Skip to main content

Alert

Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for August 15, 2022

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
08/14/2022 - 08/15/2022

Agreement State
Event Number: 56033
Rep Org: California Department of Public Health
Licensee: Advanced Geotechnical Solutions, Inc.
Region: 4
City: San Diego   State: CA
County:
License #: 7856-37
Agreement: Y
Docket:
NRC Notified By: L. Robert Greger
HQ OPS Officer: Karen Cotton-Gross
Notification Date: 08/05/2022
Notification Time: 15:46 [ET]
Event Date: 03/06/2021
Event Time: 00:00 [PDT]
Last Update Date: 08/08/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
Roldan-Otero, Lizette (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL)
CNSNS (Mexico), - (EMAIL)
Event Text
EN Revision Imported Date: 8/8/2022

EN Revision Text: AGREEMENT STATE REPORT - THEFT OF RADIOACTIVE GAUGE

The following information was provided by the licensee via email:
During an inspection on 7/26/22, the RSO [Radiation Safety Officer] of Advanced Geotechnical Solutions stated that on March 6, 2021, an Authorized User of radioactive gauges for Advanced Geotechnical Solutions discovered that his SUV had been broken into and the radioactive gauge Troxler, 3430, serial #70783 that he had checked out from the permanent storage site at [REDACTED], had been stolen. The Authorized User had transported the radioactive gauge to his personal residence and left it locked in his vehicle rather than transport it back to the permanent storage location in Escondido. The Authorized User reported the theft to his RSO, and to the San Diego Police Department, and the RSO reported the theft to Cal OES [California Governor's Office of Emergency Services] on 3/7/21, instead of to the Brea, CA office since it was a weekend. The report of the lost gauge apparently did not get to the Brea office, and consequently no investigation was conducted, nor was the theft reported to NRC.

The RSO had contacted local newspapers in an attempt to retrieve the stolen radioactive gauge, as well as notifying local servicing vendors of radioactive gauges to be alert for the serial number of the stolen gauge in case it turns up for service, but the gauge has not been recovered. The investigation is ongoing, including why the Cal OES report did not get to the Brea, CA, RHB [Radiologic Health Branch] inspection office.



THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf


Agreement State
Event Number: 56034
Rep Org: MA Radiation Control Program
Licensee: PETNET Solutions
Region: 1
City: Woburn   State: MA
County:
License #: 42-0650
Agreement: Y
Docket:
NRC Notified By: Tony Carpenito
HQ OPS Officer: Mike Stafford
Notification Date: 08/05/2022
Notification Time: 16:56 [ET]
Event Date: 08/05/2022
Event Time: 00:00 [EDT]
Last Update Date: 08/05/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
Henrion, Mark (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Event Text
AGREEMENT STATE REPORT - POTENTIAL OVEREXPOSURE TO EXTREMITY

The following information was received from the Massachusetts Radiation Control Program (the Agency) via email:

"Licensee reported employee weekly finger ring exposure exceeding 50 rem (67.569 rem for wear period, 7/4/22-7/10/22) a situation reportable within 24 hours per 105 CMR 120.282 (B) (1) (c). The other finger ring dosimeter worn by the subject employee received 31.509 rem exposure for same wear period. Exact cause of exposure not yet known. Licensee investigation ongoing. Licensee, a radiopharmaceutical manufacturer/distributer, stated that subject employee does perform work involved with F-18 radiopharmaceutical manufacturing operations.

"The Agency considers this matter still open."

MA Event Number: TBD


Agreement State
Event Number: 56035
Rep Org: Illinois Emergency Mgmt. Agency
Licensee: Cleveland-Cliffs Riverdale, LLC
Region: 3
City: Riverdale   State: IL
County:
License #: IL-01636-01
Agreement: Y
Docket:
NRC Notified By: Gary Forsee
HQ OPS Officer: Ernest West
Notification Date: 08/07/2022
Notification Time: 15:21 [ET]
Event Date: 08/07/2022
Event Time: 09:22 [CDT]
Last Update Date: 08/07/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
Ruiz, Robert (R3DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Event Text
AGREEMENT STATE REPORT - DAMAGED GAUGE

The following information was provided by the Illinois Emergency Management Agency (The Agency) via email:

"The RSO for Cleveland-Cliffs Riverdale, LLC, contacted the Agency Operations Center on 8/7/22 to report a mold had failed during casting at their Riverdale, IL facility at approximately 0922 CDT that morning. The incident resulted in molten steel overflowing onto a radioactive source holder which contained a 46.5 mCi Co-60 source in a Berthold LB300MLT holder.

