Event Notification Report for January 03, 2023

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/02/2023 - 01/03/2023

EVENT NUMBERS
56294
Power Reactor
Event Number: 56294
Facility: Vogtle
Region: 2     State: GA
Unit: [1] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: Devon Thompson
HQ OPS Officer: Ian Howard
Notification Date: 01/04/2023
Notification Time: 06:08 [ET]
Event Date: 01/03/2023
Event Time: 22:59 [EST]
Last Update Date: 01/05/2023
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation
Person (Organization):
Miller, Mark (R2DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
EN Revision Imported Date: 1/6/2023

EN Revision Text: LOSS OF OFFSITE POWER SOURCE

The following information was provided by the licensee via email:

"At 2259 EST on 1/3/2023, with Unit 1 and Unit 2 in Mode 1 at 100 percent power, an actuation of the Unit 1 B and Unit 2 A emergency diesel generator (EDG) systems, as well as an actuation of the associated auxiliary feedwater (AFW) systems on each unit occurred. The reason for the EDG auto-starts was due to a loss of an offsite power source (loss of one of the two reserve auxiliary transformers (RAT) on each unit) to the Unit 1 B and Unit 2 A safety related buses. The EDG and AFW systems automatically started as designed when the valid undervoltage signal on the affected safety related bus was received.

"This event is being reported as an eight-hour, non-emergency notification per 10 CFR 50.72(b)(3)(iv)(A) as an event that results in a valid actuation of the Emergency Diesel Generator and the Auxiliary Feedwater Systems for both Unit 1 and Unit 2.

"There was no impact on the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified."