Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for December 11, 2007

U.S. Nuclear Regulatory Commission
Operations Center

Event Reports For
12/10/2007 - 12/11/2007

** EVENT NUMBERS **


43832

To top of page
Power Reactor Event Number: 43832
Facility: PALISADES
Region: 3 State: MI
Unit: [1] [ ] [ ]
RX Type: [1] CE
NRC Notified By: TODD MULFORD
HQ OPS Officer: JASON KOZAL
Notification Date: 12/10/2007
Notification Time: 22:21 [ET]
Event Date: 12/10/2007
Event Time: 18:30 [EST]
Last Update Date: 12/10/2007
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
JOHN MADERA (R3)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation

Event Text

NOTIFICATION TO OFFSITE AGENCIES DUE TO ELEVATED TRITIUM LEVELS

"Five new ground water monitoring wells were recently installed at Palisades Nuclear Plant in support of the Nuclear Energy institute (NEI) ground water initiative. The initial sampling of one of these wells displayed a level of tritium that triggered the communication protocol of the NEI initiative on ground water protection. On December 10, 2007, at 1830 hours, Entergy confirmed that the tritium concentration for this well was 22,000 picoCuries per liter (pCi/l). The threshold for initiating the communication protocol is 20,000 pCi/l (Offsite Dose Calculation Manual limit for drinking water). This well is located inside the owner controlled area and inside the protected area. This well is not a drinking water source. Entergy is continuing to investigate the source of tritium identified in this well. Samples from the remaining four wells are below minimum detectable activity levels. There is no indication that tritium has migrated off the Palisades site. The licensee plans to notify the State of Michigan, Van Buren County Office of Domestic Preparedness, City of South Haven, Covert Township, and the South Haven Charter Township.

"The licensee has notified the NRC Resident Inspector."