"Reportedly, the top of the source holder was sheared off and the shutter stuck open. Operators are routinely more than six feet away at the time of casting - and were further away during the accident - in large part due to the heat. Exposure rates were recorded at a maximum of 20 mR/hour directly above the source holder on the mold. Six inches above the mold, the exposure rate drops to 2 mR/hour. The area has been blocked off and boundaries surveyed at 0.1 mR/hour. A leak test is being collected, but the licensee is not capable/authorized to perform analysis.

"The manufacturer's representative, Radiametrics Technologies, will be on site tomorrow (8/8/22) to assess, remove from service, and properly package the source for transport. They are bringing a spare source holder. Agency inspectors will perform a reactive inspection to verify conditions did not result in any public or worker exposures and that the damage to the source did not result in any contamination."

Illinois reference number: IL220028


Agreement State
Event Number: 56036
Rep Org: Colorado Dept of Health
Licensee: Service King #340
Region: 4
City: Colorado Springs   State: CO
County:
License #: GL002527
Agreement: Y
Docket:
NRC Notified By: Kathryn Kirk
HQ OPS Officer: Ernest West
Notification Date: 08/08/2022
Notification Time: 17:41 [ET]
Event Date: 07/11/2022
Event Time: 00:00 [MDT]
Last Update Date: 08/08/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
O'Keefe, Neil (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL)
Event Text
AGREEMENT STATE REPORT- LOST STATIC ELIMINATOR

The following summary was received from the Colorado Department of Public Health and Environment via email:

The Colorado Department of Public Health and Environment reported one NRD, LLC static eliminator, model number P-2021, containing 0.01 Ci of Po-210 was lost by the licensee [Service King #340]. The incident occurred July 11, 2022.

CO Event Report ID no.: CO220027

THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf


Agreement State
Event Number: 56037
Rep Org: Colorado Dept of Health
Licensee: Service King #344
Region: 4
City: Colorado Springs   State: CO
County:
License #: GL002625
Agreement: Y
Docket:
NRC Notified By: Kathryn Kirk
HQ OPS Officer: Ernest West
Notification Date: 08/08/2022
Notification Time: 17:44 [ET]
Event Date: 07/11/2022
Event Time: 00:00 [MDT]
Last Update Date: 08/08/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
O'Keefe, Neil (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL)
Event Text
AGREEMENT STATE REPORT- LOST STATIC ELIMINATOR

The following summary was received from the Colorado Department of Public Health and Environment via email:

The Colorado Department of Public Health and Environment reported one NRD, LLC static eliminator, model number P-2021, containing 0.01 Ci of Po-210 was lost by the licensee [Service King #344]. The incident occurred July 11, 2022.

CO Event Report ID no.: CO220028

THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf


Power Reactor
Event Number: 56044
Facility: Palo Verde
Region: 4     State: AZ
Unit: [1] [3] []
RX Type: [1] CE,[2] CE,[3] CE
NRC Notified By: Joshua McDowell
HQ OPS Officer: Karen Cotton-Gross
Notification Date: 08/15/2022
Notification Time: 01:18 [ET]
Event Date: 08/14/2022
Event Time: 17:02 [MST]
Last Update Date: 08/15/2022
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation
Person (Organization):
O'Keefe, Neil (R4DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
3 N Y 100 Power Operation 100 Power Operation
Event Text
VALID ACTUATIONS OF UNIT 1 AND UNIT 3 EMERGENCY DIESEL GENERATORS AND UNIT 1 AUXILIARY FEEDWATER PUMP

The following information was provided by the licensee via phone and email:

"At 1702 MST on August 14, 2022, a start-up transformer de-energized, resulting in a loss of power to the Unit 1 Train B 4.16 kV Class 1E Bus and the Unit 3 Train A 4.16 kV Class 1E Bus. The Unit 1 Train B Emergency Diesel Generator (EDG) and Unit 3 Train A EDG automatically started and energized their respective 4.16 kV Class 1E Buses. As a result of the loss of power on the Unit 1 Train B 4.16 kV Class 1E Bus, the B Auxiliary Feedwater Pump automatically started, as expected. The B Auxiliary Feedwater Pump was not needed for steam generator level control and no auxiliary feedwater valves repositioned. The B Auxiliary Feedwater Pump did not supply feedwater to the steam generators.

"This event is being reported in accordance with 10 CFR 50.72(b)(3)(iv)(A) as an event that results in a valid actuation of emergency AC electrical power systems and an auxiliary feedwater system.

"All systems operated as expected. Per the Emergency Plan, no classification was required due to the event. The 4.16 kV Class 1E Buses in Unit 2 were not affected by the de-energization of the start-up transformer since it was not aligned as normal power for Unit 2. Units 1, 2 and 3 remain in Mode 1 at 100% power.

"The cause of the start-up transformer being de-energized is under investigation. No plant transient occurred as a result of this failure.

"The NRC Resident Inspectors have been informed."