Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for June 25, 1999

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           06/24/1999 - 06/25/1999

                              ** EVENT NUMBERS **

35855  35856  35857  35858  35859  

+------------------------------------------------------------------------------+
|Fuel Cycle Facility                              |Event Number:   35855       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PADUCAH GASEOUS DIFFUSION PLANT      |NOTIFICATION DATE: 06/24/1999|
|   RXTYPE: URANIUM ENRICHMENT FACILITY          |NOTIFICATION TIME: 05:18[EDT]|
| COMMENTS: 2 DEMOCRACY CENTER                   |EVENT DATE:        06/23/1999|
|           6903 ROCKLEDGE DRIVE                 |EVENT TIME:        20:50[CDT]|
|           BETHESDA, MD 20817    (301)564-3200  |LAST UPDATE DATE:  06/24/1999|
|    CITY:  PADUCAH                  REGION:  3  +-----------------------------+
|  COUNTY:  McCRACKEN                 STATE:  KY |PERSON          ORGANIZATION |
|LICENSE#:  GDP-1                 AGREEMENT:  Y  |MIKE JORDAN          R3      |
|  DOCKET:  0707001                              |ROBERT PIERSON       NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  MATT MAURER                  |                             |
|  HQ OPS OFFICER:  FANGIE JONES                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NLTR                     LICENSEE 24 HR REPORT  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| 24 HOUR REPORT - SAFETY SYSTEM ACTUATION                                     |
|                                                                              |
| "At 2050 CDT on 6/23/99, C-333A Autoclave Position 1 North received a High   |
| Autoclave Steam Pressure Alarm while in Technical Specification Requirement  |
| mode 5.  The Autoclave Steam Pressure Control System is required to be       |
| operable while in mode 5 per LCO 2.2,3.3.  An Increase in autoclave steam    |
| pressure was observed by the Autoclave Steam Pressure Control System and the |
| system isolated the steam from the autoclave as designed.  The autoclave was |
| placed in mode 2 and the cause of the safety system actuation is being       |
| investigated."                                                               |
|                                                                              |
| The NRC Resident Inspector has been notified of this event.                  |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Hospital                                         |Event Number:   35856       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  U.S. VETERANS ADMINISTRATION         |NOTIFICATION DATE: 06/24/1999|
|LICENSEE:  DURHAM VA HOSPITAL                   |NOTIFICATION TIME: 15:00[EDT]|
|    CITY:  DURHAM                   REGION:  2  |EVENT DATE:        05/28/1999|
|  COUNTY:                            STATE:  NC |EVENT TIME:        12:00[EDT]|
|LICENSE#:  32-01134-01           AGREEMENT:  Y  |LAST UPDATE DATE:  06/24/1999|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |AL BELISLE           R2      |
|                                                |FRED COMBS           NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  LYNNE McGUIRE                |                             |
|  HQ OPS OFFICER:  BOB STRANSKY                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|BAB1 20.2201(a)(1)(i)    LOST/STOLEN LNM>1000X  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| LOSS OF IODINE-125 SEEDS INTO SANITARY SEWER                                 |
|                                                                              |
| "On May 28, 1999, two I-125 sources, with a combined activity of 0.584 mCi,  |
| were lost from the Medical Center.  The seeds had been implanted into a      |
| patient's prostate earlier in the day.  The patient had been instructed to   |
| save his urine so that any seeds passed in the urine could be recovered.  An |
| instruction sheet was posted on the door, directing that all urine, trash    |
| and linen be saved, and nurses had been trained for the procedure.  A nurse  |
| called nuclear medicine to report that two seeds were in the urine           |
| container.  When nuclear medicine personnel arrived to recover the seeds,    |
| the urine had been flushed into the sanitary sewer by another staff member   |
| on the floor.                                                                |
|                                                                              |
| "The toilet and urine container were surveyed with a portable low-energy     |
| gamma detector, and no residual activity was detected.  The sources are      |
| presumed to have gone into the sewer, and assuming the seeds remain covered  |
| by water, no significant exposure is expected to any individual member of    |
| the public.  On June 1, 1999, the loss of the sources was reported by phone  |
| to the VA National Health Physics Program.                                   |
|                                                                              |
| "In order to prevent recurrence of this type of incident, the nurses on ward |
| 7A have been retrained in the proper procedures.  In the future, implant     |
| patient rooms will be posted with larger signs saying 'hold urine, trash,    |
| linen'."                                                                     |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35857       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: NINE MILE POINT          REGION:  1  |NOTIFICATION DATE: 06/24/1999|
|    UNIT:  [] [2] []                 STATE:  NY |NOTIFICATION TIME: 17:05[EDT]|
|   RXTYPE: [1] GE-2,[2] GE-5                    |EVENT DATE:        06/24/1999|
+------------------------------------------------+EVENT TIME:        15:41[EDT]|
| NRC NOTIFIED BY:  ROY GREEN                    |LAST UPDATE DATE:  06/24/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |GLENN MEYER          R1      |
|10 CFR SECTION:                                 |                             |
|ARPS 50.72(b)(2)(ii)     RPS ACTUATION          |                             |
|AESF 50.72(b)(2)(ii)     ESF ACTUATION          |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     A/R        Y       100      Power Operation  |0        Hot Shutdown     |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AUTOMATIC REACTOR SCRAM WITH PARTIAL LOSS OF OFFSITE POWER                   |
|                                                                              |
| An automatic reactor scram occurred due to low reactor vessel water level.   |
