Morning Report for December 13, 2005
Headquarters Daily Report

REGION III
Manual Trip of Reactor
| Licensee/Facility: NUCLEAR MANAGEMENT CO., LLC Point Beach 1 TWO RIVERS, Wisconsin Dockets: 05000266 [1] W-2-LP License No: | Notification: MR Number: 3-2005-0023 Date: 12/13/2005 Call from Licensee |
Discussion:
At 3:39 a.m., control room operators manually tripped Unit 1 when main condenser vacuum began to decrease rapidly. Loss of vacuum would have resulted in an automatic reactor trip had the operators not manually tripped the reactor. The decrease in vacuum was caused by the failure of a running circulating water pump. The initial evaluation indicated a failure of the coupling between the pump and motor. The licensee is developing plans to evaluate the cause of the failure and repair the coupling. Plant equipment responded as designed to the trip.
Regional Action: The resident inspectors are following the licensee's evaluation of the cause of the coupling failure.
Accession Numbers:
| Accession No | Accession Date |
|---|---|
| ML053470321 | 12/13/2005 |