Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Part 21 Report - 1997-070

LICENSEE: VICTOREEN, INC. SITE: VICTOREEN, INC. EN NUMBER:31692 DOCKET: EVENT DATE: 01-27-97 RX TYPE: EVENT TIME: 00:00 VENDORS: NOTIFY DATE: 01-30-97 EMERGENCY CLASS: N/A REGION: 3 STATE: OH TIME: 14:12 OPS OFFICER: LEIGH TROCINE 10 CFR SECTION: CCCC 21.21 UNSPECIFIED PARAGRAPH VICTOREEN INC. MADE A 10 CFR PART 21 NOTIFICATION REGARDING A DIGITAL DISPLAY UNIT. VICTOREEN INC. LOCATED AT 6000 COCHRAN ROAD IN CLEVELAND, OHIO, MADE A 10 CFR PART 21 NOTIFICATION THAT THEIR DIGITAL DISPLAY IN THE DIABLO CANYON NUCLEAR POWER PLANT CONTROL ROOM (RDU), FOR SAFETY-RELATED MONITOR R44B, STOPPED UPDATING (i.e, DISPLAY FROZEN). FURTHER TESTING DETERMINED THAT ALTHOUGH THE ALARM RELAY CHANGED STATE AFTER INPUTTING A TEST SIGNAL, THE RELAY OUTPUT AT THE RDU DID NOT. THIS IS AN UNIDENTIFIED FAILURE CONDITION IN THE DESIGN.