Bulletin 83-01: Failure of Reactor Trip Breakers (Westinghouse DB-50) to Open on Automatic Trip Signal
SSINS No.: 6820 OMB No.: 3150-00012 Expiration Date: 04/30/85 IEB 83-01 UNITED STATES NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION AND ENFORCEMENT WASHINGTON, D.C. 20555 February 25, 1983 IE BULLETIN NO. 83-01: FAILURE OF REACTOR TRIP BREAKERS (WESTINGHOUSE DB-50) TO OPEN ON AUTOMATIC TRIP SIGNAL Addressees: All pressurized water nuclear power reactor facilities holding an operating license (OL) for action and to other nuclear power reactor facilities for information. Purpose: The purpose of this bulletin is to inform CP holders and licensees about recent failures of W DB type circuit breakers to trip open on receipt of an automatic trip signal from the reactor protection system (RPS) and to require action of all operating pressurized water reactors to assure proper operation of those breakers in the future. Description of Circumstances: On February 25, 1983, during startup of the Salem Unit 1 plant, both DB-50 RPS breakers failed to open automatically upon receipt of a valid trip signal on low-low steam generator level. This failure to trip has been attributed to sticking of the undervoltage trip attachment. The reactor was tripped manually from the control room about 30 seconds after the automatic trip signal was generated. The manually initiated trip was accomplished by the shunt relays installed in each DB-50 breaker. Background: In some reactor protection system designs, the automatic protection signals are fed only to the undervoltage (UV) trip attachment of the reactor trip breakers; the manual signals are fed both to the UV trip and to a shunt trip coil of each breaker. In the recent past, on two separate occasions, one RPS breaker at the Salem facility failed to open automatically due to binding of the UV trip attachment. These events have been reported in LER's 82-072/03X-1 and 83-001/03L. In addition, on February 22, 1983, Salem Unit 1 tripped on low-low steam generator level; however, since the operator manually tripped the reactor at a time almost coincidental with the automatic trip signal, the actual trip mechanism (manual or automatic) cannot be ascertained. 8212060367 . IEB 83-01 February 25, 1983 Page 2 of 3 Similar failures involving the UV trip attachment to the RPS have been reported to the NRC. These failures only involved one of the two series breakers, therefore they did not result in a failure to automatically trip the reactor. Said failures have occurred at H. B. Robinson, Connecticut Yankee, Prairie Island and St. Lucie in addition to those at Salem. As a result of these events, the NRC issued IE Bulletin No. 71-02 and IE Circular No. 81-12, and Westinghouse issued Technical Bulletin No. NSD-78-74-1 dated January 11, 1974 and NSD Data Letter 74-2 dated February 14, 1974. Required Actions for All Holders of Operating Licenses for Pressurized Water Reactors: Licensees with W DB type breakers using undervoltage trip attachment in Reactor Protective System applications are requested to: 1. Perform surveillance test of undervoltage trip function independent of the shunt trip within 24 hours of receipt of this Bulletin unless equivalent testing has been performed within 5 days. Those plants for which on-line testability is not provided may complete this item before resuming operation or if currently operating, at the next plant shutdown. 2. Review the maintenance program for conformance to recommended W program (attachment) including frequency and lubricant applied to trip mechanism. Verify actual implementation of the W program. If maintenance including lubrication does not conform, initiate such maintenance within 5 days of receipt of this bulletin or provide an alternate maintenance program. Repeat the testing required in item 1 prior to declaring the breaker OPERABLE. 3. Notify all licensed operators of the failure-to-trip event which occurred at Salem. Review the appropriate emergency operating procedures for the event of failure-to-trip with each operator upon his arrival on-shift. 4. Provide written reply within 7 days of receipt of this bulletin, a. identifying results of testing performed in response to item 1, b. identifying conformance of maintenance program to W recommendation and describing results of maintenance performed directly as a result of this Bulletin in response to item 2, c. provide statement that provisions are in place to notify licensed operators of the Salem event and bring to their attention appropriate failure-to-trip emergency procedures upon their arrival on-shift. d. You are reminded of the requirements for prompt notification in accordance with 10 CFR 50.72 in the event of detecting an inoperable RPS breaker. . IEB 83-01 February 25, 1983 Page 3 of 3 PWR Licensees not using the subject undervoltage trip attachment and therefore not affected by this bulletin shall submit a negative declaration within 7 days of the receipt of this bulletin. The written report required shall be submitted to the appropriate Regional Administrator under oath or