Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for March 08, 2021

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/07/2021 - 03/08/2021

EVENT NUMBERS
55116551225512655119
Agreement State
Event Number: 55116
Rep Org: TEXAS DEPT OF STATE HEALTH SERVICES
Licensee: Lanxess Corporation
Region: 4
City: Baytown   State: TX
County:
License #: L 05810
Agreement: Y
Docket:
NRC Notified By: Chris Moore
HQ OPS Officer: Bethany Cecere
Notification Date: 03/01/2021
Notification Time: 11:18 [ET]
Event Date: 03/01/2021
Event Time: 00:00 [CST]
Last Update Date: 03/01/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
GROOM, JEREMY (R4)
NMSS_EVENTS_NOTIFICATION, (EMAIL)
Event Text
AGREEMENT STATE REPORT - STUCK GAUGE SHUTTER

The following was received by email from the Texas Department of State Health Services:

"On March 1, 2021, the [Texas Department of State Health Services] was contacted by a licensee stating that during routine testing, the shutter on a nuclear gauge was found stuck in the open position. The gauge is an Ohmart Vega model SH-F2-30, containing a 100 milliCurie (original activity) cesium-137 source. Source serial number is 1965CG and the manufacturer is Ohmart. The licensee reported there is no risk of radiation exposure to members of the general public or workers at the facility due to the failure. The licensee stated they were working on a plan to repair the gauge and would provide that information once the plan is completed. Additional information will be provided as it is received in accordance with SA-300."

TX Incident #: 9829


Power Reactor
Event Number: 55122
Facility: Calvert Cliffs
Region: 1     State: MD
Unit: [2] [] []
RX Type: [1] CE,[2] CE
NRC Notified By: Kent Mills
HQ OPS Officer: Kerby Scales
Notification Date: 03/04/2021
Notification Time: 04:00 [ET]
Event Date: 03/04/2021
Event Time: 03:23 [EST]
Last Update Date: 03/04/2021
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(3)(ii)(A) - Degraded Condition
Person (Organization):
BURKET, ELISE (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N N 0 Refueling 0 Refueling
Event Text
NOTIFICATION OF DEGRADED CONDITION

"At time 0323 [EST] on March 04, 2021, it was determined that the Reactor Coolant System (RCS) pressure boundary did not meet the acceptance criteria under ASME, Section XI IWB-3600, "Analytical Evaluation of Flaws." This condition will be resolved prior to plant start up. This event is being reported as an eight hour non-emergency notification per 10 CFR 50.72(b)(3)(ii)(A).

"There was no impact on the health and safety of the public or plant personnel. The NRC Resident has been notified."


Part 21
Event Number: 55126
Rep Org: Crane Nuclear, Inc.
Licensee: Crane Nuclear, Inc.
Region: 3
City: Bolingbrook   State: IL
County:
License #:
Agreement: N
Docket:
NRC Notified By: Joyce Hammam
HQ OPS Officer: Joanna Bridge
Notification Date: 03/05/2021
Notification Time: 16:20 [ET]
Event Date: 01/06/2021
Event Time: 00:00 [CST]
Last Update Date: 03/05/2021
Emergency Class: Non Emergency
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
Person (Organization):
BURKET, ELISE (R1DO)
MILLER, MARK (R2DO)
HILLS, DAVID (R3DO)
GROOM, JEREMY (R4DO)
PART 21/50.55 REACTORS, - (EMAIL)
Event Text
INTERIM PART 21 REPORT - WELD PROCEDURES DO NOT MEET ASME CODE

The following is a summary of the report provided by the supplier:

On January 6, 2021, Crane Nuclear, Inc (CNI) received an e-mail message from a customer identifying that the weld procedures Crane summitted for use on the customer's purchase order were unacceptable, as the procedure did not meet the requirements of ASME Code Section IX. CNI immediately began research and determined the customer to be correct.

CNI is currently conducting research to determine where the affected weld procedures were used. The scope of supply is Code and safety related valve and valve parts supplied by CNI since 2009.

