The U.S. Nuclear Regulatory Commission is in the process of rescinding or revising guidance and policies posted on this webpage in accordance with Executive Order 14151 Ending Radical and Wasteful Government DEI Programs and Preferencing, and Executive Order 14168 Defending Women From Gender Ideology Extremism and Restoring Biological Truth to the Federal Government. In the interim, any previously issued diversity, equity, inclusion, or gender-related guidance on this webpage should be considered rescinded that is inconsistent with these Executive Orders.

Morning Report for April 22, 2002

                       Headquarters Daily Report

                         APRIL 22, 2002

***************************************************************************
                    REPORT             NEGATIVE            NO INPUT
                    ATTACHED           INPUT RECEIVED      RECEIVED

HEADQUARTERS                           X
REGION I                               X
REGION II           X
REGION III                             X
REGION IV                              X
PRIORITY ATTENTION REQUIRED  MORNING REPORT - REGION II  APRIL 22, 2002

Licensee/Facility:                     Notification:

Duke Power Co.                         MR Number: 2-02-0007
Oconee 1                               Date: 04/22/02
Seneca,South Carolina
Dockets: 50-269
PWR/B&W-L-LP

Subject: SEVERED PLUGGED TUBE DISCOVERED IN STEAM GENERATOR

Discussion:

On April 15, 2002, the licensee informed the NRC that they had discovered
a severed plugged tube in the 1B steam generator during outage
inspections.  Tube 78-124 was severed at the lower tube sheet.  The
licensee found the severed tube when an adjacent tube's plug was pulled
for repair and wear scars were detected on it by eddy current
examination.  The licensee removed a section of the severed tube for
metallurgical examination and root cause analysis.

Regional Action:

Under the guidance of NRC Management Directive 8.3, Region II initiated a
Special Inspection on April 17, 2002.  The location of the severed tube
indicated that the failure mechanism was different than a recent severed
tube at Three Mile Island 1, as described in NRC Information Notice
2002-02, Recent Experience With Plugged Steam Generator Tubes.  The
specific issue of concern to be addressed by the inspection is to obtain
information so that the generic implications of the tube failure can be
assessed.

Contact:  JEROME BLAKE               (404)562-4607