Skip to main content

The NRC is modernizing nrc.gov with an updated design and improved navigation to enhance usability. We are committed to a smooth transition and will work to minimize any disruption. The site may be briefly unavailable at times during launch. Thank you for your patience.

Part 21 Report - 1995-148

LICENSEE: ROCHESTER GAS & ELECTRIC CORP.
SITE: GINNA 1                               EN NUMBER:28955
DOCKET: 05000244                         EVENT DATE: 06-16-95
RX TYPE: PWR                             EVENT TIME: 00:00
VENDORS: W-2-LP                         NOTIFY DATE: 06-16-95
EMERGENCY CLASS: N/A  REGION: 1 STATE: NY      TIME: 10:25
OPS OFFICER: CHAUNCEY GOULD
10 CFR SECTION: CCCC  21.21               UNSPECIFIED PARAGRAPH
UNIT  SCRAM   RX   INIT  INITIAL MODE     CURR   CURRENT MODE
      CODE   CRIT  PWR                    PWR
 1    N       Y     97   POWER OPERATION   97   POWER OPERATION

THE LICENSEE REPORTED THAT THE BUTTERFLY VALVE MANUFACTURED BY
FISHER CONTROLS WAS SUPPLIED AS AN AIR-TO-OPEN VALVE INSTEAD OF
AN AIR-TO-CLOSE VALVE. THIS VALVE IS A BASIC COMPONENT IN THE
SERVICE WATER OUTLET FOR CONTAINMENT RECIRCULATION FAN COOLERS, A
SAFETY HAZARD COULD BE CREATED BY SUCH A DEFECT, WHICH WOULD
CAUSE THE LOSS OF SERVICE WATER TO THE FAN COOLERS. CORRECTIVE
ACTION WAS COMPLETED WHEN THEY ALTERED THE ACTUATOR LEVER WHICH
RESULTED IN THE VALVE FUNCTIONING CORRECTLY. THIS VALVE WAS
PURCHASED AS A REPLACEMENT FOR A SPECIFIC SERIAL NUMBERED ITEM.
THE ORIGINAL ENGINEERING REQUIREMENTS FOR THIS VALVE STIPULATED
AIR-TO-CLOSE OPERATION.


Page Last Reviewed/Updated Wednesday, March 24, 2021

Page Last Reviewed/Updated Wednesday, March 24, 2021