Skip to main content

The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.

Part 21 Report - 1999-220

 

 

LICENSEE: COLTEC INDUSTRIES
SITE: ROCHESTER GAS AND ELECTRIC COR EN NUMBER:35567
DOCKET: EVENT DATE: 04-09-99
RX TYPE: EVENT TIME:
VENDORS: NOTIFY DATE: 04-09-99
EMERGENCY CLASS: N/A REGION: 1 STATE: NY TIME: 13:50
OPS OFFICER: CHAUNCEY GOULD  
10 CFR SECTION: CCCC UNSPECIFIED PARAGRAPH  

THE LICENSEE REPORTED A PART 21 DEFECT ON A REPLACEMENT TURBOCHARGER SUPPLIED BY COLTEC INDUSTRIES.

THE LICENSEE REPLACED A TURBOCHARGER(MODEL 730), SUPPLIED BY COLTEC INDUSTRIES, ON THEIR "B" EMERGENCY DIESEL GENERATOR (ALCO MODEL 16-251F) AT GINNA STATION. IT WAS DETERMINED THAT THERE WAS A MANUFACTURING DEFICIENCY IN THE REPLACEMENT TURBOCHARGER WHICH CONSISTED OF A MISSING DRAIN PORT IN THE INTERMEDIATE CASING ON THE TURBINE END WHICH WOULD PREVENT ENGINE LUBRICATING OIL FROM BEING ABLE TO DRAIN BACK TO THE ENGINE SUMP FROM THE TURBOCHARGER SHAFT AND BEARINGS. THIS DEFICIENCY CREATED A CONDITION WHERE ENGINE LUBE OIL WAS BEING DIRECTED INTO THE CYLINDERS THROUGH THE EXHAUST MANIFOLD PIPING, WHICH COULD HAVE RESULTED IN SERIOUS ENGINE DAMAGE.

Page Last Reviewed/Updated Thursday, August 27, 2026

Page Last Reviewed/Updated Thursday, August 27, 2026