The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.
Part 21 Report - 1995-156
ACCESSION #: 9507070477
ABB
ASEA BROWN BOVERI
June 28, 1995
Director, Office of Nuclear Reactor Regulation
U.S. Nuclear Regulatory Commission
Washington, DC 20555
Subject: Notification of Potential Defect per 10CFR Part 21
Type CVE-1 Relays
Notification by: Cheryl A. Dahle
Quality Manager
ABB Power T&D Company Inc.
Relay Division
4300 Coral Ridge Drive
Coral Springs, FL 33065
(305) 752-6700
This letter is a notification of a potential defect on the Class 1E type
CVE-1 relay style numbers 1326D67A01 and 1326D67A02. This defect
consists of an incorrectly rated telephone relay used as V1 and V2.
The Class 1E type CVE-1 relays are equipped with two 110 volts rated
telephone relays. The typical operating voltage in the field exceeds the
telephone relays (V1 and V2) rating; therefore, the telephone relays may
overheat and fail. To correct this, the design has been changed to a 120
volts rated telephone relay.
A copy of this notification is being sent to all customers who our
records indicate have purchased these type of relays.
If you have any questions or require any additional information regarding
this announcement, please do not hesitate to contact the Quality Manager
at the Relay Division.
Cheryl A. Dahle Jose R. Gierbolini
Quality Manager Profit Center Manager
Electromechanical Relays
ABB Power T&D Company Inc.
Relay 4300 Coral Ridge Drive Telephone: (305) 752-6700
Division Coral Springs, FL 33065 Telefax: (305) 345-5329
95MR009
*** END OF DOCUMENT ***
Page Last Reviewed/Updated Wednesday, March 24, 2021
Page Last Reviewed/Updated Wednesday, March 24, 2021