Skip to main content

Event Notification Report for February 11, 2026

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
02/10/2026 - 02/11/2026

EVENT NUMBERS
581495815158160
Agreement State
Event Number: 58149
Rep Org: Georgia Radioactive Material Pgm
Licensee: St. Francis Health, LLC
Region: 1
City: Columbus   State: GA
County:
License #: GA 631-2
Agreement: Y
Docket:
NRC Notified By: Stacy Allman
HQ OPS Officer: Eric Simpson
Notification Date: 02/04/2026
Notification Time: 09:01 [ET]
Event Date: 01/12/2026
Event Time: 00:00 [EST]
Last Update Date: 02/04/2026
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
Bickett, Brice (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Event Text
AGREEMENT STATE REPORT - LEAKING SEALED SOURCE

The following information was provided by the Georgia Radioactive Materials Program (the Department) via email:

"On January 14, 2026, the licensee's radiation safety officer (RSO) notified the Department of a leaking check source found during a routine check on January 12, 2026. The vial had a visible defect, so the physicist immediately collected a wipe sample and placed the vial back in its shielded container. The container was sealed with tape, and all potentially contaminated items were triple bagged, sealed, labeled, and placed in storage in the hot lab. Area surveys and wipes were performed in the location where the source was located and no contamination was found. The RSO is currently in the process of obtaining quotes from disposal companies and will inform the Department when it is disposed.

"The Department will update with more information when obtained."

GA incident number: 113


Agreement State
Event Number: 58151
Rep Org: Florida Bureau of Radiation Control
Licensee: University of Miami
Region: 1
City: Miami   State: FL
County:
License #: 1319-1
Agreement: Y
Docket:
NRC Notified By: John A. Williamson
HQ OPS Officer: Ernest West
Notification Date: 02/04/2026
Notification Time: 17:57 [ET]
Event Date: 02/03/2026
Event Time: 00:00 [EST]
Last Update Date: 02/04/2026
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
Bickett, Brice (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Event Text
AGREEMENT STATE REPORT - MEDICAL EVENT

The following information was provided by the Florida Bureau of Radiation Control via email:

"A 68-year-old patient with metastatic castration-resistant prostate cancer treated with Xofigo Ra-223 dichloride was prescribed a dose of 171.6 microcuries and was treated on 02/03/2026. On 02/04/2026, the actual dose delivered was determined to be 118 microcuries. [The treating] physician has been informed. The patient will be notified on 02/05/2026 during a follow up appointment."

Incident number: FL26-011

A Medical Event may indicate potential problems in a medical facility's use of radioactive materials. It does not necessarily result in harm to the patient.


Non-Power Reactor
Event Number: 58160
Rep Org: Univ Of New Mexico (NEWM)
Licensee: University Of New Mexico
Region: 0
City: Albuquerque   State: NM
County: Bernalillo
License #: R-102
Agreement: Y
Docket: 05000252
NRC Notified By: Rowdy Davis
HQ OPS Officer: Adam Koziol
Notification Date: 02/10/2026
Notification Time: 16:48 [ET]
Event Date: 01/21/2026
Event Time: 14:00 [MST]
Last Update Date: 02/10/2026
Emergency Class: Non Emergency
10 CFR Section:
Person (Organization):
Helvenston, Edward (PM)
Waugh, Andrew (DANU)
Lin, Brian (DANU)
Farahmandfar, Zeinab (PM)
Event Text
TECHNICAL SPECIFICATION VIOLATION

The following information was provided by the licensee via phone:

On January 21, 2026, a technical specification (TS) violation was discovered per TS 3.4.d due to improper shielding during operation. The TS requires that the thermal column be filled with water or graphite, however, the thermal column contained water and lead. Since lead is not identified in the TS as a permissible shield, this was identified as a violation. The site will file a license amendment to add lead to the TS as an approved shielding material for the thermal column.

The licensee notified the NRC Project Manager and Inspector.