affirmation under provisions of Section 182a, Atomic Energy Act of 1954, as amended. The original copy of the cover letters and a copy of the reports shall be transmitted to the U. S. Nuclear Regulatory Commission, Document Control Desk, Washington, D.C. 20555 for reproduction and distribution. This request for information was approved by the Office of Management and Budget under a blanket clearance number 3150-00012 which expires April 30, 1985. Comments on burden and duplication may be directed to the Office of Management and Budget, Reports Management, Room 3208, New Executive Office Building, Washington, D.C. 20503. If you have any questions regarding this matter, please contact the Regional Administrator of the NRC Regional Office or the technical contact listed below. Richard C. DeYoung, Director Office of Inspection and Enforcement Technical Contact: I. Villalva, IE 301-492-9635 V. Thomas, IE 301-492-4755 J. T. Beard, NRR 301-492-7465 Attachment: 1. Transcription of Westinghouse NSD Ltr. 74-2 2. List of Recently Issued IE Bulletins . ATTACHMENT 1 IEB 83-01 February 25, 1983 Verbatim transcription of Westinghouse NSD letter 74-2. Original signed by W. H. Furfari and Sydney G. Caslake. . NSD DATA LETTER 74-2 FROM : Nuclear Service Division WIN : 236-4744 DATE : February 19, 1974 SUBJECT : Reactor Trip Breaker Maintenance NUCLEAR ENERGY SYSTEMS TO: Distribution Technical Bulletin NSD-TB-74-1 (issued 1/11/74) described a reactor trip breaker malfunction which occurred at H. B. Robinson station in December of 1973, and recommended certain additional periodic maintenance measures to improve the reliability of these breakers. The malfunction (failure to trip during a regularly scheduled periodic test) was attributed to excessive friction in the linkage of the Undervoltage Trip Attachment, which is the device that initiates the breaker drop-open action by elevating the trip bar. The problem was corrected by cleaning and lightly lubricating certain portions of the linkage. To preclude the possibility of reoccurrence of this malfunction, Westinghouse recommends that the reactor trip breakers be given regularly scheduled periodic inspection/maintenance as described in the Instruction. Manual and in line with the following guidelines. 1. Scope. These recommendations are intended to apply to Westinghouse DB-50 (or DB-25) breakers in Reactor Trip applications. Some future WNES plants will be supplied with Westinghouse Type DS (stored energy) breakers, which should be maintained in accordance with their instruction manual. 2. Related Operations. It is expected that these inspection and main- tenance measures would normally be carried out in conjunction with breaker periodic operational testing or during plant shutdowns. However, these recommendations in no way are intended to supersede breaker operational testing commitments and requirements. 3. Frequency. Intervals between maintenance will be influenced by operating and atmospheric conditions, but we would recommend that initially it be performed on a semi-annual basis. The period might then be extended to 9 or 12 months if experience shows this to be sufficient. . NSD DATA LETTER 74-2 - 2 - February 19, 1974 4. Cleaning. Clean the entire unit by blowing with dry instrument air (or a hand bellows), followed by vacuum cleaning. Particular attention should be paid to the cleanness of the undervoltage trip device, which can be inspected without component disassembly. 5. Solvents. In general, the use of a cleaning solvent is not encouraged since some can be damaging to electrical components. If there is a particularly heavy deposit of contaminants, an inert or mild solvent such as Stoddard solvent could be used if applied sparingly. 6. Lubricants. Although the Instruction Manual (page 5) cautions against any re-lubrication in the field, the manufacturers have agreed that the reliability of the breaker is improved by lightly lubricating the linkage of the undervoltage device occasionally. However, the lubricant should be applied only sparingly to the front and back faces of the vertical-traveling latch (interfacing with the flat copper-alloy spring). A dry or near-dry molybdenum disulfide lubricant should be used. Technical Bulletin NSD-TB-74-1 indicated Molykote G as a possible choice. That information is incorrect and is hereby rescinded Molykote G uses a thickened mineral oil as a vehicle, which would tend to collect foreign material. A better choice would be Molykote M-88, or Spray-kote. Both are commercially available Dow Corning products. 7. Inspection. Following the above cleaning and lubrication the entire breaker should be operationally checked and inspected for broken parts, loose bolts or excessive wear. This Date Letter and the above information supersedes Technical Bulletin NSD-TB-74-1, which is hereby cancelled. W. H. Furfari Electric Technology TECHNICAL OPERATIONS APPROVED: Syndey G. Caslake, Manager Electric Technology TECHNICAL OPERATIONS WHF/nev Attachment
Page Last Reviewed/Updated Tuesday, March 09, 2021
Page Last Reviewed/Updated Tuesday, March 09, 2021