Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for June 1, 2006

U.S. Nuclear Regulatory Commission
Operations Center

Event Reports For
05/31/2006 - 06/01/2006

** EVENT NUMBERS **


42611

To top of page
Power Reactor Event Number: 42611
Facility: POINT BEACH
Region: 3 State: WI
Unit: [1] [2] [ ]
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: DEAN RAASCH
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 05/31/2006
Notification Time: 14:15 [ET]
Event Date: 05/30/2006
Event Time: 09:23 [CDT]
Last Update Date: 05/31/2006
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
LAURA KOZAK (R3)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation

Event Text

CONTROL ROOM EMERGENCY FILTRATION SYSTEM INOPERABLE

"Control Room Emergency Filtration System (CREFS) was declared Inoperable at 0923 on 5/30/2006 per TS 5.5.10.c 'Ventilation Filter Testing Program'. Laboratory testing results of a sample of the charcoal adsorber taken on 5/2/2006 did not meet the methyl iodide penetration percentage acceptance criteria of less than or equal to 1.0%. This condition is covered by TS 3.7.9 and both Unit 1 and Unit 2 entered Condition A, 'CREFS Inoperable' with a Required Action of 'Restore CREFS to OPERABLE status' with a Completion Time of 7 Days.

"CREFS is a single train system. Based on the guidance in NUREG-1022 for single train systems that perform safety functions, this condition was determined to be reportable under 10 CFR 50.72(b)(3)(v), 'Event or Condition That Could Have Prevented Fulfillment of a Safety Function'. Technical Specifications allow this system to be inoperable for a period of seven days.

"This condition was not reported within the 8 Hour Non-Emergency reporting requirements."

The charcoal has been replaced and the licensee estimates testing at approximately 17:00.

The licensee notified the NRC Resident Inspector.