Event Notification Report for January 24, 2005

U.S. Nuclear Regulatory Commission
Operations Center

Event Reports For
01/21/2005 - 01/24/2005

** EVENT NUMBERS **


41343 41348 41350

To top of page
General Information or Other Event Number: 41343
Rep Org: NC DIV OF RADIATION PROTECTION
Licensee: BUILDING & EARTH SCIENCES, INC.
Region: 1
City: COLUMBUS State: GA
County:
License #:
Agreement: Y
Docket:
NRC Notified By: LEE COX
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 01/18/2005
Notification Time: 16:50 [ET]
Event Date: 01/17/2005
Event Time: 07:25 [EST]
Last Update Date: 01/18/2005
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
Person (Organization):
HAROLD GRAY (R1)
E. WILLIAM BRACH (NMSS)

Event Text

NORTH CAROLINA AGREEMENT STATE REPORT - DAMAGED TROXLER

The following information was reported by facsimile.

The North Carolina Department of Environment and Natural Resources reported a damaged Troxler moisture density gage during construction activities in Reidsville, NC. The NC Radiation Protection Section dispatched a health physicist to the site, the health physicist secured the damaged gage on site and conducted radiation exposure surveys to access the status of the radioactive sources. All indications and surveys support that no radiological damage occurred to those workers involved and no damage was incurred to the environment.

Damage to the gage resulted in a potential loss of shielding. If the gage is mishandled the source rod will pull out. The gage was secured and the sliding block was closed.

Stakeholders and responsible parties were contacted and are arranging to have the gage appropriately transferred to the manufacturer for further evaluation.

Troxler Model # 3430, S/N 34504

Radiological Information:
Cs-137 10 milliCi S/N 77-1449
Am/Be 40 milliCi S/N 47-29961

Survey Results:
Background: 20 microR/hr
three inches from gage: 8 milliR/hr
After gage removed: 20 microR/hr (no indication of contamination)

NC Incident Report: 05-01 The license number was not provided.

To top of page
Power Reactor Event Number: 41348
Facility: BROWNS FERRY
Region: 2 State: AL
Unit: [ ] [2] [ ]
RX Type: [1] GE-4,[2] GE-4,[3] GE-4
NRC Notified By: WILLIAM BAKER
HQ OPS Officer: STEVE SANDIN
Notification Date: 01/21/2005
Notification Time: 08:19 [ET]
Event Date: 01/20/2005
Event Time: 23:53 [CST]
Last Update Date: 01/21/2005
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
CHARLES R. OGLE (R2)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation

Event Text

HIGH PRESSURE COOLANT INJECTION (HPCI) DECLARED INOPERABLE BASED ON INABILITY TO VERIFY HPCI KEEP FILL FUNCTION REQUIRED BY TECHNICAL SPECIFICATIONS

"At 23:53 CST Unit 2 HPCI pump suction automatically transferred from the Condensate Storage Tank to the Suppression Pool. This caused HPCI to be declared inoperable due to not meeting Technical Specification Surveillance Requirement 3.5.1.1. HPCI keep fill could not be verified so HPCI was declared inoperable.

"This event is being reported pursuant to 10CFR 50.72(b)(3)(v) as 'Any event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to: (D) Mitigate the consequences of an accident.'"

HPCI remains inoperable pending venting of the system. The licensee is conducting an investigation to determine the root cause for the automatic transfer.

The licensee informed the NRC Resident Inspector.

To top of page
Power Reactor Event Number: 41350
Facility: CALVERT CLIFFS
Region: 1 State: MD
Unit: [1] [2] [ ]
RX Type: [1] CE,[2] CE
NRC Notified By: DAVID SMITH
HQ OPS Officer: MIKE RIPLEY
Notification Date: 01/23/2005
Notification Time: 13:51 [ET]
Event Date: 01/23/2005
Event Time: 12:00 [EST]
Last Update Date: 01/23/2005
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
HAROLD GRAY (R1)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation

Event Text

LOSS OF EMERGENCY NOTIFICATION SIREN CAPABILITY DUE TO LOSS OF POWER

A significant portion of the emergency notification sirens (19 of 50) located in Calvert County, MD are out of service due to a Southern Maryland Electric Cooperative (SMECO) power outage. The licensee stated that power is expected to be restored by 1700 ET 01/23/05.

The licensee will inform the NRC Resident Inspector.

* * * UPDATE FROM PACE TO CROUCH @ 2022 HRS EST ON 1/23/05 * * *

The out of service sirens have been tested and returned to service as of 2000 hrs. EST. The licensee has notified the NRC Resident Inspector.

Notified R1DO (Gray).