Event Notification Report for April 01, 2022
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
03/31/2022 - 04/01/2022
Power Reactor
Event Number: 55808
Facility: Summer
Region: 2 State: SC
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-AP1000,[3] W-AP1000
NRC Notified By: Justin Bouknight
HQ OPS Officer: Brian Lin
Region: 2 State: SC
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-AP1000,[3] W-AP1000
NRC Notified By: Justin Bouknight
HQ OPS Officer: Brian Lin
Notification Date: 03/30/2022
Notification Time: 09:43 [ET]
Event Date: 06/22/2021
Event Time: 00:00 [EST]
Last Update Date: 03/30/2022
Notification Time: 09:43 [ET]
Event Date: 06/22/2021
Event Time: 00:00 [EST]
Last Update Date: 03/30/2022
Emergency Class: Non Emergency
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
Person (Organization):
Miller, Mark (R2DO)
Part 21/50.55 Reactors, - (EMAIL)
Miller, Mark (R2DO)
Part 21/50.55 Reactors, - (EMAIL)
Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
---|---|---|---|---|---|---|
1 | N | Y | 100 | Power Operation | 100 | Power Operation |
EN Revision Imported Date: 4/1/2022
EN Revision Text: PART 21 - POPPET SEAL FAILURE
The following information was provided by the licensee via fax or email:
"This is a non-emergency notification required by 10 CFR 21.21(d)(3)(i). A written notification in accordance with 10 CFR 21.21(d)(3)(ii) will be provided within 30 days.
"On June 22, 2021, VC Summer Nuclear Station (VCSNS) received information indicating that a poppet seal failure in the Feedwater Isolation Valve (FWIV) 'B' control block was due to laminations in the Viton material. The failure occurred on May 12, 2021 and was captured in the corrective action program as CR-21-01263.
"VCSNS completed a Substantial Safety Hazard Evaluation and determined that the laminations in VCSNS poppet seal lots 7064051 and 7081558 constituted a substantial safety hazard. The FWIV poppet seals are responsible for retaining and directing pressurized air to each side of the FWIV actuator for repositioning and maintaining FWIV position in both the open and closed positions.
"The NRC Senior Resident Inspector has been notified."
EN Revision Text: PART 21 - POPPET SEAL FAILURE
The following information was provided by the licensee via fax or email:
"This is a non-emergency notification required by 10 CFR 21.21(d)(3)(i). A written notification in accordance with 10 CFR 21.21(d)(3)(ii) will be provided within 30 days.
"On June 22, 2021, VC Summer Nuclear Station (VCSNS) received information indicating that a poppet seal failure in the Feedwater Isolation Valve (FWIV) 'B' control block was due to laminations in the Viton material. The failure occurred on May 12, 2021 and was captured in the corrective action program as CR-21-01263.
"VCSNS completed a Substantial Safety Hazard Evaluation and determined that the laminations in VCSNS poppet seal lots 7064051 and 7081558 constituted a substantial safety hazard. The FWIV poppet seals are responsible for retaining and directing pressurized air to each side of the FWIV actuator for repositioning and maintaining FWIV position in both the open and closed positions.
"The NRC Senior Resident Inspector has been notified."
Agreement State
Event Number: 55803
Rep Org: SC Dept of Health & Env Control
Licensee: International Paper-Georgetown Mill
Region: 1
City: Georgetown State: SC
County:
License #: 060
Agreement: Y
Docket:
NRC Notified By: Andrew M. Roxburgh
HQ OPS Officer: Mike Stafford
Licensee: International Paper-Georgetown Mill
Region: 1
City: Georgetown State: SC
County:
License #: 060
Agreement: Y
Docket:
NRC Notified By: Andrew M. Roxburgh
HQ OPS Officer: Mike Stafford
Notification Date: 03/28/2022
Notification Time: 04:45 [ET]
Event Date: 03/27/2022
Event Time: 14:00 [EDT]
Last Update Date: 03/28/2022
Notification Time: 04:45 [ET]
Event Date: 03/27/2022
Event Time: 14:00 [EDT]
Last Update Date: 03/28/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
Jackson, Don (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Jackson, Don (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
EN Revision Imported Date: 4/4/2022
EN Revision Text: AGREEMENT STATE REPORT - DAMAGE TO GAUGE FROM FIRE
The following event was received from the South Carolina Department of Health [the Department] via email:
"On 3/27/2022, the Department was notified by the licensee's [radiation safety officer] RSO that one of its fixed gauges was damaged during a fire at the plant. The fixed gauge is a TN Technologies Model 5206 containing 200 mCi of Cs-137. The licensee took radiation readings around the gauge and has contacted System Services. Systems Services is arriving on the evening of 3/27/22 to service the gauge. The licensee's radiation readings were 3 mR/hr on the surface of the bottom of the gauge, 250 mR/hr on the top of the gauge. The licensee also took a radiation reading on the walkway three feet above the gauge and the reading was 0.3 mR/hr. The licensee also took a reading at the bottom of the ladder, and it was 0.1 mR/hr. The licensee has barricaded roped off areas on the walkway and at the bottom of the ladder. The gauge is located approximately 12 feet off the floor and is not readily accessible by employees."
EN Revision Text: AGREEMENT STATE REPORT - DAMAGE TO GAUGE FROM FIRE
The following event was received from the South Carolina Department of Health [the Department] via email:
"On 3/27/2022, the Department was notified by the licensee's [radiation safety officer] RSO that one of its fixed gauges was damaged during a fire at the plant. The fixed gauge is a TN Technologies Model 5206 containing 200 mCi of Cs-137. The licensee took radiation readings around the gauge and has contacted System Services. Systems Services is arriving on the evening of 3/27/22 to service the gauge. The licensee's radiation readings were 3 mR/hr on the surface of the bottom of the gauge, 250 mR/hr on the top of the gauge. The licensee also took a radiation reading on the walkway three feet above the gauge and the reading was 0.3 mR/hr. The licensee also took a reading at the bottom of the ladder, and it was 0.1 mR/hr. The licensee has barricaded roped off areas on the walkway and at the bottom of the ladder. The gauge is located approximately 12 feet off the floor and is not readily accessible by employees."
Agreement State
Event Number: 55805
Rep Org: NJ Dept of Environmental Protection
Licensee: Merck (Schering)
Region: 1
City: Rahway State: NJ
County:
License #: 456557
Agreement: Y
Docket:
NRC Notified By: Sarah Sanderlin
HQ OPS Officer: Kerby Scales
Licensee: Merck (Schering)
Region: 1
City: Rahway State: NJ
County:
License #: 456557
Agreement: Y
Docket:
NRC Notified By: Sarah Sanderlin
HQ OPS Officer: Kerby Scales
Notification Date: 03/28/2022
Notification Time: 15:25 [ET]
Event Date: 03/28/2022
Event Time: 00:00 [EDT]
Last Update Date: 03/28/2022
Notification Time: 15:25 [ET]
Event Date: 03/28/2022
Event Time: 00:00 [EDT]
Last Update Date: 03/28/2022
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
Werkheiser, Dave (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL)
Werkheiser, Dave (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL)
EN Revision Imported Date: 4/4/2022
EN Revision Text: AGREEMENT STATE REPORT - LOST MASS SPEC-GAS CHROMATOGRAPH
The following information was received from the state of New Jersey Bureau of Environmental Radiation (the Bureau), Radioactive Materials Program (RMP) via email:
"On 3/28/2022 RMP staff was notified via [Radiation Safety Officer] RSO that a mass spec-gas chromatograph with a 15 mCi Ni-63 source (S/N U11650) was sold from their Rahway site without the source being removed. On 10/18/2021, the unit was moved to a surplus warehouse in Kenilworth, NJ. At the time it arrived at the warehouse, the radiation safety label was removed. On 12/30/2021, the unit was sold by the contract service. The RSO will update the Bureau throughout their investigation to find the root cause."
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
EN Revision Text: AGREEMENT STATE REPORT - LOST MASS SPEC-GAS CHROMATOGRAPH
The following information was received from the state of New Jersey Bureau of Environmental Radiation (the Bureau), Radioactive Materials Program (RMP) via email:
"On 3/28/2022 RMP staff was notified via [Radiation Safety Officer] RSO that a mass spec-gas chromatograph with a 15 mCi Ni-63 source (S/N U11650) was sold from their Rahway site without the source being removed. On 10/18/2021, the unit was moved to a surplus warehouse in Kenilworth, NJ. At the time it arrived at the warehouse, the radiation safety label was removed. On 12/30/2021, the unit was sold by the contract service. The RSO will update the Bureau throughout their investigation to find the root cause."
