Information Notice No. 91-29, Supplement 3: Deficiencies Identified During Electrical Distribution System Functional Inspections
UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF NUCLEAR REACTOR REGULATION WASHINGTON, D.C. 20555-0001 November 22, 1995 NRC INFORMATION NOTICE 91-29, SUPPLEMENT 3: DEFICIENCIES IDENTIFIED DURING ELECTRICAL DISTRIBUTION SYSTEM FUNCTIONAL INSPECTIONS Addressees All holders of operating licenses or construction permits for nuclear power reactors. Purpose The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice supplement to provide additional information on deficiencies the staff found during electrical distribution system functional inspections (EDSFIs) at nuclear plants. It is expected that recipients will review the information for applicability to their facilities and consider actions, as appropriate, to avoid similar problems. However, suggestions contained in this information notice are not NRC requirements; therefore, no specific action or written response is required. Background During various multi-discipline inspections, the NRC had identified numerous deficiencies related to the electrical distribution system. To address these deficiencies, the NRC developed the EDSFI to specifically evaluate the electrical distribution system. Attachment 1, "Related Information Notices," contains previously identified deficiencies from NRC inspections. Description of Circumstances The EDSFIs focused on the capacity of the electrical distribution system to perform its intended functions during all plant operating and accident conditions and the capability and performance of engineering organizations in providing engineering and technical support for the operation of the electrical distribution system. The NRC has completed inspections of all operating plants in accordance with Temporary Instruction (TI) 2515/107, "Electrical Distribution System Functional Inspection," and this IN supplement addresses deficiencies identified during the EDSFIs in addition to those discussed in the listed information notices. The inspections findings included the following: 1) availability and reliability of offsite power sources, 2) design review of inadequate fast bus transfer, 3) inadequate tests for emergency diesel generator systems, and 4) deficiencies in class 1E battery systems. These findings are discussed in 9511130071. IN 91-29, Supp. 3 November 22, 1995 Page 2 of 2 detail in Attachment 2, "Inspection Findings for Electrical Distribution System Functional Inspections." This information notice requires no specific action or written response. If you have any questions about the information in this notice, please contact the technical contact listed below or the appropriate Office of Nuclear Reactor Regulation (NRR) project manager. /s/'d by DMCrutchfield Dennis M. Crutchfield, Director Division of Reactor Program Management Office of Nuclear Reactor Regulation Technical contact: Roy K. Mathew (301) 415-2965 Attachments: 1. Related Information Notices 2. Inspection Findings for Electrical Distribution System Functional Inspections 3. List of Recently Issued NRC Information Notices . Attachment 1 IN 91-29, Supp. 3 November 22, 1995 Page 1 of 1 RELATED INFORMATION NOTICES (1) IN 91-29, "Deficiencies Identified During Electrical Distribution System Functional Inspections," dated April 15, 1991, addressed inadequate ac voltages at the 480-Vac and 120-Vac distribution levels, inadequate procedures to test circuit breakers, and inadequate determinations and evaluations of setpoints. (2) IN 91-51, "Inadequate Fuse Control Programs," dated August 20, 1991. (3) IN 92-40, "Inadequate Testing of Emergency Bus Undervoltage Logic Circuitry," dated May 27, 1992. (4) IN 92-53, "Potential Failure of Emergency Diesel Generators Due to Excessive Rate of Loading," dated July 29, 1992. (5) IN 91-29, Supplement 1, "Deficiencies Identified During Electrical Distribution System Functional Inspections," dated September 14, 1992, addressed the following: inadequate undervoltage relay setpoints for degraded voltage conditions, inadequate interrupting capacity of fault protection devices, improper coordination of fault protection devices, inadequate analysis of emergency diesel generator (EDG) capacity to power safety-related loads during postulated accidents, and deficiencies in EDG mechanical interface systems. (6) IN 92-77, "Questionable Selection and Review to Determine Suitability of Electropneumatic Relays For Certain Applications," dated November 17, 1992. (7) IN 91-29, Supplement 2, "Deficiencies Identified During Electrical Distribution System Functional Inspections," dated December 22, 1993, addressed the potential for the electrical bus transfer logic allowing repeated bus transfers between the two offsite sources supplying power to the safety-related buses. (8) IN 94-19, "Emergency Diesel Generator Vulnerability to Failure From Cold Fuel Oil," dated March 16, 1994. . Attachment 2 IN 91-29, Supp. 3 November 22, 1995 Page 1 of 4 INSPECTION FINDINGS FOR ELECTRICAL DISTRIBUTION SYSTEM FUNCTIONAL INSPECTIONS Discussion of Inspection Findings Availability and Reliability Issues