| The low level condition was caused by the failure of a feedwater level       |
| controller.  All control rods inserted following the scram.  Offsite power   |
| line #5 failed to transfer following the scram, causing the following ESF    |
| actuations to occur:  reactor building ventilation isolation, standby gas    |
| treatment system initiation, Division 1 and 3 emergency diesel generator     |
| (EDG) initiation, and control room special filter train initiation.  In      |
| addition, operators manually closed the main steam isolation valves (MSIVs)  |
| in response to decreasing condenser vacuum caused by a loss of power to the  |
| offgas system.  The unit is currently in Hot Shutdown, with reactor vessel   |
| water level being controlled by the reactor core isolation cooling (RCIC)    |
| system, and decay heat being removed via the safety/relief valves (SRVs).    |
| The licensee plans to take the unit to Cold Shutdown.                        |
|                                                                              |
| The licensee is currently troubleshooting the offsite power line #5 in order |
| to restore power to affected systems.                                        |
| The NRC resident inspector has been informed of this event.                  |
|                                                                              |
| * * * Update at 2244 on 06/24/99 from Trombley taken by Stransky * * *       |
|                                                                              |
| Scram recovery activities are continuing.  Offsite power line #5 has been    |
| restored, and the Division 1 EDG has been secured.  The licensee is          |
| currently in the process of securing the Division 3 EDG.  Operators          |
| experienced some problems with the RCIC flow controller and have taken       |
| manual control of the system [see related EN 35859].  The NRC Operations     |
| Officer notified R1DO (Glenn Meyer).                                         |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Hospital                                         |Event Number:   35858       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  ALASKA REGIONAL HOSPITAL             |NOTIFICATION DATE: 06/24/1999|
|LICENSEE:  ALASKA REGIONAL HOSPITAL             |NOTIFICATION TIME: 19:27[EDT]|
|    CITY:  ANCHORAGE                REGION:  4  |EVENT DATE:        06/24/1999|
|  COUNTY:                            STATE:  AK |EVENT TIME:        12:00[YDT]|
|LICENSE#:  50-18244-01           AGREEMENT:  N  |LAST UPDATE DATE:  06/24/1999|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |JOSEPH TAPIA         R4      |
|                                                |ROBERT PIERSON       NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  BRADLEY CRUZ                 |                             |
|  HQ OPS OFFICER:  BOB STRANSKY                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|LADM 35.33(a)            MED MISADMINISTRATION  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| MEDICAL MISADMINISTRATIONS CAUSED BY INCORRECT REPLACEMENT PART IN           |
| APPLICATOR                                                                   |
|                                                                              |
| The licensee reported that four medical misadministrations occurred due to   |
| the installation of an incorrect replacement part into an applicator that is |
| used in conjunction with a brachytherapy device.  The affected part is an    |
| insert for a "Duiclos mini ovoid" applicator (manufacturer unknown),         |
| purchased from the Radiation Products Design catalog.  The supplied          |
| replacement part looks similar to the original one, but is slightly shorter  |
| (the parts are not imprinted with any identification number). Due to the     |
| differing dimensions, treatments given using the applicator result in the    |
| source being placed at a slightly different axial location than intended,    |
| resulting in less than prescribed doses to the treatment area.  The          |
| misadministrations are characterized as follows:  (1) patient prescribed     |
| 3000 rads (cGy), received 1874 rads; (2) patient prescribed 3000 rads,       |
| received 2035 rads; (3) patient prescribed 2500 rads, received 1822 rads;    |
| (4) patient prescribed 3000 rads, received 2004 rads.  This condition was    |
| discovered when an x-ray indicated that the source was slightly out of       |
| position.                                                                    |
|                                                                              |
| The licensee plans to contact the vendor in order to obtain the correct      |
| insert for the applicator.                                                   |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35859       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: NINE MILE POINT          REGION:  1  |NOTIFICATION DATE: 06/24/1999|
|    UNIT:  [] [2] []                 STATE:  NY |NOTIFICATION TIME: 22:44[EDT]|
|   RXTYPE: [1] GE-2,[2] GE-5                    |EVENT DATE:        06/24/1999|
+------------------------------------------------+EVENT TIME:        22:07[EDT]|
| NRC NOTIFIED BY:  WALT TROMBLEY                |LAST UPDATE DATE:  06/24/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |GLENN MEYER          R1      |
|10 CFR SECTION:                                 |                             |
|AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     N          N       0        Hot Shutdown     |0        Hot Shutdown     |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| RCIC SYSTEM DECLARED INOPERABLE                                              |
|                                                                              |
| The Unit 2 reactor core isolation cooling (RCIC) system was declared         |
| inoperable after operators noticed swings of 200-300 gpm in the system flow  |
| rate.  The system is currently being used to provide level control to the    |
| reactor vessel following a scram [see related EN 35857].  The system flow    |
| rate stabilized after operators placed the RCIC flow controller in manual,   |
| so the licensee considers the system to be inoperable but functional.  The   |
| licensee is continuing to cool down Unit 2.  The licensee plans to inform    |
| the NRC resident inspector of this report.                                   |
+------------------------------------------------------------------------------+