries back to full charge. Before performing a discharge test, the charger should be put in equalize mode. AMETEK was not able to evaluate this specific instance of failure, but it was determined the circuit does not meet the minimum contact current rating. As a result, the operation of the relay may be unreliable and the charger may experience a loss of output when equalize is initiated, failing to charge the batteries. The failed relay was installed in 2017 and was original to the equipment.
Effect on System Performance:
If the charger fails to transfer between float and equalize, the equalize light may turn on, the charger output will fail, voltage will drop below float voltage or to 0, and there will be no charging capabilities. An alarm will indicate Low DC voltage in the event the charger does not transfer between float and equalize. The charger will restart after the AC input breaker is cycled Off and On. The relay should be replaced if the charger output is lost. Other alarm(s) may be included with the design:
- Battery Discharge Alarm
- Low Current Alarm
The battery will charge with float voltage, but will take longer than with equalize voltage (~8-24 hours after charging current stabilizes).
The safety impact is a loss of battery charger output after an event where the float/equalize button is utilized and does not retransfer to equalize for charging. If the charger fails to transfer and the output is lost prior to a safety event, the battery may not be at full capacity for a shutdown. Each utility will need to evaluate the application of the battery charger and the battery it is charging.
Affected Entities:
Alabama Power Company; Arkansas Nuclear One; Atomic Energy of Canada; Constellation Energy; Consumer's Power, Palisades; Dominion - Kewaunee; Dominion Energy; Dominion Inc.; Duke Energy; Duke Power Co.; EM Test (Switzerland) GMBH; Engine Systems; Ergytech Inc.; Exelon; Exelon Generation Co.; First Energy; Formosa Nextech Co.; Framatome Technologies; Georgia Power; Indiana Michigan Power Co.; Millstone Nuclear Power Station; Niagara Mohawk; NPP Krsko; Progress Energy; TVA; TVA Watts Bar; Ulysses - Taiwan Power; and Ulysses System Development.
Ametek Contact: Ametek Solidstate Controls Client Services group, 1-800-222-9079 or 614-846-7500, extension 1.
Agreement State
Event Number: 55482
Rep Org: UTAH DIVISION OF RADIATION CONTROL
Licensee: University of Utah
Region: 4
City: Salt Lake City State: UT
County:
License #: UT 1800001
Agreement: Y
Docket:
NRC Notified By: Tim Butler
HQ OPS Officer: Mike Stafford
Licensee: University of Utah
Region: 4
City: Salt Lake City State: UT
County:
License #: UT 1800001
Agreement: Y
Docket:
NRC Notified By: Tim Butler
HQ OPS Officer: Mike Stafford
Notification Date: 09/21/2021
Notification Time: 10:35 [ET]
Event Date: 09/09/2021
Event Time: 12:00 [MDT]
Last Update Date: 09/21/2021
Notification Time: 10:35 [ET]
Event Date: 09/09/2021
Event Time: 12:00 [MDT]
Last Update Date: 09/21/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
YOUNG, CALE (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
YOUNG, CALE (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
EN Revision Imported Date: 10/21/2021
EN Revision Text: AGREEMENT STATE REPORT - LOSS OF CONTROL OF RADIOACTIVE MATERIAL
The following report was received from the Utah Department of Environmental Quality, Division of Waste Management and Radiation Control (the Division) via email:
"On August 27, 2021, local heavy rain infiltrated the Merrill Engineering Building, causing flooding on the first and third floors. The first floor also included some radioactive materials labs. While stripping the labs on September 9, 2021, in preparation for repair, the contractor violated policy and failed to notify the lab owners before moving material from the lab. Included in the material removed from the lab was a safe containing 13 exempt calibration sources and one 0.006 milliCurie U-235 ceramic source. The safe was moved to an onsite trailer that was under control of the contractor and not the University. When the lab owner returned to the lab later in the day they immediately reported the sources missing. Investigation by licensee personnel lead them to where the sources were being stored. The sources were out of the licensee's exclusive control for 1 to 3 hours. The sources were re-secured and placed under the licensee's exclusive control closing the incident. The report was not determined to be reportable until the Division was able to conduct its on site investigation on September 20, 2021."
Utah Event Report ID Number: UT 210005
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - LOSS OF CONTROL OF RADIOACTIVE MATERIAL
The following report was received from the Utah Department of Environmental Quality, Division of Waste Management and Radiation Control (the Division) via email:
"On August 27, 2021, local heavy rain infiltrated the Merrill Engineering Building, causing flooding on the first and third floors. The first floor also included some radioactive materials labs. While stripping the labs on September 9, 2021, in preparation for repair, the contractor violated policy and failed to notify the lab owners before moving material from the lab. Included in the material removed from the lab was a safe containing 13 exempt calibration sources and one 0.006 milliCurie U-235 ceramic source. The safe was moved to an onsite trailer that was under control of the contractor and not the University. When the lab owner returned to the lab later in the day they immediately reported the sources missing. Investigation by licensee personnel lead them to where the sources were being stored. The sources were out of the licensee's exclusive control for 1 to 3 hours. The sources were re-secured and placed under the licensee's exclusive control closing the incident. The report was not determined to be reportable until the Division was able to conduct its on site investigation on September 20, 2021."
Utah Event Report ID Number: UT 210005
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf