Skip to main content

Alert

Due to a lapse in appropriations, the NRC has ceased normal operations. However, excepted and exempted activities necessary to maintain critical health and safety functions—as well as essential progress on designated critical activities, including those specified in Executive Order 14300—will continue, consistent with the OMB-Approved NRC Lapse Plan.

Event Notification Report for April 04, 2022

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
04/03/2022 - 04/04/2022

Agreement State
Event Number: 55803
Rep Org: SC Dept of Health & Env Control
Licensee: International Paper-Georgetown Mill
Region: 1
City: Georgetown   State: SC
County:
License #: 060
Agreement: Y
Docket:
NRC Notified By: Andrew M. Roxburgh
HQ OPS Officer: Mike Stafford
Notification Date: 03/28/2022
Notification Time: 04:45 [ET]
Event Date: 03/27/2022
Event Time: 14:00 [EDT]
Last Update Date: 03/28/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
Jackson, Don (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Event Text
EN Revision Imported Date: 4/5/2022

EN Revision Text: AGREEMENT STATE REPORT - DAMAGE TO GAUGE FROM FIRE

The following event was received from the South Carolina Department of Health [the Department] via email:

"On 3/27/2022, the Department was notified by the licensee's [radiation safety officer] RSO that one of its fixed gauges was damaged during a fire at the plant. The fixed gauge is a TN Technologies Model 5206 containing 200 mCi of Cs-137. The licensee took radiation readings around the gauge and has contacted System Services. Systems Services is arriving on the evening of 3/27/22 to service the gauge. The licensee's radiation readings were 3 mR/hr on the surface of the bottom of the gauge, 250 mR/hr on the top of the gauge. The licensee also took a radiation reading on the walkway three feet above the gauge and the reading was 0.3 mR/hr. The licensee also took a reading at the bottom of the ladder, and it was 0.1 mR/hr. The licensee has barricaded roped off areas on the walkway and at the bottom of the ladder. The gauge is located approximately 12 feet off the floor and is not readily accessible by employees."


Agreement State
Event Number: 55805
Rep Org: NJ Dept of Environmental Protection
Licensee: Merck (Schering)
Region: 1
City: Rahway   State: NJ
County:
License #: 456557
Agreement: Y
Docket:
NRC Notified By: Sarah Sanderlin
HQ OPS Officer: Kerby Scales
Notification Date: 03/28/2022
Notification Time: 15:25 [ET]
Event Date: 03/28/2022
Event Time: 00:00 [EDT]
Last Update Date: 03/28/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
Werkheiser, Dave (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL)
Event Text
EN Revision Imported Date: 4/5/2022

EN Revision Text: AGREEMENT STATE REPORT - LOST MASS SPEC-GAS CHROMATOGRAPH

The following information was received from the state of New Jersey Bureau of Environmental Radiation (the Bureau), Radioactive Materials Program (RMP) via email:

"On 3/28/2022 RMP staff was notified via [Radiation Safety Officer] RSO that a mass spec-gas chromatograph with a 15 mCi Ni-63 source (S/N U11650) was sold from their Rahway site without the source being removed. On 10/18/2021, the unit was moved to a surplus warehouse in Kenilworth, NJ. At the time it arrived at the warehouse, the radiation safety label was removed. On 12/30/2021, the unit was sold by the contract service. The RSO will update the Bureau throughout their investigation to find the root cause."


THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf


Power Reactor
Event Number: 55818
Facility: Browns Ferry
Region: 2     State: AL
Unit: [3] [] []
RX Type: [1] GE-4,[2] GE-4,[3] GE-4
NRC Notified By: Chase Hensley
HQ OPS Officer: Donald Norwood
Notification Date: 04/02/2022
Notification Time: 15:10 [ET]
Event Date: 04/02/2022
Event Time: 13:45 [CDT]
Last Update Date: 04/02/2022
Emergency Class: Unusual Event
10 CFR Section:
50.72(a) (1) (i) - Emergency Declared
Person (Organization):
Miller, Mark (R2DO)
Kennedy, Silas (IR)
Dudes, Laura (R2RA)
Veil, Andrea (NRR)
Screnci, Diane (PAO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 N Y 10 Power Operation 10 Power Operation
Event Text
EN Revision Imported Date: 4/4/2022

EN Revision Text: UNUSUAL EVENT DECLARED DUE TO A FIRE AT THE 3B REACTOR FEEDWATER PUMP

The following information was provided by the licensee via fax:

"At 1345 CDT, Browns Ferry declared a Notification of Unusual Event due to a fire at the 3B Reactor Feedwater Pump within the Turbine Building which was not extinguished within 15 minutes. Subsequently, the fire was extinguished at 1402 CDT. Unit 3 remains in Mode 1 at approximately 9.5 percent rated thermal power (RTP). Unit 1 and 2 remain at 100 percent RTP and unaffected."

The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:

The fire began at 1332 CDT. It is believed that the fire was in the oil system of the Feedwater Pump. The fire was extinguished by the on-site fire brigade. No off-site assistance was requested. The Unusual Event was declared under Emergency Action Level HU-4. The licensee notified the NRC Resident Inspector and required State and local government agencies. Unit 3 is currently stable.

Notified DHS-SWO, FEMA Ops Center, and CISA Central Watch Officer, and FEMA NWC, DHS NRCC THD Desk, and DHS NuclearSSA via email.

* * * UPDATE FROM CHASE HENSLEY TO DONALD NORWOOD AT 1650 EDT ON 4/2/2022 * * *

"The Notification of Unusual Event was exited at 1544 CDT."

Notified R2DO (Miller), IR-MOC (Kennedy), NRR-EO (Felts), DHS-SWO, FEMA Ops Center, and CISA Central Watch Officer.


Agreement State
Event Number: 55806
Rep Org: New York State Dept. of Health
Licensee: Northwell Health Imaging
Region: 1
City: Lake Success   State: NY
County:
License #: 5255
Agreement: Y
Docket:
NRC Notified By: Daniel Samson
HQ OPS Officer: Howie Crouch
Notification Date: 03/29/2022
Notification Time: 09:34 [ET]
Event Date: 03/17/2022
Event Time: 00:00 [EDT]
Last Update Date: 03/29/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
Person (Organization):
Werkheiser, Dave (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL)
CNSC (Canada), - (Email)
Event Text
EN Revision Imported Date: 4/5/2022

EN Revision Text: AGREEMENT STATE REPORT - LOST GD-153 and CO-57 SOURCES

The following information was received from the state of New York (NYSDOH) via fax:

"Four transmission/reference/calibration sources were shipped out in two separate shipments via [a common carrier] to Eckert & Ziegler on 3/17/2022 under two-day shipping and have been listed as 'delayed' since 3/18/2022. Upon contacting [the common carrier], an incident (No. C-61803614) was opened to attempt to locate the sources as [the common carrier] was unable to locate the two shipments. The licensee formally reported the sources as missing to NYSDOH on 3/28/2022.

"The Gd-153 source, (1.27 mCi as of 3/17/22), is deemed a reportable quantity under 20.2201 (a)(1)(ii), as greater than 10 times the Appendix C to Part 20 value (10 microCi), but less than 1000 times. The three other sources (Cobalt-57) fall below the values in Appendix C of 10 CFR 20 and are not reportable under 10 CFR 20.2201.

"The licensee is continuing to contact [the common carrier] regarding these sources and keeping NYSDOH updated on the status. NYS is consistently monitoring this situation under Incident No. 1389:
Device Manufacturer: Eckart & Zeigler
Device Model: TBD
Device S/N: S5-864
Source Manufacturer: Eckart & Zeigler
Source Model: TBD
Source S/N: S5-864
Isotope: Gd-153
Activity: 1.27 millicuries on 3/17/2022 (10 mCi assayed on 4/1/2020)

THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL

Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf


Part 21
Event Number: 55807
Rep Org: Engine Systems, Inc.
Licensee: Engine Systems, Inc.
Region: 2
City: Rocky Mount   State: NC
County:
License #:
Agreement: Y
Docket:
NRC Notified By: Dan Roberts
HQ OPS Officer: Karen Cotton-Gross
Notification Date: 03/29/2022
Notification Time: 16:38 [ET]
Event Date: 01/27/2022
Event Time: 00:00 [EDT]
Last Update Date: 03/29/2022
Emergency Class: Non Emergency
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
Person (Organization):
Miller, Mark (R2DO)
Part 21/50.55 Reactors, - (EMAIL)
Event Text
EN Revision Imported Date: 4/5/2022

EN Revision Text: PART 21 - ELECTRO-MOTIVE DIESEL (EMD) CYLINDER HEAD WITH FIREFACE THICKNESS BELOW SPECIFICATION

The following is a summary of the information provided by Engine Systems, Inc. (ESI) via fax:

ESI reported that a fatigue crack was discovered in the fireface of an EMD cylinder head, P/N 40121485, D/C 18K, installed on an emergency diesel generator set. The crack initiated on the coolant side and propagated through the fireface wall of the combustion side resulting in a water leak. Fatigue failure was likely caused by a reduced fireface thickness which reduced overall rigidity of the fireface, allowing increased deformation and ultimately failure due to high tensile stress at the blend between the fireface and valve seat. A reduced fireface thickness could result in a through wall crack that would introduce jacket water into the combustion chamber. Over time if the crack propagated or went undetected engine damage may occur. Ultimately, a crack in the fireface could lead to a failure of the diesel engine which would prevent the emergency diesel generator set from performing during a safety-event.

This Part 21 applies to the Cylinder heads from D/C 18K, supplied within some power pack assemblies at Watts Bar Nuclear Power Plant.

Corrective Actions:
ESI recommends an ultrasonic thickness inspection on the fireface to confirm thickness is within specified range to plants with these power pack assemblies. ESI has also revised its dedication package to increase the number of ultrasonic thickness inspection points. An additional enhancement is the inclusion of an inspection map for guidance and clarity of the locations to be measured. The revision was implemented on March 15, 2022.

Technical questions concerning this notification can be directed to Dan Roberts, Quality Manager and John Kriesel, Engineering Manager at (252) 977-2720.