Regarding Offsite Power Sources During the EDSFI at the Millstone 1 facility (Report No. 50-245/91-81, dated December 30, 1991), the inspection team noted that the licensee had conducted load flow and stability studies in 1979 and had conducted additional studies to support the startup of the Millstone 3 facility in 1982. The team asked the licensee to confirm the validity of those studies with respect to the current design and the expected system load in the next few years. Subsequent analysis by the licensee determined that the offsite power supply could become unstable after an occurrence of disturbances in the vicinity of Millstone station caused by over 5,000 MW of power that had been added to the New England Power Pool by cogeneration and independent power producers. The grid power flow conditions had changed as a result of the addition of these generating units not considered in the earlier studies. The licensee imposed restrictions on the power level of the Millstone units to prevent instability. To account for fluctuations in power flow conditions and to ensure stability, licensees generally perform periodic analyses for the following conditions in order to maintain current licensing bases: (1) the largest generating capacity being supplied to the grid is lost; (2) the largest load is lost from the grid; (3) the most critical transmission line is lost; or (4) the unit itself is lost. At the Arkansas Nuclear One (ANO) facility (Report No. 50-313/92-16, dated July 2, 1992), the EDSFI team observed that under certain loading conditions, sufficient voltage would not be available for one of the offsite electrical power supplies. The two required sources of offsite power are supplied to the ANO site through the 500-kV switchyard and the 161-kV switchyard. The 500-kV switchyard normally supplies power through an onsite autotransformer to the 161-kV switchyard. The licensee engineering evaluation showed that the voltage at the 161-kV switchyard would not be adequate under all operating conditions if the 500-kV system was not available. The degradation in the available voltage occurred because of increased offsite loading of the 161-kV transmission system. The degradation had not been detected because the 500-kV transmission system had maintained the 161-kV transmission system at acceptable voltage levels. After becoming aware of the deficient condition, the licensee implemented immediate procedural changes to ensure that two acceptable sources of offsite electrical power were available and that long-term modifications were made to the 161-kV transmission system before peak loading. The procedural changes and the modifications ensured that adequate voltage levels would be available under all operating conditions. . Attachment 2 IN 91-29, Supp. 3 November 22, 1995 Page 2 of 4 Design Review of Inadequate Fast Bus Transfer At the Palo Verde site (Report No. 50-528/90-42, dated December 27, 1990), the EDSFI team noted that non-Class 1E loads from the unit auxiliary transformer were transferred to the startup transformer by an automatic bus transfer scheme upon a reactor trip, a turbine trip, or a loss-of-coolant accident. The effects of these additional loads on the ratings of startup transformer windings and available voltages to engineered safety features components had not been considered. As a result, the availability of the offsite power source could have been affected. At the Millstone 1 facility (Report No. 50-245/91-81, dated December 30, 1991), the EDSFI team noted that the licensee was unable to verify that the fast bus transfer was analyzed or tested to demonstrate the operation of fast bus transfer logic. Further analysis and tests by the licensee to verify the operation of the fast bus transfer scheme showed that the scheme would not function as designed. Specifically, the completion time for sending the signal and tripping the unit generator output breakers was longer than assumed; hence, the breaker could have closed with an unacceptable phase angle between the unit and the offsite power source. In such a case, it would be possible to damage running safety-related motors. The licensee review also identified that if a three phase bolted fault in the main stepup transformer occurs, with the switchyard generator output breakers taking more time than assumed to trip, it could result in the loss of the 345- kV grid. Inadequate Tests for Emergency Diesel Generator Systems At Vermont Yankee (Report No. 50-271/92-81, dated September 30, 1992) and other facilities, the EDSFI teams determined that the check valves between the non-Class 1E air compressors and the diesel generator air start receivers were not tested for any backleakage. Under the inservice test program, these valves were not adequately tested to demonstrate that the disk traveled to the seat promptly on cessation or reversal of flow. Therefore, there was no assurance that an adequate supply of air would be available to start the diesel generators if the nonsafety-related compressor was lost or a failure occurred in the nonsafety-related portion of the air start system. At Nine Mile Point 1 (Report No. 50-220/91-80, dated