Part 21 Report - 1996-180
LICENSEE: COMMONWEALTH EDISON CO. SITE: BRAIDWOOD 1 2 EN NUMBER:29906 DOCKET: 05000456 05000457 EVENT DATE: 01-30-96 RX TYPE: PWR PWR EVENT TIME: 00:00 VENDORS: W-4-LP W-4-LP NOTIFY DATE: 01-30-96 EMERGENCY CLASS: N/A REGION: 3 STATE: IL TIME: 14:48 OPS OFFICER: RUDY KARSCH 10 CFR SECTION: CDEG 21.21(c)(3)(i) DEFECTS/NONCOMPLIANCE UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE CODE CRIT PWR PWR 1 N Y 100 POWER OPERATION 100 POWER OPERATION 2 N Y 100 POWER OPERATION 100 POWER OPERATION THE LICENSEE REPORTED SOLDERING DEFECTS IN RELAYS USED IN EMERGENCY DIESEL GENERATORS (EDGs) AT BYRON AND BRAIDWOOD STATIONS. RELAYS MANUFACTURED BY THE AMERACE CORPORATION HAVE A COMMERCIAL GRADE ADD-ON BOARD WITH COMPONENTS TO SUPPRESS A COIL DEENERGIZATION TRANSIENT. THE LICENSEE DISCOVERED THAT THE SOLDER CONNECTION BETWEEN THE RELAY AND THIS ADD-ON BOARD IS DEFECTIVE. THE FAILURE OF THIS RELAY COULD CAUSE THE EDG TO FAIL TO START. THE LICENSEE HAS REPAIRED THE DEFECTIVE SOLDER JOINTS AND REINSTALLED THE RELAYS. DEFECTIVE RELAYS COULD BE INSTALLED AT OTHER NUCLEAR PLANTS.
Page Last Reviewed/Updated Wednesday, March 24, 2021
Page Last Reviewed/Updated Wednesday, March 24, 2021