Part 21 Report - 1995-030
LICENSEE: COMMONWEALTH EDISON CO. SITE: DRESDEN 2 3 EN NUMBER:28285 DOCKET: 05000237 05000249 EVENT DATE: 01-26-95 RX TYPE: BWR BWR EVENT TIME: 15:45 VENDORS: GE-3 GE-3 NOTIFY DATE: 01-26-95 EMERGENCY CLASS: N/A REGION: 3 STATE: IL TIME: 17:43 OPS OFFICER: TIM McGINTY 10 CFR SECTION: ADEG 50.72(b)(1)(ii) DEGRAD COND DURING OP UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE CODE CRIT PWR PWR 2 N Y 99 POWER OPERATION 99 POWER OPERATION 3 N Y 99 POWER OPERATION 99 POWER OPERATION TIP SYSTEM ISOLATION VALVES WOULD RE-OPEN IF THE CONTROL SWITCHES WERE IN THE OPEN POSITION WHEN A GROUP 2 ISOLATION SIGNAL WAS RESET. THE SYSTEM ENGINEERING DEPARTMENT REPORTED THAT A REVIEW OF THE TRAVERSING IN-CORE PROBE (TIP) SYSTEM ISOLATION LOGIC PRINTS INDICATED THAT DRESDEN STATION HAS THE SAME DESIGN DEFICIENCY EXPERIENCED AT QUAD CITIES AND COOPER (SEE RELATED EVENT REPORTS 28281 & 28245, RESPECTIVELY). THIS DEFICIENCY WOULD ALLOW THE TIP SYSTEM ISOLATION VALVES TO AUTO RE-OPEN UPON RESET OF A GROUP 2 PRIMARY CONTAINMENT ISOLATION IF THE CONTROL SWITCHES ARE NOT LEFT IN THE "CLOSED" POSITION. DRESDEN STATIONS UPDATED REVISED FSAR STATES THAT THE ISOLATION LOGIC HAS BEEN MODIFIED TO PREVENT THE VALVES FROM AUTOMATICALLY OPENING WHEN THE ISOLATION SIGNAL IS RESET. THE PRINT REVIEW INDICATES THAT THE TIP SYSTEM ISOLATION VALVES WERE NOT INCLUDED IN THIS MODIFICATION, AND ARE THEREFORE OUTSIDE THE DESIGN BASES. ADMINISTRATIVE CONTROLS HAVE BEEN PLACED IN EFFECT TO ENSURE THAT TIP SYSTEM ISOLATION VALVE CONTROL SWITCHES ARE IN THE CLOSED POSITION, AND VALVES ARE VERIFIED CLOSED PRIOR TO RESET OF ANY GROUP 2 PRIMARY CONTAINMENT ISOLATION. THE LICENSEE WILL BE INVESTIGATING LONG-TERM CORRECTIVE ACTIONS, AND WILL INFORM THE RESIDENT INSPECTOR.
Page Last Reviewed/Updated Wednesday, March 24, 2021
Page Last Reviewed/Updated Wednesday, March 24, 2021