Part 21 Report - 1995-213
CLINTON 1 29426 10-06-95 POW
LICENSEE: ILLINOIS POWER CO.
SITE: .CLINTON 1 . EN NUMBER:29426
DOCKET: 05000461 EVENT DATE: 10-06-95
RX TYPE: BWR EVENT TIME: 11:49
VENDORS: GE-6 NOTIFY DATE: 10-06-95
EMERGENCY CLASS: N/A REGION: 3 STATE: IL TIME: 11:49
OPS OFFICER: JOSEPH SEBROSKY
10 CFR SECTION: CCCC 21.21 UNSPECIFIED PARAGRAPH
UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE
CODE CRIT PWR PWR
1 N Y 100 POWER OPERATION 100 POWER OPERATION
THE LICENSEE ISSUED A 10 CFR PART 21 REPORT DUE TO A PROBLEM WITH
A SOLID STATE TRIP DEVICE FOR ELECTRICAL BREAKERS.
ON AUGUST 7, 1995, DURING AN ATTEMPT TO SHIFT THE CONTROL ROOM
HEATING VENTILATING AND AIR CONDITIONING SYSTEM OPERATION FROM
THE A-TRAIN TO THE B-TRAIN, THE B-TRAIN RETURN AIR FAN WOULD NOT
START. AN INVESTIGATION FOUND THE FAN'S CIRCUIT BREAKER IN A
TRIPPED CONDITION. TROUBLESHOOTING LED TO REPLACEMENT OF THE
BREAKER. TESTING OF THE DEFICIENT BREAKER IDENTIFIED THAT ITS
SOLID STATE TRIP DEVICE WAS CAUSING THE BREAKER TO TRIP.
ILLINOIS POWER OFFICIALS RETURNED THE SOLID STATE TRIP DEVICE TO
THE MANUFACTURER FOR FURTHER TESTING.
ON AUGUST 21, 1995, ILLINOIS POWER IDENTIFIED ANOTHER POTENTIALLY
DEFICIENT SOLID STATE TRIP DEVICE. THIS DEVICE WAS INSTALLED IN
THE CIRCUIT BREAKER FOR THE 'B' SWITCHGEAR HEAT REMOVAL SYSTEM
CONDENSING UNIT MOTOR.
THE BASIC COMPONENTS INVOLVED ARE SOLID STATE TRIP DEVICES, TYPE
SS-13, MANUFACTURER PART NUMBER 609901-T012. THE DEVICES WERE
MANUFACTURED BY GOULD/ITE (NOW ABB, ASEA BROWN BOVERI). THE
LICENSEE DOES NOT INDICATE IN THE PART 21 REPORT THE TOTAL NUMBER
OF THIS TYPE OF TRIP DEVICES AT CLINTON OR OTHER NUCLEAR POWER
PLANTS. HOWEVER, THE LICENSEE DOES STATE THAT A MODEL SS-13
SOLID STATE TRIP DEVICE IS TYPICALLY INSTALLED ON AUXILIARY POWER
480-VOLT CIRCUIT BREAKERS USED FOR MOTOR CONTROL AT CLINTON.