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Power Reactor
Event Number: 55818
Facility: Browns Ferry
Region: 2 State: AL
Unit: [3] [] []
RX Type: [1] GE-4,[2] GE-4,[3] GE-4
NRC Notified By: Chase Hensley
HQ OPS Officer: Donald Norwood
Region: 2 State: AL
Unit: [3] [] []
RX Type: [1] GE-4,[2] GE-4,[3] GE-4
NRC Notified By: Chase Hensley
HQ OPS Officer: Donald Norwood
Notification Date: 04/02/2022
Notification Time: 15:10 [ET]
Event Date: 04/02/2022
Event Time: 13:45 [CDT]
Last Update Date: 04/02/2022
Notification Time: 15:10 [ET]
Event Date: 04/02/2022
Event Time: 13:45 [CDT]
Last Update Date: 04/02/2022
Emergency Class: Unusual Event
10 CFR Section:
50.72(a) (1) (i) - Emergency Declared
10 CFR Section:
50.72(a) (1) (i) - Emergency Declared
Person (Organization):
Miller, Mark (R2DO)
Kennedy, Silas (IR)
Dudes, Laura (R2RA)
Veil, Andrea (NRR)
Screnci, Diane (PAO)
Miller, Mark (R2DO)
Kennedy, Silas (IR)
Dudes, Laura (R2RA)
Veil, Andrea (NRR)
Screnci, Diane (PAO)
Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
---|---|---|---|---|---|---|
3 | N | Y | 10 | Power Operation | 10 | Power Operation |
EN Revision Imported Date: 4/4/2022
EN Revision Text: UNUSUAL EVENT DECLARED DUE TO A FIRE AT THE 3B REACTOR FEEDWATER PUMP
The following information was provided by the licensee via fax:
"At 1345 CDT, Browns Ferry declared a Notification of Unusual Event due to a fire at the 3B Reactor Feedwater Pump within the Turbine Building which was not extinguished within 15 minutes. Subsequently, the fire was extinguished at 1402 CDT. Unit 3 remains in Mode 1 at approximately 9.5 percent rated thermal power (RTP). Unit 1 and 2 remain at 100 percent RTP and unaffected."
The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:
The fire began at 1332 CDT. It is believed that the fire was in the oil system of the Feedwater Pump. The fire was extinguished by the on-site fire brigade. No off-site assistance was requested. The Unusual Event was declared under Emergency Action Level HU-4. The licensee notified the NRC Resident Inspector and required State and local government agencies. Unit 3 is currently stable.
Notified DHS-SWO, FEMA Ops Center, and CISA Central Watch Officer, and FEMA NWC, DHS NRCC THD Desk, and DHS NuclearSSA via email.
* * * UPDATE FROM CHASE HENSLEY TO DONALD NORWOOD AT 1650 EDT ON 4/2/2022 * * *
"The Notification of Unusual Event was exited at 1544 CDT."
Notified R2DO (Miller), IR-MOC (Kennedy), NRR-EO (Felts), DHS-SWO, FEMA Ops Center, and CISA Central Watch Officer.
EN Revision Text: UNUSUAL EVENT DECLARED DUE TO A FIRE AT THE 3B REACTOR FEEDWATER PUMP
The following information was provided by the licensee via fax:
"At 1345 CDT, Browns Ferry declared a Notification of Unusual Event due to a fire at the 3B Reactor Feedwater Pump within the Turbine Building which was not extinguished within 15 minutes. Subsequently, the fire was extinguished at 1402 CDT. Unit 3 remains in Mode 1 at approximately 9.5 percent rated thermal power (RTP). Unit 1 and 2 remain at 100 percent RTP and unaffected."
The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:
The fire began at 1332 CDT. It is believed that the fire was in the oil system of the Feedwater Pump. The fire was extinguished by the on-site fire brigade. No off-site assistance was requested. The Unusual Event was declared under Emergency Action Level HU-4. The licensee notified the NRC Resident Inspector and required State and local government agencies. Unit 3 is currently stable.
Notified DHS-SWO, FEMA Ops Center, and CISA Central Watch Officer, and FEMA NWC, DHS NRCC THD Desk, and DHS NuclearSSA via email.
* * * UPDATE FROM CHASE HENSLEY TO DONALD NORWOOD AT 1650 EDT ON 4/2/2022 * * *
"The Notification of Unusual Event was exited at 1544 CDT."
Notified R2DO (Miller), IR-MOC (Kennedy), NRR-EO (Felts), DHS-SWO, FEMA Ops Center, and CISA Central Watch Officer.