January 10, 1992), Millstone 1 (Report No. 50-245/91-81, dated December 30, 1991), and other facilities, the EDSFI teams determined that the diesel generator tests were performed to the kilowatt load requirement of the generator rather than the kilovoltampere (kVA) and kilovars (kvar) requirements. Specifically, the steady-state tests were conducted at the near unity power factor rather than at the EDG rated power factor or the actual load power factor. This loading condition did not meet either the licensee calculated design-basis accident load or the rated load of the generator. As a consequence, the current producing/carrying components of the generators were not adequately tested to demonstrate that the diesel generators could carry all of the safety-related loads during a design-basis event.. Attachment 2 IN 91-29, Supp. 3 November 22, 1995 Page 3 of 4 IN 91-13, dated March 4, 1991, discussed inadequate testing of emergency diesel generators due to insufficient electrical loading as well as insufficient compensation for the expected electrical power factor. Deficiencies in Class 1E Battery Systems The EDSFI teams noted deficiencies in the Class 1E battery systems at various sites. The inspection reports containing various deficiencies are referenced below. (1) Several licensees were not using adequate design margins, temperature correction factors, or aging factors for sizing the batteries. Normal industry design practices are: (a) Addition of a design margin of 10 to 15 percent to the cell size, as determined by calculations, to provide sufficient capacity margin for unanticipated loads, maintenance uncertainties, and poor battery operating conditions. (b) Use of an appropriate temperature correction factor to compensate for the reduction in cell capacity when the anticipated minimum battery electrolyte temperature is below the standard value of 25 �C [77 �F]. The temperature correction factor ensures the available battery capacity during low temperature conditions. (c) Use of a 1.25 factor to compensate for degradation caused by aging to ensure that batteries have adequate capacity at the end of their service life. (2) The teams determined that the design-basis accident loads were not conservatively accounted for in the loading calculation. Failure to determine accurate load current values for the accident loads raises uncertainty concerning available battery margins. (3) The teams determined that voltage drop studies were insufficient for determining if adequate voltage would be available to the Class 1E inverters and to the connected loads. For voltage drop studies, the voltage drop for the most limiting components was not considered, nor were the battery discharge limits set to ensure that adequate voltage limits existed at the end devices. (4) The teams determined that the battery service test procedures did not incorporate appropriate acceptance criteria for the final battery voltage as required by the design calculations to ensure adequate voltage for the safety-related components. One team also found that the battery service tests did not account for all the design loads required by the design calculations to demonstrate the capability of the battery. . Attachment 2 IN 91-29, Supp. 3 November 22, 1995 Page 4 of 4 (5) The teams identified one or more of the following deficiencies in heating, ventilation, and air conditioning (HVAC) systems for the safety-related battery rooms. Failure of the plant battery room HVAC systems to maintain temperature at or above the design minimum temperature for a design-basis event could result in decreased capacity and capability of the battery to meet its intended safety-related function. (a) No design provisions had been made to ensure that the temperature of the safety-related battery room would remain above the minimum required design-basis temperature. (b) Nonsafety-related heaters were installed to maintain an adequate temperature in the safety-related battery rooms, and there were no alarms or indications to alert the operators regarding low temperature conditions. (c) There was no evidence of seismic qualification of room heaters for maintaining the design-basis temperature in the battery rooms. Inspection Report References for Class 1E Battery Systems Deficiencies 1. ANO facility (Report No. 50-313/92-16, dated July 2, 1992) 2. Calvert Cliffs 1 & 2 (50-317, 50-318/92-80, June 5, 1992) 3. Catawba 1 (50-413/92-01, March 18, 1992) 4. Crystal River 3 (50-302/93-18, September 10, 1993) 5. Dresden 2 (50-237/91-201, September 20, 1991) 6. Fermi 2 (50-314/91-017, October 9, 1991) 7. Haddam Neck (50-213/91-80, May 3, 1991) 8. Indian Point 3 (50-286/91-80, August 14, 1991) 9. La Salle 2 (50-374/91-019, November 10, 1991) 10. Limerick 1 & 2 (50-352, 50-353/92-81, December 4, 1992) 11. Oyster Creek (50-219/92-80, July 7, 1992) 12. Perry 1 (50-440/91-005, June 27, 1991) 13. Prairie Island 1 (50-282/93-007, June 11, 1993) 14. San Onofre 2 & 3 (50-361, 50-362/89-200, January 12, 1990) 15. Waterford 3 (50-382/90-023, April 10, 1991)
Page Last Reviewed/Updated Tuesday, March 09, 2021
Page Last Reviewed/Updated Tuesday, March 09, 2021