Joyce Hammam
Director, Safety and Quality
(678) 451-2280
Crane Nuclear, Inc.
860 Remington Blvd
Bolingbrook, IL 60440


Agreement State
Event Number: 55119
Rep Org: MA RADIATION CONTROL PROGRAM
Licensee: QSA Global, Inc.
Region: 1
City: Burlington   State: MA
County:
License #: 12-8361
Agreement: Y
Docket:
NRC Notified By: Robert Locke
HQ OPS Officer: Donald Norwood
Notification Date: 03/01/2021
Notification Time: 16:31 [ET]
Event Date: 03/01/2021
Event Time: 14:00 [EST]
Last Update Date: 03/05/2021
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
ELISE BURKET (R1DO)
SILAS KENNEDY (IR)
REBECCA RICHARDSON (ILTAB)
THERESA CLARK (NMSS)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Event Text
EN Revision Imported Date: 3/8/2021

EN Revision Text: AGREEMENT STATE REPORT - CATEGORY 2 PACKAGE CONTAINING SEVEN SEALED SOURCES LOST IN TRANSIT

"The licensee reported to the Agency [Massachusetts Radiation Control Program] at 1400 EST on March 1, 2021, that it discovered on March 1, 2021 at 1200 EST that a package (Yellow-III, T.I. 2.6, Type B, UN 2916) containing seven sealed sources (Ir-192; 59.9 Ci, 59.2 Ci, 58.1 Ci, 59.9 Ci, 59.5 Ci, 59.8 Ci, and 69.2 Ci) in a model 976C source changer was missing.

"The package was shipped by QSA Global, Inc. on February 12, 2021, for export to their customer NDT Instruments, based in Singapore. On March 1, 2021 at 1200 EST, QSA Global, Inc. discovered that the package had not been received.

"The carrier indicated that the package had been at their Memphis, TN facility on 2/13/2021, and that since then the location is unknown.

"The reporting requirement is immediate and is of 105 CMR 120.281(A)(1), missing licensed radioactive materials in aggregate quantity equal to or greater than 1,000 times the quantity specified in 105 CMR 120.297, Appendix C. The four-hour reporting requirement of 105 CMR 120.077(B), missing shipment of Category 2 quantity of radioactive material, also applies."

The Agency considers this event to be open.

Notified: DHS-SWO, FEMA-OC, USDA-OC, HHS-OC, DOE-OC, DHS CISA Central, and EPA-EOC, Notified via E-mail: FDA- EOC, Nuclear SSA, FEMA-NWC, and CWMD-Watch Desk.

* * * UPDATE ON 3/5/2021 AT 1534 EST FROM ROBERT LOCKE TO JOANNA BRIDGE * * *

The following was received via e-mail from the Radiation Control Officer, Massachusetts Radiation Control Program:

"Licensee reports that they were notified on [5 March, 2021] that the missing package had been located in Memphis. The package was found undamaged and will continue for export to Singapore."

Notified R1DO (BURKET), NMSS (RIVERA-CAPELLA), IR MOC (GOTT), and ILTAB (RICHARDSON) and via email NMSS EVENTS NOTIFICATION, and INES NATIONAL OFFICER (MILLIGAN). Also notified DHS-SWO, FEMA-OC, USDA-OC, HHS-OC, DOE-OC, DHS CISA Central, and EPA-EOC and via email FDA- EOC, Nuclear SSA, FEMA-NWC, and CWMD-Watch Desk.

THIS MATERIAL EVENT CONTAINS A "CATEGORY 2" LEVEL OF RADIOACTIVE MATERIAL

Category 2 sources, if not safely managed or securely protected, could cause permanent injury to a person who handled them, or were otherwise in contact with them, for a short time (minutes to hours). It could possibly be fatal to be close to this amount of unshielded radioactive material for a period of hours to days. These sources are typically used in practices such as industrial gamma radiography, high dose rate brachytherapy and medium dose rate brachytherapy. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf